Page 72
ST 700 Series HART/DE Option User’s Manual
Revision 4.0
10.
When prompted, remove the pressure.
11.
On the next prompt:
Please enter Calibration Date in MM/DD/YYYY format
, for example
“05/27/2009,” and click
Enter
.
12.
On the next prompt:
Please enter current Calibration Time in 24Hr Clock format (Hour
field)
, enter the hour portion of the calibration time in the 24Hr format HH, for example “12,”
and click
Enter
.
13.
On the next prompt:
Please enter current Calibration Time (Minute field)
, enter the
Minutes field MM (example 23), and click
Enter
.
14.
When prompted, return the loop to automatic control, and click
Enter
.
8.3.3 Resetting Calibration
ST 700 Standard SmartLine HART Pressure Transmitter can erase incorrect calibration data by
resetting the device back to
final factory calibration
, which is performed per the ordered range.
The Corrects Reset command returns the zero and span calibration factors to the original precise
factory calibration.
The following procedure is used to reset calibration data to factory calibrated range using the
communicator:
1.
Connect the MC Toolkit per
Figure 6
across the loop wiring and turn on.
2.
Turn the MC Toolkit on, start the FDC application.
3.
On the
FDC
homepage, click
Online
, and establish communication with the Transmitter.
4.
Click the
My Device
menu, and choose from the following options:
a.
Device Setup \ Calibration \ Calibration Methods \ Reset Corrects
5.
You will be prompted to remove the loop from automatic control. After removing the loop
from automatic control, press OK.
6.
You will be notified that a Reset Corrects is about to occur. Click
OK
.
7.
When the message
Reset Corrects OK
appears, click
OK
. The previous calibration
“Corrects” are removed and calibration is reset to the factory values.
8.
When prompted to return the loop to automatic control, click
OK
.
8.3.4 Calibration Records
A history of the date and time of the last three Calibration procedures is available for the HART
device. Run the Methods and follow the screen prompts to read the Calibration Records.
Click
My Device\Device Setup\Calibration
to select the following calibration records
Correct URV Records
Correct LRV Records
Zero Trim Records
Reset Corrects Records
Содержание SmartLine ST700
Страница 88: ...Page 74 ST 700 Series HART DE Option User s Manual Revision 4 0 This page has been intentionally left blank ...
Страница 98: ...Page 84 ST 700 Series HART DE Option User s Manual Revision 4 0 This page intentionally left blank ...
Страница 115: ...Revision 4 0 ST 700 Series HART DE Option User s Manual Page 101 11 9 Trend Charts ...
Страница 175: ...Revision 4 0 ST 700 Series HART DE Option User s Manual Page 161 This page intentionally left blank ...
Страница 188: ...Page 174 ST 700 Series HART DE Option User s Manual Revision 4 0 20 9 Trend Charts ...