Table 8-10 SmartLine Wireless
– Modbus table
Wireless Pressure
Name
Description
Data Type
Data Size Access
Class
Enum Value
Enum Description
UAP_VERREV
Field device application revision.
VisibleString
64 Read Only
Static
UAP_STREV
Field device application static data revision level. Uint16
2 Read Only
Static Revision
IDENT_NUMBER
Field device application identity.
OctetString
8 Read Only
Static
CTS_VERSION
Field device application CTS version.
Uint16
2 Read Only
Static
ITS_VERSION
Field device application ITS version.
Uint16
2 Read Only
Static
DIAG_STATUS
Field device application diagnostic status
bitstring.
BitString
4 Read Only
Dynamic
2147483647 - Failure Status
Failure status
1073741824 - Function Check Status
Function check status
536870912 - Out of Specification Status
Out of specification status
268435456 - Maintenance Required Status Maintenance required status
134217728 - Fault in Electronics
Faults in electronics
67108864 - Fault in Sensor or Actuator
Element
Faults in sensor or actuator element
33554432 - Installation or Calibration
Problem
Installation or calibration problem
8388608 - Outside Sensor Limits
Outside sensor limits
1048576 - Power is Critically Low:
Maintenance Need Short-term
Power is critical low: maintenance
need short-term
128 - Configuration Error
Invalid
inconsistent
corrupted or lost static data
1 - Detail Information Available
Detail information available
UAP_OPTION
Option
BitString
2 Read/Write Static
8192 - Enable Software Write Protect
Enable Software Write Protect
UAPMO_ALERT
No Help Available
Uint8
1 Read/Write Static
0 - Begin Alert Recovery
No Help Available
1 - End Alert Recovery
No Help Available
2 - Device Restart
No Help Available
3 - Maintenance Alert
No Help Available
4 - Out of Specification Alert
No Help Available
5 - Function Check Alert
No Help Available
6 - Failure Status Alert
No Help Available
DIAG_STATUS_DETAIL_1
Diag status detail
BitString
4 Read Only
Dynamic
1 - Electronics Failure
An electronic component has failed
4 - Input Failure
Input failure
16 - Low Battery
Battery needs replacement
128 - Calibration Error
Persistent calibration error
256 - No Radio Error
Radio is not present or not
functioning
4096 - Low External Power
External power is low
65536 - Program Memory Fault
Program memory is corrupted
131072 - RAM Fault
Random access memory is corrupted
262144 - NVM Fault
Non-volatile memory is corrupted
524288 - ADC Failure
Analog to digital converter failed
1048576 - Characterization Memory Fault Characterization memory fault
16777216 - Meter Body Over Temperature Meter body temperature is too high
33554432 - Meter Body Overload
Pressure input exceeds twice the
upper range limit
67108864 - Excess Zero Calibration
Zero calibration exeeds 5 percent
134217728 - Excess Span Calibration
Span calibration exeeds 5 percent
268435456 - Excess Calibrated Range
Calibrated span exceeds the sensor
span
536870912 - Calibration Cleared
Calibration was reset
Содержание SmartLine
Страница 2: ......
Страница 8: ......
Страница 14: ...xiv SmartLine Wireless User s Manual Revision 2 ...
Страница 108: ...94 SmartLine Wireless User s Manual Revision 2 Appendix B Certifications and Approvals B1 EU Declaration of Conformity ...
Страница 109: ...Revision 2 SmartLine Wireless User s Manual 95 ...
Страница 110: ...96 SmartLine Wireless User s Manual Revision 2 ...
Страница 111: ...Revision 2 SmartLine Wireless User s Manual 97 ...
Страница 119: ...Revision 2 SmartLine Wireless User s Manual 105 B5 Control Drawing ...
Страница 120: ...106 SmartLine Wireless User s Manual Revision 2 ...
Страница 121: ...Revision 2 SmartLine Wireless User s Manual 107 ...
Страница 122: ...108 SmartLine Wireless User s Manual Revision 2 ...
Страница 123: ...Revision 2 SmartLine Wireless User s Manual 109 ...
Страница 128: ...114 SmartLine Wireless User s Manual Revision 2 This page has been intentionally left blank ...