background image

 

Honeywell Process Solutions 

 

 

 

 

 

 

 

SmartLine Wireless Transmitter 

Professional Installation Guide 

 

 

34-SW-25-03 

Revision 1 

December 2018 

 

 

 

 

Содержание STAW740

Страница 1: ...Honeywell Process Solutions SmartLine Wireless Transmitter Professional Installation Guide 34 SW 25 03 Revision 1 December 2018 ...

Страница 2: ...urpose and makes no express warranties except as may be stated in its written agreement with and for its customers In no event is Honeywell liable to anyone for any indirect special or consequential damages The information and specifications in this document are subject to change without notice Honeywell PlantScape Experion PKS and TotalPlant are registered trademarks of Honeywell International In...

Страница 3: ...r the application based on security safety and performance Additionally it is up to the end user to ensure that the control strategy sheds to a safe operating condition if any crucial segment of the control solution fails Revision Information Document Name SmartLine Wireless Transmitter Professional Installation Guide Document ID 34 SW 25 03 Revision Number Publication Date 1st release Revision 1 ...

Страница 4: ...ropriate Honeywell Support web site Honeywell Corporate www honeywell com Honeywell Process Solutions https www honeywellprocess com Training Classes https www honeywellprocess com en US training Telephone and Email Contacts Area Organization Phone Number United States and Canada Honeywell Inc 1 800 343 0228 Customer Service 1 800 423 9883 Global Technical Support Global Email Support Honeywell Pr...

Страница 5: ...ymbol on the equipment refers the user to the product manual for additional information The symbol appears next to required information in the manual WARNING Risk of electrical shock Potential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms 42 4 Vpeak or 60 VDC may be accessible ESD HAZARD Danger of an electro static discharge to which equipment may be sensitive Observe precautions...

Страница 6: ...irective ATEX Directive named after the French ATmosphere EXplosible For radio equipment used in the European Union in accordance with the R TTE Directive the CE Mark and the notified body NB identification number is used when the NB is involved in the conformity assessment procedure The alert sign must be used when a restriction on use output power limit by a country at certain frequencies applie...

Страница 7: ...stry Canada IC Identification Numbers 6 2 3 1 ISA100 Radios 6 2 4 Intended Country Usage 6 2 4 1 NORTH AMERICA 6 2 4 2 EUROPEAN UNION 6 3 SMARTLINE WIRELESS TRANSMITTER GENERAL DESCRIPTION 7 3 1 Intended Used 7 3 2 SmartLine Wireless Transmitter 7 4 PRODUCT SPECIFICATION 8 4 1 ISA100 Radio 2 4 GHz 8 4 2 SmartLine Wireless Transmitter User Environment 9 4 3 SmartLine Wireless Instrument Power Speci...

Страница 8: ...tting 18 9 AGENCY LABEL INFORMATION 19 9 1 External FCC IC Labels 19 9 1 1 External FCC IC Label 19 10 RF SAFETY MAXIMUM PERMISSIBLE EXPOSURE MPE STATEMENT 20 10 1 MPE Statement 20 11 AGENCY COMPLIANCE 21 11 1 Radio and EMC Certifications 21 11 1 1 Federal Communication Commission FCC 21 11 1 2 Industry Canada IC 21 11 1 3 European Telecommunications Standards Institute ETSI 21 11 2 Product Safety...

Страница 9: ...Transmitter 9 Table 5 1 Transmitter to Antenna or Lightning Arrestor Cable Specifications for SmartLine Wireless with N connectors 11 Table 6 1 Approved Antenna Types Gains 13 Table 7 1 Maximum EIRP Limits for ISA100 Radios 14 Table 7 2 ISA100 Transmit Power Settings for the antennas and cable lengths specified above 16 Figures Figure 3 1 SmartLine Wireless Pressure Transmitter showing 4 dBi Integ...

Страница 10: ......

Страница 11: ...nsmitter types Table 1 1 SmartLine Wireless Transmitter Types Model Number Type Model Number Description Model Key Number STDW Differential Pressure Transmitter STDW810 820 830 870 720 730 770 STGW Gauge Pressure Transmitter STGW840 870 84L 87L STGW740 770 73L 74L 77L 78L 79L STAW Absolute Pressure Transmitter STAW84L 740 74L STFW Flange Mount Pressure Transmitter STFW828 724 STRW Remote Seal Pres...

Страница 12: ...ireless SmartLine Wireless User s Guides for general information on overall system implementation configuration and management of these devices The SmartLine Wireless is classified by the FCC as a device that must be professionally installed To be in compliance with FCC requirements the transmitter must be installed with one of the approved antennas listed in this document 1 4 Site survey It is as...

Страница 13: ...ican Wire Gauge Co located Two or more radios transmitting simultaneously and with less than 20cm of separation distance CSA Canadian Standards Association DCS Distributed Control System DSSS Direct Sequence Spread Spectrum EMC Electromagnetic Compatibility ETSI European Telecommunications Standards Institute EU European Union FCC Federal Communications Committee FHSS Frequency Hopping Spread Spec...

Страница 14: ...aximum Permissible Exposure MSG Honeywell Model Selection Guide NA North America United States of America and Canada NEMA National Electrical Manufacturers Association OQPSK Offset Quadrature Phase Shift Keying TELEC Japan Telecom Engineering Center TIIS Japan Technology Institution of Industrial Safety TNTC Thailand National Telecommunications Commission TX Transmit Wi Fi Wireless Local Area Netw...

Страница 15: ...ss consent of the party responsible for compliance Any such modifications could void the user s authority to operate the equipment and will void the manufacturer s warranty 2 2 Industry Canada IC 2 2 1IC Compliance Statements To reduce potential radio interference to other users the antenna type and its gain should be so chosen that the equivalent isotropic radiated power EIRP is not more than tha...

Страница 16: ...ywell Identification for ISA100 Intrinsically Safe RF Modules 51454941 001 Honeywell SmartLine Wireless Transmitter ISA100 Radio Limited Modular Approval Federal Communication Commission Identification for Intrinsically Safe RF Modules S5751454941 Industry Canada Identification for Intrinsically Safe RF Modules 573W 51454941 2 4 Intended Country Usage 2 4 1NORTH AMERICA Country ISO 3166 2 letter c...

Страница 17: ...ss Transmitter is a key component of the Honeywell OneWireless Network The SmartLine Wireless Transmitter uses a low powered ISA100 2 4 GHz radio to communicate with Radio Infrastructure and Gateway devices that are connected to a wired DCS network 3 2 SmartLine Wireless Transmitter Figure 3 1 shows the SmartLine Wireless Transmitter with integral antenna Figure 3 1 SmartLine Wireless Pressure Tra...

Страница 18: ...ecified TX power settings antenna types and gains and cable lengths attenuation as outlined in this document are valid for SmartLine Wireless Transmitter installations Table 4 1 Specifications of ISA100 Radio Module in SmartLine Wireless Transmitter Item Specification Wireless Standard FCC 15 247 IEEE 802 15 4 Direct Sequence Spread Spectrum DSSS 2 4 GHz Data Rates and Modulation Data Rate 250 kbp...

Страница 19: ...able on the Honeywell website www honeywellprocess com 4 3 SmartLine Wireless Instrument Power Specifications The SmartLine Wireless Transmitters operate from two 2 D size 3 6V Lithium Thionyl Chloride Li SOCl2 batteries These are joined in series to produce a maximum voltage of 7 6 Vdc An optional external 24 Volt power supply option is also available 4 4 Weight Most non pressure sensing versions...

Страница 20: ...cation 4 5 Dimensions 10 SmartLine Wireless Transmitter Professional Installation Guide Revision 3 4 5 Dimensions Figure 4 1 Dimensions of a typical SmartLine Wireless Transmitter with the 4 dBi Integral Antenna Option ...

Страница 21: ...oneywell Part Number Cable Type Connector Type Frequency GHz Length m Loss dB 50018278 001 400 Series N male to N male 2 4 1 1 50018278 003 400 Series N male to N male 2 4 3 2 50018278 010 400 Series N male to N male 2 4 10 3 TYPE N MALE TYPE N MALE 5 2 Transmitter connection status Table 5 3 Lightning Arrestor to Antenna Cable Specifications Honeywell Part Number Cable Type Connector Type Frequen...

Страница 22: ...er Manufacturer Part Number Specification Connector Type Frequency GHz Attenuation dB 50018279 090 ALTELECON AL NFNFB 9 50 ohm N Female to N Female 0 3 0 4 max The lightning surge arrestor must be properly grounded in order to perform per specification Connecting to local ground using a No 12 4 mm2 copper conductor is recommended See the installation manual for other details Figure 5 1 Lightening ...

Страница 23: ...ion Manufacturer Manufacturer Part Number Honeywell Part Number Agency Compliance Notes Omni integral Point to Multi Point EM Wave EM B145103 MMP Z6 50029933 002 Omni remote Point to Multi Point L COM HGV 2409U 50018414 001 Directional remote Point to Multi Point L COM HG2414D 50018415 001 Figure 6 1 Remote Antennas The SmartLine Wireless Transmitter is available with 8 dBi Omnidirectional or 14 d...

Страница 24: ...h The EIRP allows making comparisons between different emitters regardless of type size or form From the EIRP and with knowledge of a real antenna s gain it is possible to calculate real power and field strength values EIRP dBm Radio TX Power dBm Cable Loss dB Antenna Gain dBi Antenna gain is expressed relative to a theoretical isotropic reference antenna dBi 7 1 EIRP LIMITS Table 7 1 Maximum EIRP...

Страница 25: ...t are given in Table 7 1 2 The values in the above tables have been determined through agency certification testing 3 The following shall apply for antenna type frequency range application usage and agency country compliance Antenna gains above the maximum values shown shall not be used Cable length loss below the minimum values shown shall not be used Maximum overall radio output power shown shal...

Страница 26: ...ni w o suppressor M10 or M20 1 3 8 12 7 8 dBi Omni w o suppressor M30 10 10 14 9 8 dBi Omni with suppressor M11 1 1 8 12 7 8 dBi Omni with suppressor M12 or M22 or M23 or M21 or M32 or M33 1 3 3 3 3 10 3 1 10 3 10 10 9 13 8 8 dBi Omni with suppressor M31 10 1 10 14 9 14 dBi directional w o suppressor 6 D10 or D20 1 3 2 6 10 14 dBi directional w o suppressor 6 D30 10 4 8 10 14 dBi directional with ...

Страница 27: ...e field away from the Model Number listed on the instrument s nameplate then the TX power setting should likewise be changed per the tables above to match the new Country antenna cable arrestor selections See Section 8 4 Note reserved for future Japan certification 5 The TX Power Setting values given in Table 7 2 represent the power produced by the Radio circuit within the RF Module These TX Power...

Страница 28: ...able only to the qualified Professional Installer Due to radio approval body regulations changing the TX Power setting is only available if the professional installer option has been explicitly enabled on your Authentication Device or Provisioning Device If you do not have the professional installer option enabled and would like to do so then please contact Honeywell Global Technical Services GTS ...

Страница 29: ...ntly labeled on the SmartLine Wireless Transmitter unit 9 1 External FCC IC Labels 9 1 1 External FCC IC Label THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS 1 THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE AND 2 THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION FCC ID S5751454941 IC ...

Страница 30: ...llowing antenna installation and device operating configurations must be satisfied Remote antenna s for this unit must be fixed and mounted on outdoor permanent structures with a separation distance between the antenna s of at least 20 cm and a separation distance of at least 20 cm from all persons When using integral antenna s the SmartLine Wireless Transmitter unit must not be co located with an...

Страница 31: ... 2 Industry Canada IC RSS 247 Issue 2 11 1 3 European Telecommunications Standards Institute ETSI Specification and Method EN 300 328 V2 1 1 EMC Product Standard EN 61326 1 2013 11 2 Product Safety Agency Certifications See product manual for list of agency certifications and standards available See product nameplate for transmitter certification information 11 2 1 European Union Certification CE ...

Страница 32: ...or contact one of the offices below ASIA PACIFIC Honeywell Process Solutions TAC hfs tac support honeywell com Australia Honeywell Limited Phone 61 7 3846 1255 FAX 61 7 3840 6481 Toll Free 1300 36 39 36 Toll Free Fax 1300 36 04 70 China PRC Shanghai Honeywell China Inc Phone 86 21 5257 4568 Fax 86 21 6237 2826 Singapore Honeywell Pte Ltd Phone 65 6580 3278 Fax 65 6445 3033 South Korea Honeywell Ko...