User’s Guide SMX-AUS
12
NS-MN-0032 / 11.2020
5.2
Front Panel LED Indications
The following table provides the details of the LED indications on the Panel:
Indicator
Color Function
To Clear the Indication
ALARM ROUTING ACTIVATED Red
The Red LED flashes when the Alarm Relay on the Relay I/O
Card is activated in fire condition. The LED illuminates
steadily after the alarm feedback input is received from the
customer's Brigade interface.
Correct the condition causing the alarm and then perform
Silence Alarm followed by panel reset.
FIRE
Red
The LED flashes when the panel has detected a fire alarm
condition.
The LED illuminates steadily after the alarm is
acknowledged using SILENCE BUZZER button.
Correct the condition causing the alarm and then perform
Silence Alarm followed by panel reset.
FAULT
Yellow The LED flashes when the panel has detected a fault.
The LED illuminates steadily after the fault is
acknowledged using SILENCE BUZZER button.
Correct the condition causing the fault.
For system faults, correct the problem and then perform a
panel reset.
SUPERVISORY
Yellow The LED flashes when the panel has detected a supervisory
condition.
The LED illuminates steadily after the supervisory signal is
acknowledged using SILENCE BUZZER button.
Undo the activity, which caused the supervisory condition.
DISABLED
Yellow Part of the system, either input or output, has been
disabled manually by the user.
Re-enable the zones or devices. Refer to Disablement
Function.
TEST
Yellow The system is in the test mode. The screen shows which zones
are being tested.
After the test is completed, cancel or stop the test mode.
ALARM SILENCED
Yellow The sounder outputs are silenced.
Correct the alarm condition and then perform a panel reset.
Press SILENCE / RESOUND again to reactivate the
sounders.
SYSTEM FAULT
Yellow The CPU has reset, or a system fault has occurred.
Correct the problem (if applicable). Then perform a panel reset.
DELAY
Yellow This indicates that the system is operating with delays to
the outputs and the delays are active.
The delays may be disabled.
SEVERAL ALARMS
Red
The indicator shows when there are more than three
alarms. You can scroll up and down the list to see details of
the alarms.
Correct the condition causing the alarms and then perform
Silence Alarm followed by panel reset.
POWER
Green STEADY: Indicates presence of power (either AC mains
and/or batteries).
Not applicable.