Parameter Descriptions
Honeywell
10
2.3 S
TOP
FUNCTION
Two stop functions can be selected in this application:
0 = Coasting
The motor coasts to a halt without control from the frequency converter
after the Stop command.
1 = Ramp stop
After the Stop command, the speed of the motor is decelerated accord-
ing to the set deceleration parameters.
If the regenerated energy is high it may be necessary to use an exter-
nal braking resistor for to be able to decelerate the motor in acceptable
time.
2.4
S
TART
/
STOP
LOGIC
With this parameter the user can select the start/stop logic.
0
= DI1 = Start forward
DI2 = Start reverse (
API FULL & LIMITED
)
Figure 10.3: Start/Stop logic, selection 0
1 The first selected direction has the highest priority.
2 When the DIN1 contact opens the direction of rotation starts the change.
3 If Start forward (DI1) and Start reverse (DI2) signals are active simultaneously the
Start forward signal (DI1) has priority.