Revision 5.0
ST 800 Series HART/DE Option User’s Manual
Page 69
4.
If corrects should not be overwritten with factory values, select
No
. If corrects need to be
overwritten, select
Yes
. The timer will appear briefly, indicating the operation is performed
This function commands the transmitter to overwrite all user input corrections with
factory default ("characterization") values. It is intended for use only when excessive
corrections render the transmitter inaccurate. It is highly recommended that input calibration
procedure be performed after calibration reset.