Smart Temperature Transmitter STT250 – Operator Manual
31
•
Step 2
- Press and hold side button on meter. Release the button when "
CAL
"
appears on the display. The meter will now carry out a zero (LRV) calibration and
revert to normal operation. Press "
OUTPUT
", "
CLEAR
" to revert transmitter to
continuous output operation.
•
Step 3
- Change output mode value to 100% by pressing "
OUTPUT
", "
1
", "
0
", "
0
",
"
ENTER
".
•
Step 4
- Press and hold side button on meter. Release button when "
CAL
"
appears on the display. The meter will now carry out a span (URV) calibration and
revert to normal operation. Press "
OUTPUT
", "
CLEAR
" to revert transmitter to
continuous output operation. Return loop to Automatic operation.
ATTENTION
- If "
bAd
" appears on the meter display after Step 2 or 4 then the
4 mA or the 20 mA signal was not within the meter's acceptable accuracy range and
calibration was aborted. Check the mA values and repeat calibration steps as
required.