Page 10
ST 700 Series HART/DE Option User’s Manual
Revision 4.0
4.4 MC Toolkit Participation
Before using the MC Toolkit, ensure that you are aware of the potential consequences of
each procedure, and that you use appropriate safeguards to avoid possible problems. For
example, if the Transmitter is an element in a control loop, the loop needs to be put in manual
mode, and alarms and interlocks (i.e., trips) need to be disabled, as appropriate, before
starting a procedure.
4.4.1 MC Toolkit Software Applications
The MC Toolkit has two software applications to work with ST 700 Standard SmartLine Pressure
Transmitters:
Field Device Configurator (FDC)
: This application is used for configuring, calibrating,
monitoring, and diagnosing HART devices. FDC conforms to the IEC 61804-3 EDDL
(Electronic Data Description Language) standard specification. The FDC application is an open
solution that supports devices with a registered device description (DD) file compatible with
HART Communication Foundation (HCF) requirements.
MC Toolkit
: This application is used for configuring, calibrating, monitoring, and diagnosing
Honeywell Digitally Enhanced (DE) devices.
Details for working with the MC Toolkit are provided in the
MC Tookit User Manual,
Document #
34-ST-25-20 (MCT202) or #34-ST 25-50 (MCT404). In subsequent sections of this manual, explicit
operating instructions are provided only in so far as necessary to complete required tasks and
procedures.
4.4.2 Configuration Databases
The MC Toolkit is used to establish and/or change selected operating parameters in a Transmitter
database.
4.4.3 Configuration
Configuration can be accomplished both online and offline with the Transmitter powered up and
connected to the MC Toolkit. Online configuration immediately changes the Transmitter operating
parameters. For offline configuration, Transmitter operating characteristics are entered into Toolkit
memory for subsequent downloading to a Transmitter.
When you set up or configure a Transmitter, it can take up to 30 seconds for the value
to be permanently stored. If you change the Sensor Type or ID and the Transmitter power is
interrupted before the change is copied to nonvolatile memory, the changed value will not be
moved to nonvolatile memory.
When Sensor Type or ID is changed, the associated parameters (Field calibration data,
Sensor bias value, disable CVD option, default CVD data and disable match PV if it is dual
input model) which are specific to that sensor input, are written to default values.
Содержание SmartLine ST700
Страница 88: ...Page 74 ST 700 Series HART DE Option User s Manual Revision 4 0 This page has been intentionally left blank ...
Страница 98: ...Page 84 ST 700 Series HART DE Option User s Manual Revision 4 0 This page intentionally left blank ...
Страница 115: ...Revision 4 0 ST 700 Series HART DE Option User s Manual Page 101 11 9 Trend Charts ...
Страница 175: ...Revision 4 0 ST 700 Series HART DE Option User s Manual Page 161 This page intentionally left blank ...
Страница 188: ...Page 174 ST 700 Series HART DE Option User s Manual Revision 4 0 20 9 Trend Charts ...