6. Operation
6.3. Transmitter PV display
Revision 2
SmartLine Wireles User's Manual
57
For Flow:
1.
Select the upper and lower scale values in flow units.
2.
Set the Pressure Scale 100% EU value to the pressure that will be asserted when the flow
is to be the upper scale value.
3.
Set the Pressure Scale 0% EU value to the pressure that will be asserted when the flow is
to be the lower scale value.
PV status
PV Status is indicated by the Second Left-most Character on the display when showing the PV
Value. Blank indicates good/normal status. ‘B’ Indicated Bad Status. ‘U’ indicates uncertain
status and ‘F’ indicates Failure Status.
Table 6-5: PV Status
PV status
Cause - Action
(blank)
PV is normal
– no action required
‘B’
Possible calibration error
– Clear calibration
AITB cannot execute due to internal firmware state
– Attempt cold restart of
device.
AITB cannot execute due to hardware fault
– Replace sensor board
Sensor failure
– Check Connection between Sensor board and meter body.
Meter body Characterization Data is Bad
– Replace meter body
Meter body A/D Failure
– Replace meter body
Meter body Sensor Fail
– Replace meter body
Configuration is bad
– Check possible units and range settings for input type
and correct AITB configuration.
Hardware fault detected - Replace sensor board
‘U’
Warning: Calibration (zero or trim) is causing excessive adjustment to
characterization value.
Warning: Input inaccurate due to uncertain input data integrity.
Warning: Input inaccurate due to input conversion limitations or resolution.
Warning: Input outside of characterized range. Value is estimated.
‘F’
Sensor Failure has occurred or the transmitter was unable to communicate
with the sensor.
Check the connection between the Sensor and the Main Board of the
transmitter.
Contact Honeywell Support if the problem persists.
Содержание SmartLine
Страница 2: ......
Страница 8: ......
Страница 14: ...xiv SmartLine Wireless User s Manual Revision 2 ...
Страница 108: ...94 SmartLine Wireless User s Manual Revision 2 Appendix B Certifications and Approvals B1 EU Declaration of Conformity ...
Страница 109: ...Revision 2 SmartLine Wireless User s Manual 95 ...
Страница 110: ...96 SmartLine Wireless User s Manual Revision 2 ...
Страница 111: ...Revision 2 SmartLine Wireless User s Manual 97 ...
Страница 119: ...Revision 2 SmartLine Wireless User s Manual 105 B5 Control Drawing ...
Страница 120: ...106 SmartLine Wireless User s Manual Revision 2 ...
Страница 121: ...Revision 2 SmartLine Wireless User s Manual 107 ...
Страница 122: ...108 SmartLine Wireless User s Manual Revision 2 ...
Страница 123: ...Revision 2 SmartLine Wireless User s Manual 109 ...
Страница 128: ...114 SmartLine Wireless User s Manual Revision 2 This page has been intentionally left blank ...