User’s Guide SMX-AUS
30
NS-MN-0032 / 11.2020
7.2.4
ENABLE OR DISABLE - OUTPUT GROUPS
You can enable or disable an output group in the panel.
1.
Tap
OUTPUT GROUPS
.
2.
All output groups in the panel are listed.
3.
Tap
ENABLE
to enable the output group or tap
DISABLE
to disable the output group.
•
State information about the Fault Relays and the Other Relays & Controls can only
be viewed.
•
Programmable relay is available only if the onboard relay is not configured as an
output for supervisory condition.
•
Fan Controls option is available only when at least one Fire Fan Control group is
configured.
•
Alarm Routing Equipment and Relay Card-Programmable Relay 8 outputs are
available only if the Relay I/O Card is fitted and configured.
•
The inputs and outputs on the Alarm Routing Equipment interface cannot be
individually disabled. If ARE is disabled, the inputs and outputs are also disabled
(except for the Disabled relay and the Alarm Feedback input).
Fig. 29: Enable or Disable the Output Groups