10.5 DIGITAL INPUTS (CONTROL PANEL: MENU PAR -> P5)
The selections for these parameters are:
0
= Not used
1
= DI1
2
= DI2
(API FULL & LIMITED)
3
= DI3
(API FULL & LIMITED)
4
= DI4
(API FULL)
5
= DI5
(API FULL)
6
= DI6
(API FULL)
5.1
S
TART
SIGNAL
1
5.2
S
TART
SIGNAL
2
5.3
R
EVERSE
5.4
E
XTERNAL
FAULT
(
CLOSE
)
5.5
E
XTERNAL
FAULT
(
OPEN
)
5.6
F
AULT
RESET
5.7
R
UN
ENABLE
5.8
P
RESET
SPEED
B0
5.9
P
RESET
SPEED
B1
5.10
P
RESET
SPEED
B2
5.11
D
ISABLE
PI
5.12 F
ORCE
T
O
I/0
The control place is forced to I/O by activating the digital input that this function
is programmed to.
The priority order of selecting control place is
1. Navigation wheel
2. Forced from I/O
3. Parameter 2.1
5.13
R
AMP
T
IME
S
ELECTION
Contact open: Acceleration/Deceleration time 1 selected
Contact closed: Acceleration/Deceleration time 2 selected
Set Acceleration/Deceleration times with parameters 4.2 and 4.3 and the al-
ternative ramp times with 4.11 and 4.12.