Honeywell Process Solutions 

 

 
 
 
 
 

SLG 700 

SmartLine Level Transmitter 

Guided Wave Radar 

FOUNDATION

TM

 Fieldbus  

Option Manual 

 

34-SL-25-07 

Revision 5.0 

September 2017 

 

 

 

 

Содержание SmartLine SLG 700

Страница 1: ...Honeywell Process Solutions SLG 700 SmartLine Level Transmitter Guided Wave Radar FOUNDATIONTM Fieldbus Option Manual 34 SL 25 07 Revision 5 0 September 2017 ...

Страница 2: ... makes no express warranties except as may be stated in its written agreement with and for its customers In no event is Honeywell liable to anyone for any indirect special or consequential damages The information and specifications in this document are subject to change without notice Honeywell PlantScape Experion PKS and TotalPlant are registered trademarks of Honeywell International Inc Other br...

Страница 3: ...ease Rev 2 0 July 2015 Security Vulnerability section added Rev 3 0 July 2016 Updates for R101 release Rev 4 0 February 2017 Updates for R102 release Rev 5 0 September 2017 DTM updates References The following list identifies all documents that may be sources of reference for material discussed in this publication SLG 700 SmartLine Level Guided Wave Radar User s Guide Document 34 SL 25 11 SLG Pock...

Страница 4: ...ate Honeywell Solution Support web site Honeywell Corporate www honeywell com Honeywell Process Solutions https www honeywellprocess com SmartLine Level Transmitters https www honeywellprocess com smartline level transmitter aspx Training Classes https www honeywellprocess com en US training Telephone and Email Contacts Area Organization Phone Number United States and Canada Honeywell Inc 1 800 34...

Страница 5: ...ol on the equipment refers the user to the product manual for additional information The symbol appears next to required information in the manual WARNING Indicates a potentially hazardous situation which if not avoided could result in serious injury or death WARNING symbol on the equipment refers the user to the product manual for additional information The symbol appears next to required informa...

Страница 6: ...n shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements Chassis Ground Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements ...

Страница 7: ... parameters The DD binary are created by passing DD source files through a standard tool called a tokenizer Device Description Language DDL A standardized programming language similar to C used to write device description source files Device Tag The Physical Device Tag of the device as specified in the Foundation Fieldbus specifications DTM Device Type Manager EEPROM Electrically Erasable Programm...

Страница 8: ...itions and descriptions of network visible objects of a device There are various object dictionaries within a device The dictionaries contain objects and their associated parameters which support the application in which they are contained Objects Entities within the FBAP such as blocks alert objects trend objects parameters display lists etc OOS Out of Service Parameters A value or variable which...

Страница 9: ...urrent Vdc Volts Direct Current Virtual Communication Relationship A defined communication endpoint Fieldbus communications can primarily only take place along an active communications path that consists of two VCR endpoints Virtual Field Device A logical grouping of user layer functions Function blocks are grouped into a VFD and system and network management are grouped into a VFD For example to ...

Страница 10: ... Device Description DD files 7 Importing the DD to Experion PKS 7 Control strategy 11 Creating control strategy 11 3 2 Device replacement 12 3 3 Configuring the function block application process 12 3 4 Resource block 15 Execution 16 Parameter List 22 Attributes 25 3 5 Level Transducer block 26 Execution 26 Parameter List 27 Attributes 34 3 6 Auxiliary Transducer Block 35 Parameter List 48 Attribu...

Страница 11: ...105 Parameter list 107 Attributes 108 3 15 Output Splitter block 109 Execution 109 Parameter list 112 Attributes 113 3 16 Configuring the transmitter using Field Device Manager system 113 4 SLG 700 FF LEVEL TRANSMITTER OPERATION 114 4 1 Operational considerations 114 LAS Capability 114 Special Non volatile parameters and NVM Wear out 114 Mode Restricted Writes to Parameters 114 4 2 Configuration o...

Страница 12: ...ing the Resource block 177 Troubleshooting the Level Transducer block 180 Troubleshooting the Diagnostics Transducer block 183 Troubleshooting the Diagnostics Transducer block 183 Troubleshooting the LCD Transducer block 184 Troubleshooting the Analog Input AI block 185 Troubleshooting the Proportional Integral Derivative PID block 186 Troubleshooting the Input Selector block 187 Troubleshooting t...

Страница 13: ...Rev 5 FOUNDATION Fieldbus Option User s Manual Page xiii 8 SECURITY 202 8 1 How to report a security vulnerability 202 ...

Страница 14: ... Table 18 Arithmetic block parameters 102 Table 19 Signal Characterizer block parameters 107 Table 20 Output Splitter block parameters 112 Table 40 Dielectric Constants Required by Application 134 Table 41 Minimum blocking distances and transition zones for the various probe types 138 Table 21 Resource block 177 Table 22 Level Transducer block 180 Table 23 Auxiliary Transducer block 183 Table 24 D...

Страница 15: ...igure 17 Input Selector Schematic Diagram 87 Figure 18 Integrator Block 90 Figure 19 Two Rate Inputs 91 Figure 20 Arithmetic Block 99 Figure 21 Arithmetic Schematic Diagram 100 Figure 22 Signal Characterizer Block 105 Figure 23 Signal Characterizer Curve 106 Figure 24 Output Splitter Block 109 Figure 25 Output Splitter Schematic 109 Figure 26 Split Range and Sequence Operation 110 Figure 27 OUT wi...

Страница 16: ...Page xvi FOUNDATION Fieldbus Option User s Manual Rev 5 ...

Страница 17: ...he following unique advantages through Smart Connection suite Transmitter messaging To enhance safety and productivity through clear identification and assignment of maintenance tasks in the local transmitter display Maintenance mode indication To enhance safety through system initiated command to identify that the device is available for maintenance FDM Plant Area Views with Health summaries To r...

Страница 18: ... terminal block assembly Sensor housing Process connector Probe also known as a waveguide These components are described below Additional mounting and optional accessories are available such as centering discs for the waveguide For list of all options and accessories please refer to purchasing specifications Representational Figure 1 Components of SLG 700 Electronics housing display buttons commun...

Страница 19: ...owing features Link master capability Supports the following standard function blocks apart from the Resource and Transducer blocks Analog Input block Input Selector block Signal Characterizer block PID with auto tune block Arithmetic block Output splitter Integrator block Function block instantiation is supported by the following blocks Analog Input block PID with auto tune block Arithmetic block...

Страница 20: ...evice On the operator interface check and make sure communications are established with the device on the Fieldbus network Verify or assign Device Tag and address Check that the Device Tag and node address are set If not assign the Device Tag and the correct node address The Device Tag and address can be set and viewed using the Fieldbus device configurator application Use a Device Tag name up to ...

Страница 21: ...the correct version of the Device Description file is present on the host computer This helps in getting the correct parameter names and its corresponding descriptions while viewing the device parameters Table 2 Transmitter parameters Parameter To verify Resource block DEV_TYPE That the transmitter is of the proper device type For all the SLG 700 SmartLine Guided Wave Radar Level Transmitter the v...

Страница 22: ...emid 324 2 3 2 Enhanced Device Description EDD There are two types of EDDs are available namely ff5 sy5 and ffo sym The ffo sym binary files are generated for the legacy hosts to load the device DD that is generated using latest tokenizer A few constructs such as Images that are supported in ff5 sy5 binaries are not supported in ffo sym binary files 2 3 3 Device Type Manager DTM The DTM is similar...

Страница 23: ...430 3 Yes 410 7 Yes The steps in the following procedure are specific to Experion only Step Action 1 From the Control Builder main screen click Fieldbus Device Description Import OR Select File New Type Fieldbus Device 2 You can Import the DD using one of the following steps Choose Browse to locate the folder where you have stored the DD file Select the required folder and click OK Select the DD f...

Страница 24: ...on blocks 5 The following dialog box appears Click OK 6 The following dialog box appears Click OK ATTENTION The device type SLGWRFF_0101_1 is used as an example 7 The device is created in the Library Containment window under the folder named Honeywell 8 From the Library Containment window drag and drop the device into the corresponding FF link on the Project Assignment window The fallowing window ...

Страница 25: ... destination column type the new name or if you want to use the default name click Finish The device is added on the FF link on the Project Assignment window Double click the device link on Monitoring Assignment the following window opens Update the capability level as 1 under uncommisioned devices menu Match the device by clicking on either ...

Страница 26: ...e following WARNING appears Click Continue 12 The following dialog box appears Select the Automatically change ALL control elements to the state selected in Post Load State after load is completed checkbox and click OK 13 On the Monitoring Assignment window you can notice that device on the Project Assignment window has been loaded to the corresponding FF link ...

Страница 27: ... must be created where function blocks are inserted and connected with other function blocks Creating control strategy For information on creating control strategy refer to the corresponding DCS document ATTENTION When control strategy is loaded by deselecting the partial download option in the Experion parameter check errors will appear Ignore the errors and continue the loading of control strate...

Страница 28: ...feature supports all the blocks The FBAP provides the block related information in a much more organized way The FBAP defines blocks to represent different types of application functions In addition the blocks have a static revision parameter The revision level of the static data is associated with the function block To support tracking changes in static parameter attributes the associated block s...

Страница 29: ...s still able to communicate that condition 10 Lost Static data If the object s static data is Bad then the object s database is set to its default values 11 Lost NV data The NV and static parameters are saved periodically This alarm occurs if new data was supposed to be saved to NV at the next NV write cycle but prevented the write due to power failure 12 Readback Check failed This indicates the r...

Страница 30: ...of each alarm is set by the following parameters HI_PRI HI_HI_PRI DV_HI_PRI DV_LO_PRI LO_PRI LO_LO_PRI The following is the order of priority for alarms Table 4 Priority for Alarms Priority Description 0 To disable the triggered alarm the priority of an alarm condition is changed to 0 1 Alarm condition with a priority 1 is reported to the system but not reported as an event and alarm 2 Alarm condi...

Страница 31: ...unction block execution The user selects the desired mode as the target Current mode of the block is shown as the Actual mode The AUTO mode allows normal operation of the resource 3 4 1 Configuring the Resource block The Resource block supports scalar input and discrete input as HARD_TYPES This parameter is a read only bit string that indicates the types of hardware that are available for this res...

Страница 32: ...constants are used by each function block and are configurable values MAX NOTIFY The MAX_NOTIFY parameter value is the maximum number of alert reports that this resource can send without getting a confirmation and to control alert flooding adjust the LIM_NOTIFY parameter to a lower value If LIM_NOTIFY is set to zero no alerts are reported The CONFIRM_TIME parameter is the time for the resource to ...

Страница 33: ...tivate write lock the soft write lock supported bit in FEATURE_SEL must be set and then set the WRITE_LOCK to locked To deactivate write lock set the WRITE_LOCK to unlocked Hardware write lock To activate write lock the hard write lock supported bit in FEATURE_SEL must be set and additionally the write lock jumper must be in the correct position as determined by the manufacturer Refer to the SLG70...

Страница 34: ...cs Check Function Output signal temporarily invalid due to on going work on the device Failed Output signal invalid due to malfunction in the field device or its peripherals FAILED_ALARMS Failed alarms indicate a failure within a device that makes the device or some part of the device non operational This implies that the device needs repair and must be fixed immediately FAILED_MAPPED parameter co...

Страница 35: ...nd is not reported MAINT_PRI designates the alarming priority of the MAINT_ALM The default is 0 MAINT_ACTIVE parameter displays the alarms that are active MAINT_ALM parameter indicates that the device needs maintenance If the condition is ignored the device fails CHECK_ALARMS It indicates that the output signal is temporarily invalid due to on going work on the device CHECK_MAPPED parameter contai...

Страница 36: ...ng Distance High Surface Blocking Distance Low Interface Blocking Distance high Interface Blocking Distance low OFFSPEC_MASK parameter masks any of the failed conditions listed in OFFSPEC_MAPPED A bit on means the condition is masked out from alarming and is not reported OFFSPEC_PRI parameter designates the alarming priority of the OFFSPEC_ALM The default is 0 OFFSPEC_ACTIVE parameter displays the...

Страница 37: ...re information refer section 7 6 MAINTENANCE_MODE It indicates if the device is available for maintenance When the resource block is in OOS mode MAINTENANCE_MODE parameter displays the text as Chk with Oper i e the device is in process and is not available for maintenance When the resource block is in AUTO mode MAINTENANCE_MODE parameter displays the text as Avail for Maint i e the device is out o...

Страница 38: ...ocate the DD file for the resource DEV_REV Manufacturer revision number associated with the resource It is used by an interface device to locate the DD file for the resource CAPABILITY_LEV The Capability Level of the Device DD_REV Revision of the DD associated with the resource It is used by the interface device to locate the DD file for the resource GRANT_DENY Options for controlling access of ho...

Страница 39: ...mbers of unconfirmed notify messages possible LIM_NOTIFY Maximum numbers of unconfirmed alert notify messages allowed CONFIRM_ TIME The time the resource waits for confirmation of receipt of a report before trying again Retry does not happen when CONFIRM_TIME 0 WRITE_LOCK If set no writes from anywhere are allowed except to clear WRITE_LOCK Block inputs continues to be updated UPDATE_EVT This aler...

Страница 40: ...ponding alarm condition is disabled and is not detected FD_MAINT_MASK Mask of MAINT_ALM It corresponds to the bit of bit to MAINT_ACTIVE A bit on means that the condition is masked out from alarming FD_MAINT_ACTIVE Enumerated list of maintenance conditions within a device FD_MAINT_ALM Alarm indicating the device needs maintenance soon If the condition is ignored the device eventually fails FD_OFFS...

Страница 41: ...ty revision number of the communications module MODEL_KEY The key number of SLG 700 level transmitter Example SLG 700 MOD_PART_1 First part of the Material of Construction Information MOD_PART_2 Second part of the Material of Construction Information HW_SIMULATE_JUMP ER_STATE State of Hardware Simulation Jumper Enabled Disabled INSTALL_DATE The date and time when the device is installed in the fie...

Страница 42: ...ues and are called as channels The measured values can be read cyclically from function blocks See Table 7 for list of parameters Figure 2 Level Transducer Block Execution The Level Transducer block supports the following process variables Product Level Product Level Distance To Product Product Level Rate Vapor Thickness Vapor Thickness Interface Level Interface Level Distance To Interface Interfa...

Страница 43: ...CK_ALM The BLOCK_ALM is used for all configuration hardware and connection failure or system problems in the block The cause of the alert is entered in the subcode field The first alert to become active sets the Active status in the Status attribute After the Unreported status is cleared by the alert reporting task another block alert may be reported without clearing the Active status if the subco...

Страница 44: ...r more details on Volume calculations PRODUCT_VOLUME_RANGE The product volume range is the range from 0 to the maximum tank volume size considering maximum product height as the tank height It also contains unit for product volume The supported units are L ft3 in3 gallon ImpGal bbl bbl liquid yd3 m3 ELECTRONIC TEMPERATURE The electronic temperature of the communication board It also contains the u...

Страница 45: ...asured if two products exist in the tank UPPER_PRODUCT_DC Dielectric constant of upper product to be measured For single liquid this is Product DC VAPOR_DC Dielectric constant of the vapor SENSOR_HEIGHT The height from the reference point at which sensor is mounted A represents Sensor Height MAX_PRODUCT_HEIGHT Maximum Product Height can be equal to or less than the Sensor Height It is the valid he...

Страница 46: ...s Level Offset PROBE_TYPE Choices 1 Custom 2 Coax 3 Rod 4 Wire 5 Multi twist wire PROBE_MATERIAL Choices 1 316 316L Stainless Steel 2 PFA Coated Stainless Steel 3 C 276 Nickel Alloy PROBE DIAMETER Lists options to choose from like Custom 8mm 12mm 16mm 22mm etc PROBE_LENGTH The allowed probe length range is 0 50m A represents Probe Length PROBE_END_TYPE Probe End types 1 Clamp 2 Weight 3 Loop 4 Non...

Страница 47: ...height can be configured only when the mounting type is selected as Nozzle or Standpipe or Stillwell The allowed range is 0 75m MOUNTING_DIAMETER The mounting diameter can be configured only when the mounting type is selected as Nozzle or Standpipe or Stillwell The allowed range is 0 1m MOUNTING_ANGLE The mounting angle can be configured only when the mounting type is selected as Bracket or Direct...

Страница 48: ...PRODUCT_ATTENUA TION The value can be between 0 0 10 UPPER_PRODUCT_ATTENUA TION The value can be between 0 0 10 VAPOR_ATTENUATION The value can be between 0 0 10 PROCESS_CONN_TYPE Threaded Flanged BACKGROUND_TYPE Factory Field Obstacle FIELD_BACKGROUND Cancel Get Status Capture Get Additional Status FIELD_BACKGROUND_CAPTU RE_STATUS Capture Not Available Capture In Progress Capture Cancelled Captur...

Страница 49: ...M write error FULL_TANK_DETECT Full tank detection DISABLED ENABLED SENSOR_TYPE Displays Type of the Sensor In this case it will display as Guided wave sensor SENSOR_SN Displays sensor serial number SENSOR_HW_REV Sensor Board Hardware Revision number SENSOR_FW_VER Sensor Board Firmware Version number ASIC_SLOPE Displays ASIC_SLOPE ASIC_OFFSET Displays ASIC_OFFSET CHARACTER_DATE Characterization Da...

Страница 50: ...ield Field background is used for background capture Obstacle Obstacle removal is used for background capture ECHO_LOST_TIMEOUT The value can be between 3 900 in seconds Attributes Supported Modes The block supports the following modes AUTO Automatic OOS mode Out of Service Alarm Types The block supports standard block alarms see section 3 2 ...

Страница 51: ...n Table to enable Dry Linearisation Please refer Table 8 Auxiliary Transducer block parameters for more details on Linearization Note The Level Linearization feature does not affect the values reported for the Distance to Product and Distance to Interface device variables If Level Linearization is enabled the distance and associated level are no longer described solely by the basic geometry and it...

Страница 52: ...is shown only in the areas where the transmitter is currently searching for reflections On short probes this will cover the full length of the probe but on longer probes where the transmitter tracks the surface interface reflections as they move there will be areas with no data visible Subtraction of background reflections near the reference plane has been applied to this data array so unwanted re...

Страница 53: ...ion of background reflections near the reference plane is not applied so all physical reflections due to a nozzle for instance will be visible This type of echo curve is useful for troubleshooting problems in the region near the reference plane Figure 4 Full Echo Curve Note A Full Echo Curve will likely take much longer to capture than a Windowed Echo Curve ...

Страница 54: ... troubleshooting Figure 5 Processed Full Echo Curve Background Subtraction Array Selecting this echo curve type allows the data array that is used to remove unwanted reflections in the region near the reference plane to be uploaded and viewed This type of echo curve is useful for troubleshooting problems in the region near the reference plane and checking whether any obstacles if present are found...

Страница 55: ...DTM or FDM can be used to read the Echo signal ATTENTION SLG700 FF DTM should be installed before proceeding Echo read The following section describes reading the echo signal using FF DTM and storing it in text file in the FDT Host environment Navigate to the Level Auxiliary block and click the Echo Curve tab Note It may take few seconds to load the Echo Curve page Configure the start and end dist...

Страница 56: ...in Text file format by selelcting Echo curve export opion shown below ATTENTION This Echo data is stored as Text file with specific format Don t try to modify the file ATTENTION FF device Width Attenuation Gain value of Surface and Interface should be configured in the HART DTM Field Set Up Tool in offline mode before proceeding model shape adjustment ...

Страница 57: ...algorithm Download HART DTM from https www honeywellprocess com en US explore products instrumentation process level sensors Pages smartline level transmitter aspx Go to Software tab ATTENTION SLG 700 HART DTM Field Set Up Tool should be installed before proceeding Echo Import feature How to open the HART DTM in offline mode Add the HART communication DTM to HOST PC and then add device DTM approri...

Страница 58: ...terization under parameter Once DTM is opened click on the Proceed to algorithm tuning tab select Open File option to select the Echo data text file exported using FF DTM and enter the correlation algorithm parameter for surface and interface models of FF device before adjusting the model shapes ...

Страница 59: ...Rev 5 FOUNDATION Fieldbus Option User s Manual Page 43 The following section describes how to do configure the Correletaion Algorthim model type ...

Страница 60: ...ick and drag cursor to move model over relevant part of the curve The example curve shown in the figure below represents a scenario of a two liquid non flooded application with oil on top of water In the example the transmitter has correctly located the surface of the upper oil layer but has failed to find the interface boundary between the oil and water due to a model miss match In this case the ...

Страница 61: ...rve decrease the Gain By gradually decreasing Gain from 5122 to 3322 the model more closely matches the blue curve while the Objective Function value has improved from 0 658 to 0 580 TIP By using the up and down arrows to increase and decrease Gain you can home in on the lowest Objective Function value 11 In the bottom graph of the Objective Function the red line indicates the Threshold The brown ...

Страница 62: ...h then the models other parameters Width and Attenuation can be adjusted to get an even closer match between the model and the curve Note that it may be necessary to collect echo curves with various levels of product to ensure that the reflection model provides a good match through the full range Figure 10 shows the example with the Gain Width and Attenuation parameters optimized to give and Objec...

Страница 63: ...del is being used therefore drag it to the part of the curve where the Surface would be expected to the right of the Reference 4 The closer the model shape matches the curve shape the lower the Objective Function value In the example the brown Surface model does not match the blue curve at that position around 570cm so the Objective Function value is high greater than 1 Adjusting the Correlation a...

Страница 64: ...lems in the block The cause of the alert is entered in the subcode field The first alert to become active sets the Active status in the Status attribute After the Unreported status is cleared by the alert reporting task another block alert may be reported without clearing the Active status if the subcode has changed PRODUCT_LEVEL This product level follows the product level of Level Transducer Blo...

Страница 65: ...D_LEVEL1 This is the first half part of the Measured Level Table which supports entries for 16 elements The user can modify it manually when Linearization Type is Dry If Linearization Type is Wet then it is allowed to enter correct single entry in the Linearization table at a time using method While executing Level Wet Linearization Method Measured Level cannot be edited by user Value of Product L...

Страница 66: ...be in proper order to select the Strapping Table option The Ideal Tank Shape can be selected and the relevant tank configurations can be updated Note 2 Select Volume Calculation Type as None if Volume related device variables Product Volume are not required to be measured and monitored by device Note 3 The SLG 700 directly measures only distance and related quantities level percent of range etc Th...

Страница 67: ...HORIZONTAL CYLINDER 6 RECTANGLE 7 VERTICAL BULLET Sphere Cubic Horizontal Bullet Vertical Cylinder Horizontal Cylinder Rectangle Vertical Bullet TANK_WIDTH Tank width is modifiable only when the tank shape selected is Rectangle or Cubic TANK_LENGTH Tank Length is modifiable only when the tank shape selected is one among the following 1 Cubic 2 Horizontal bullet 3 Horizontal cylinder 4 Rectangle ...

Страница 68: ...r in DRY or WET While executing Volume Wet Calculation Method Level_1 table cannot be edited by user Product Level Value or Interface level value if Measured Product Type is Two Liquid Flooded is copied in the Level Table based on the selected strapping table index Level Table entry is limited by the Volume strapping Table Size If entry exceeds Volume strapping table Size the parameter check error...

Страница 69: ...lane region when the surface level is far from the reference plane This array can then be subtracted from the echo curve to improve near zone performance ECHOCURVE_ST_DIST Distance from reference to begin the curve ECHOCURVE_END_DIST Distance from reference to end the curve ECHOCURVE_RESOLUTION Distance between samples on the curve Lower number results in more detail but takes longer to process EC...

Страница 70: ...y increasing threshold END_OF_PROBE_REFL_MODEL_WT Determines the width of the Probe End wave where it crosses the x axis one half wavelength END_OF_PROBE_REFL_MODEL_GAIN Amplitude of the wave shape END_OF_PROBE_REFL_MODEL_ATTEN Increased attenuation results in smaller side lobes of the wave s shape END_OF_PROBE_OBJ_FUN_THRESHOL D If changing the gain does not help try increasing threshold PROCESS_...

Страница 71: ...ad only Surface Position SURFACE_AMP Read only Surface Amplitude INTERFACE_POS Read only Interface Position INTERFACE_AMP Read only Interface Amplitude END_OF_PROBE_POS Read only End of Probe Position END_OF_PROBE_AMP Read only End of Probe Amplitude REFERENCE_ECHO_STATUS Read only Reference Echo Status PROCESS_CONN_REF_POS Process Connector Reflection Position Observed Distance PROCESS_CONN_REF_A...

Страница 72: ... variable indicates the degree of match between the reflection model and the live echo curve data This value is 1 minus the objective function value see section 3 6 2 and values close to 1 represent a very good match If this number drops too low the reflection models should be checked as described in section 3 6 5 Signal Strength This variable indicates the amplitude of the indicated reflection Th...

Страница 73: ...pt to reload the firmware If the problem persists replacement of the sensor housing will be required Sensor Power Supply 2 5 OSC Fault Power Accumulator malfunction Power cycle the device and if problem persists replace Sensor housing If problem still persists replace the terminal block assembly Sensor Power Supply 2 5V Fault Power Accumulator malfunction Power cycle the device and if problem pers...

Страница 74: ...r reflection in remote mount transmitters Upload an echo curve and confirm that the reference and process connector only for remote mounts model parameters are set for a good match with actual reflections Perform a soft or hard reset Sensor NVRAM corrupt Sensor board NVRAM data has been corrupted Use sensor NVRAM corrupt reset method from host to clear the sensor NVRAM error This method will defau...

Страница 75: ...r zone near the End of Probe where measurements are not accurate This is a condition that can occur during normal operation and does not generally require corrective action If this condition is triggered when it is not expected verify that the Blocking Distance Low parameter is set correctly for the current conditions If distance to product is in Lower zone then status associated with device varia...

Страница 76: ... Distance Low parameter is set correctly for the current conditions If distance to interface is in Lower zone then status associated with device variables derived from distance to interface will be shown as uncertain in local display and on host the status would be poor accuracy Surface rate of change exceeded This indicates that the rate of change the product level is excedding the limit Check th...

Страница 77: ...𝑒 𝑤𝑎𝑠 𝑢𝑛𝑑𝑒𝑟 𝑠𝑡𝑟𝑒𝑠𝑠𝑓𝑢𝑙 𝑐𝑜𝑛𝑑𝑖𝑡𝑖𝑜𝑛𝑠 𝑇𝑖𝑚𝑒 𝑖𝑛 𝑠𝑒𝑟𝑣𝑖𝑐𝑒 𝑜𝑓 𝑡ℎ𝑒 𝑑𝑒𝑣𝑖𝑐𝑒 Power Cycle Track The power cycle track gives diagnostics related to the power up information of the device The Power Cycles is the number of power ups experienced by the device after leaving factory The Last Power Up Cycle time is the date and time of the last power up Operating Voltage Track The statistics data for the supply voltage...

Страница 78: ...reporting task another block alert may be reported without clearing the Active status if the subcode has changed EL_TEMP_DIAGNOSTIC Electronic Temperature Diagnostic parameters SENSOR_DIAGNOSTICS Sensor Diagnostics parameters POWER_TRAC Power Up Track Data OP_VOLTAGE Operating Voltage TIME_IN_SERVICE Summation of time in minutes that power has been applied to the device since leaving the factory S...

Страница 79: ...isplays communication board model part 2 SENSOR_MODEL_NO None Sensor model number Comm model number It is used to reconcile the model number from sensor to comm and vice versa SENSOR_NVRAM_RESET DISABLE ENABLE Enabled Resets the sensor NVRAM Attributes Supported Modes The block supports the following modes AUTO Automatic OOS Out of Service Alarm Types The block supports standard block alarms see s...

Страница 80: ...rt of the control strategy is selected an error appears in the Display Execution 3 8 1 Advanced Display The Advanced Display provides three formats and describes the field in each of the three Advanced Display formats namely PV Bar Graph and PV Trend Essentially all three formats provide the same information but with the following differences PV User configurable display shows the configured PV Ba...

Страница 81: ...ng the LCD block The selected parameter value will be displayed on the local display screen Table 12 LCD parameters Block FF Parameter RADAR LEVELTB Product Level Distance To Product Product Level Rate Interface Level Distance To Interface Interface Level Rate Vapor Thickness Product Volume Electronic Temperature Vapor Volume Upper Product Volume Lower Product Volume Upper Product Thickness ANALOG...

Страница 82: ... FF Parameter PID BLOCK PID SP PV OUT IN CAS_IN BKCAL_IN BKCAL_OUT RCAS_IN ROUT_IN RCAS_OUT ROUT_OUT FF_VAL TRK_VAL SIGNAL CHARACTERIZER BLOCK OUT_1 OUT_2 IN_1 IN_2 OUTPUT SPLITTER BLOCK CAS_IN BKCAL_IN_1 BKCAL_IN_2 BKCAL_OUT OUT_1 OUT_2 INTEGRATOR OUT IN_1 IN_2 ...

Страница 83: ...s the Active status in the Status attribute As soon as the Unreported status is cleared by the alert reporting task another block alert may be reported without clearing the Active status if the subcode has changed DISP_SEQ_TIME Periodic rotation time of the display screens in seconds Range 3 30 sec LANGUAGE Language selection for the Display Supported Languages English French German Spanish Turkis...

Страница 84: ... is present in all the eight screens CUSTOM_TAG_1 CUSTOM_TAG_2 CUSTOM_TAG_3 CUSTOM_TAG_4 CUSTOM_TAG_5 CUSTOM_TAG_6 CUSTOM_TAG_7 and CUSTOM_TAG_8 DISPLAY_TEMPLATE Represents the display screen template Possible Values a PV PV value is displayed b PV and Trend PV value followed by a Trend is shown on the display c PV and Bar Graph PV value followed by a Bargraph is shown on the display d None Screen...

Страница 85: ...ND_DURATION_3 TREND_DURATION_4 TREND_DURATION_5 TREND_DURATION_6 TREND_DURATION_7 and TREND_DURATION_8 DISPLAY_MESSAGE A message with a maximum of 64 characters that appears on the Advanced Display of the transmitter ROTATE_ENABLE Parameter to Enable or Disable screen rotation Attributes Supported Modes The block supports the following modes AUTO Automatic OOS Out of Service Alarm Types The block ...

Страница 86: ...ce to Level and Distance to Interface Values These values are used to calculate the Product Level Interface Level Vapor Thickness and Upper Product Thickness These values use Level use the elements in Product Level Range to determine the engineering units the decimal places for the display and also the high and low scale of the value This Product Level and Interface Level values are further used t...

Страница 87: ...True any calculated output below the low cut off value changes to zero This is only useful for zero based measurement devices such as flow The PV filter whose time constant is PV_FTIME is applied to the PV and not the FIELD_VAL Equations FIELD_VAL 100 channel value EU 0 EU 100 EU 0 XD_SCALE Direct PV channel value Indirect PV FIELD_VAL 100 EU 100 EU 0 EU 0 OUT_SCALE Ind Sqr Root PV sqrt FIELD_VAL ...

Страница 88: ...CALE determines the units conversion of the signal presented to the output When L_TYPE equals Direct OUT is the same as the value passed from the transducer block When L_TYPE is Indirect the PRIMARY_VALUE is converted to XD_SCALE and that value is set equal to OUT FIELD_VAL The OUT in is re ranged to a value using the OUT_SCALE OUT status The following table provides the resulting status of AI blo...

Страница 89: ...in block execution OUT The block output value and status SIMULATE A group of data that contains the current transducer value and status the simulated transducer value and status and the enable disable bit XD_SCALE Elements used to display the value obtained from the transducer block The elements are High and low scale values EU_100 and EU_0 Engineering units to display the value UNITS_INDEX Decima...

Страница 90: ...nged ALARM_SUM The summary alarm is used for all process alarms in the block The cause of the alert is entered in the subcode field The first alert to become active sets the Active status in the Status parameter As soon as the Unreported status is cleared by the alert reporting task another block alert may be reported without clearing the Active status if the subcode has changed ACK_OPTION Used to...

Страница 91: ...fers to the sensor limits Propagate Fault Forward If the status from the sensor is Bad Device failure or Bad Sensor failure propagate it to OUT without generating an alarm The use of these sub status in OUT is determined by this option Through this option the user may determine whether alarming sending of an alert is done by the block or propagated downstream for alarming Uncertain if Limited Set ...

Страница 92: ...chemes and it is commonly used The PID function integrates the errors If there is difference in process time constants of a primary process and secondary process measurement then the block can be cascaded if required Auto tuning is a feature that tunes the PID constants as per the process automatically Figure 14 PID Block Figure 15 PID Block Schematic Diagram ...

Страница 93: ...trol schemes are stable BYPASS can only be changed when the block mode is in MAN or OOS mode When BYPASS is set the value of SP in percent of range is passed directly to the target output and the value of OUT is used for BKCAL_OUT When the mode is changed to Cas the upstream block is requested to initialize to the value of OUT When a block is in Cas mode on the transition out of BYPASS the upstrea...

Страница 94: ...ing constants There are three tuning constants in the ideal PID equation The robust PID uses four tuning constants 1 GAIN is the tuning constant of the Proportional term 2 RESET is the tuning constant of the Integral 3 RATE is the tuning constant of the Derivative RATE is usually modified by a lag which is set at some fixed ratio higher than the rate time to create a rate gain There is no lag with...

Страница 95: ...pesetting A B or C has no effect on the validation of these tuning parameters The PID function block rejects all values outside the following ranges Table 15 PID Tuning parameters Parameter Initial Value Minimum Value Maximum Value Comment PV_FTIME 0 0 200 Units seconds GAIN 0 004 250 GAIN_NLIN 0 004 250 RATE sec 0 32 Ts 7500 The value of ZERO is permitted to turn off rate action RESET sec INF 2 T...

Страница 96: ...ontrol and is used for integrating process Auto tuning procedure There are nine parameters applicable for auto tuning AT_TYPE TUNING_CRITERIA TUNE_REQ ATI AT_MODE AT_ERR AT_GAIN AT_RESET and AT_RATE AT_Type There are two types of selections namely Disable and Cycle Tune When Disable is selected AT_MODE becomes inactive When Cycle Tune is selected AT_MODE becomes AT Ready TUNING_CRITERIA There are ...

Страница 97: ...miting and setpoint rate of change limiting OUT The block input value and status PV_SCALE The high and low scale values engineering units code and number of digits to the right of the decimal point associated with PV OUT_SCALE The high and low scale values engineering units code and number of digits to the right of the decimal point associated with OUT GRANT_DENY Options for controlling access of ...

Страница 98: ...ss limit status OUT_HI_LIM The maximum output value allowed OUT LO_LIM The minimum output value allowed BKCAL_HYS The amount the output value must change away from its output limit before limit status is turned off BKCAL_OUT The value and status required by the BKCAL_IN input of another block to prevent reset windup and to provide bump less transfer of closed loop control RCAS_IN Target setpoint a...

Страница 99: ...the block The cause of the alert is entered in the subcode field The first alert to become active sets the Active status in the Status parameter As soon as the Unreported status is cleared by the alert reporting task another block alert may be reported without clearing the Active status if the subcode has changed ACK_OPTION Used to set auto acknowledgment of alarms ALARM_HYS The amount the alarm v...

Страница 100: ...ied to calculated output value See OUT_LAG parameter Linear and non linear gain parameters are available ALGO_TYPE Configuration parameter specifies algorithm type which can be A B or C Type A equation where Proportional Integral and Derivative act on ERROR Type B equation where Proportional and Integral act on ERROR and Derivative acts on PV Type C equation where Integral acts on ERROR and Propor...

Страница 101: ...ing is disabled AT_ERROR Auto Tune Error supports the following errors Abort Not ready OK and Run AT_GAIN Auto tuned Gain AT_RESET Auto tuned Reset AT_RATE Auto tuned Rate Attributes Supported Modes The block supports the following modes AUTO Automatic MAN Manual OOS Out of Service IMan Cas RCas ROut LO Alarm Types The block supports standard block alarms see section 3 2 in addition to it standard...

Страница 102: ...ports signal status propagation The block is used to provide control input selection in the forward path only and hence no back calculation support is provided SELECTED indicates which input has been selected or the number of inputs selected by the algorithm The block does not support process alarms Figure 16 Input Selector Block Execution 3 11 1 Input processing If DISABLE_n is True the correspon...

Страница 103: ...umber of the input with the highest value If SELECT_TYPE is Middle if there are 3 or 4 values the highest and lowest value is discarded The average of the remaining two values is computed and the value is transferred to the output of the block The value of SELECTED becomes zero if an average is used else the value of SELECTED is the number of the input with the middle value If SELECT_TYPE is Avera...

Страница 104: ...s may be shown OUT The block output value and status GRANT_DENY Options for controlling access of host computers and local control panels to operating tuning and alarm parameters of the block Not used by device STATUS_OPTI ONS It helps to select options for status handling and processing The supported status option for the integrator block is Use Uncertain as Good Uncertain if MAN mode IN_1 The bl...

Страница 105: ...the Active status if the subcode has changed Attributes Supported Modes The block supports the following modes AUTO Automatic MAN Manual OOS Out of Service Alarm Types The block supports standard block alarms see section 3 2 Status Handling During normal operations the value and status of the selected input is shown by OUT If the number of inputs with Good status is fewer than MIN_GOOD then the ou...

Страница 106: ...ate volume or mass variation in vessels or as an optimizing tool for flow ratio control The block does not support process alarms ATTENTION Alternatively IN_1 and IN_2 can be used as pulse inputs coming from other blocks The same general rules for integration applies for the accumulation of pulses Figure 18 Integrator Block Execution The basic function of the Integrator block is to integrate an an...

Страница 107: ...option is Rate Each input needs a parameter to define the rate time unit IN_1 IN_2 The time unit can be selected in seconds minutes hours days The second analog input must be converted into the same unit as that of the first input IN_2 must be converted into the same units of IN_1 This can be done by using the parameter UNIT_CONV For example if IN_1 is in seconds and if IN_2 is in minutes IN_2 mus...

Страница 108: ...SE_VAL2 as appropriate The result is the increment in engineering units of for example mass volume or energy per block execution Net Flow The Net Flow is calculated by considering the direction of flow The direction of the flow is calculated by selecting the parameters REV_FLOW and REV_FLOW2 When the status is set to True for any of these two parameters the direction of the flow for that input is ...

Страница 109: ...becomes zero The integration starts as SP and increments are subtracted from the SP DN_DEM The output is calculated even beyond zero till the block is reset The integration starts from SP PERIODIC The integration is done for the assigned period specified in seconds in CLOCK_PER After that period the block is reset automatically DEMAND The integration is done positive or negative depending on the d...

Страница 110: ...pe 3 or 4 it starts from a value given by TOTAL_SP When the value of OUT is equal to or less than PRE_TRIP the discrete output OUT_PTRIP is set When the count reaches zero the discrete output OUT_TRIP is set OUT_PTRIP remains set When a reset occurs the comparisons that set OUT_PTRIP and OUT_TRIP are no longer True so they are cleared OUT_TRIP shall remain set for five seconds after an automatic r...

Страница 111: ...ed the input IN_1 IN_2 whose status is Bad is considered for integration INTEG_OPTS 0 Carry This option is used only for UP_AUTO and DN_AUTO kind of integrations only When this option is selected the residual value after the integration is added subtracted from the integral value in the next cycle of integration INTEG_OPTS 0 Add Zero if Bad When this option is selected if IN_1 IN_2 is bad the inpu...

Страница 112: ...tion OUT The block output value and status OUT_RANGE The high and low scale values engineering units code and number of digits to the right of the decimal point associated with OUT GRAND_DENY Options for controlling access of host computers and local control panels to operating tuning and alarm parameters of the block not used by the device STATUS_OPTS It helps to select option for status handling...

Страница 113: ... up of PRE_TRIP when counting down N_RESET Counts the number of resets It cannot be written or reset PCT_INC Indicates the percentage of inputs with Good status compared to the ones with Bad or Uncertain and Bad status GOOD_LIMIT Sets the limit for PCT_INC Below this limit OUT receives the status Good UNCERTAIN_LIMIT Sets the limit for PCT_INC Below this limit OUT receives the status Uncertain OP_...

Страница 114: ...d together and the resulting status is the worst of the two The option Add zero if Bad in INTEG_OPTS causes the net increment to be zero if its status is Bad The percentage of Bad or Uncertain and Bad counts can be determined by calculating the value of PCT_INCL from Rtotal and Atotal As Atotal is the sum of increments with Good and Bad status and Rtotal is the sum of increments with Bad status At...

Страница 115: ...aditional Summer Fourth order polynomial Simple HTG compensated level Fourth order Polynomial Based on PV Figure 20 Arithmetic Block Execution The block has five inputs namely IN IN_LO IN_1 IN_2 and IN_3 The first two inputs IN IN_LO are designed for a range extension function that results in a Process Variable PV with the status indicating the input in use The remaining three inputs IN_1 IN_2 and...

Страница 116: ...d greater than RANGE_LO then g is set to one If the status of IN is unusable and IN_LO is usable and less than RANGE_HI then g is set to zero For three auxiliary inputs six constants are used and each input has a BIAS_IN_i and a GAIN_IN_i The output has a BIAS and a GAIN static constant For the inputs the bias is added and the gain is applied to the sum The result is an internal value called t_i i...

Страница 117: ...𝑡𝑒𝑑 3 Flow compensation approximate Both IN_2 and IN_3 would be connected to the same temperature 𝑓𝑢𝑛𝑐 𝑓 𝑃𝑉 𝑓 𝑡_1 𝑡_2 𝑡_3 𝑡_3 𝑙𝑖𝑚𝑖𝑡𝑒𝑑 4 BTU flow where IN_1 is inlet temperature and IN_2 the outlet temperature 𝑓𝑢𝑛𝑐 𝑓 𝑃𝑉 𝑓 𝑡_1 𝑡_2 𝑙𝑖𝑚𝑖𝑡𝑒𝑑 5 Traditional Multiply Divide 𝑓𝑢𝑛𝑐 𝑓 𝑃𝑉 𝑓 𝑡_1 𝑡_2 𝑡_3 𝑙𝑖𝑚𝑖𝑡𝑒𝑑 6 Average 𝑓𝑢𝑛𝑐 𝑃𝑉 𝑡_1 𝑡_2 𝑡_3 𝑓 f number of inputs used in computation unusable inputs are not used 7...

Страница 118: ... is not checked of processed by the block ALERT_KEY The identification number of the plant unit This information may be used in the host for sorting alarms etc MODE_BLK The actual target permitted ad normal modes of the block Target The mode to go to Actual The mode the block is currently in Permitted Allowed modes that target may take Normal Most common mode for target BLOCK_ERR This parameter re...

Страница 119: ...er value for IN_3 COMP_HI_LIM Determines the high limit of the compensation input COMP_LO_LIM Determines the low limit of the compensation input ARITH_TYPE The set of 9 arithmetic functions applied as compensation to or augmentation of the range extended input BAL_TIME Specifies the time for a block value to match an input output or calculated value or the time for dissipation of the internal bala...

Страница 120: ... Manual OOS Out of Service Alarm Types The block supports standard block alarms see section 3 2 Status Handling The INPUT_OPTS bit string controls the use of auxiliary inputs with less than Good status The status of unused inputs is ignored The status of the output is the worst of the inputs used in the calculation after applying INPUT_OPTS ...

Страница 121: ...se the backward control path the block provides an option to swap the axes of the function Figure 22 Signal Characterizer Block The block calculates OUT_1 from IN_1 and OUT_2 from IN_2 using a curve given by the co ordinates x1 y1 x2 y2 x21 y21 Where x is the Input and y is the Output The x coordinates are given in engineering units of X_RANGE The y coordinates are given in engineering units of Y_...

Страница 122: ...ller than x1 and the output is at ym when the input is larger than xm Since the ends of the y curve act as limits the OUT status is shown when either limit is active Backward Control path A reverse function swaps the interpretation of IN_2 and OUT_2 that provides a way to do reverse calculation using the same curve If the parameter SWAP_2 is set to True the block provides IN_1 x and OUT_1 y while ...

Страница 123: ...s OUT_2 The block output value and status X_RANGE The display scaling of the variable corresponding to the x axis for display It has no effect on the block Y_RANGE The display scaling of the variable corresponding to the y axis for display It has no effect on the block GRANT_DENY Options for controlling access of host computers and local control panels to operating tuning and alarm parameters of t...

Страница 124: ...the input is limited the appropriate limit must be indicated in the output sub status Limits shall be reversed if the curve slope is negative If SWAP_2 is set cascade initialization is controlled by the lower block When this block is in OOS mode the cascade to both the lower and upper blocks is broken by Bad status at the outputs When the block goes to AUTO mode the lower block can begin cascade i...

Страница 125: ...ionately to full as the input drops to 0 and the other valve opens proportionately as the input rises above 50 In a typical sequencing application both the valves are closed at 0 input One of the valves opens proportionately to full as the input rises to 50 while the other stays shut The second valve opens as the input rises above 50 and the first valve may remain open or shut off quickly As this ...

Страница 126: ... and 2nd coordinates of the nth curve respectively IN_ARRAY OUT_ARRAY Index Coordinate Index Coordinate 1 X11 Start value of SP for the OUT_1 line X11 X12 1 Y11 Value of OUT_1 at X11 2 X12 End value of SP for the OUT_1 line X11 X12 2 Y12 Value of OUT_1 at X12 3 X21 Start value of SP for the OUT_1 line X21 X22 3 Y21 Value of OUT_2 at X21 4 X22 Start value of SP for the OUT_1 line X21 X22 4 Y22 Valu...

Страница 127: ...11 when X is greater than X12 Some hysteresis in the switching point may be required because the output may change by a full stroke of the valve HYSTVAL contains the amount of hysteresis If X X12 HYSTVAL OUT_1 may be determined by the calculated y value If X12 HYSTVAL X X12 and X has not reached X12 since it was less than X12 HYSTVAL OUT_1 may be determined by the calculated y value If X transitio...

Страница 128: ...of out_1 of the block OUT_2_RANGE The maximum value range of out_1 of the block GRANT_DENY Options for controlling access of host computers and local control panels to operating tuning and alarm parameters of the block Not used by the device STATUS_OPTS Helps select options for status handling and processing The supported status options for the OS block are IFS if Bad CAS_IN and Target to next per...

Страница 129: ...the Unreported status is cleared by the alert reporting task another block alert is reported without clearing the Active status if the subcode has changed Attributes Supported Modes The block supports the following modes AUTO Automatic IMAN Manual OOS Out of Service Cas Alarm Types Standard block alarm Status Handling Sub status values received at CAS_IN shall be passed to both outputs except for ...

Страница 130: ...block specifies this update interval To provide predictable restart behavior in the transmitter the following Non Volatile parameters are updated to NVM each time they are written over the fieldbus MODE TARGET for all blocks SP VALUE for the PID block Since these are user written parameters these additional updates to NVM contribute negligibly to NVM wear out However users are cautioned to not con...

Страница 131: ...d or change selected operating parameters in a Transmitter database The process of viewing and or changing database parameters is called configuration Configuration can be accomplished both online and offline with the Transmitter powered up and connected to the handheld The online configuration immediately changes the Transmitter operating parameters For offline configuration Transmitter operating...

Страница 132: ...d or deleted Before block instantiation the device checks whether the particular block is supported and if there is sufficient memory to store the parameters After Instantiation the instantiated block must be loaded into the device and then the strategies can be created Block instantiation using Experion PKS The following are the steps for performing block instantiation using Experion PKS Step Act...

Страница 133: ...wnload classes 1 2 3 The transmitter supports only one type of download class as per FOUNDATION Fieldbus specifications SLG 700 device FF variant supports download type Class 3 only A class 3 firmware download is performed irrespective of whether the device is ON OFF process Class 3 When class 3 download is performed the device prepares for the download and goes out of the link as the memory of th...

Страница 134: ...firmware to one device type at a time in a H1 link This reduces the chance for unknown interactions between devices to cause link issues or download failures 4 Reduce usage of DTM through tools like FDM in the H1 link This reduces the traffic on the link and therefore reduces the time required for the download to complete 5 Parallel Firmware downloads from single Control Builder Firmware downloads...

Страница 135: ...laced by Multidomain Family Device Type is represented as four hexadecimal digits leading and trailing zeroes are included Leading 0 s are not suppressed for Manufacturer ID and Device Type Trailing blanks are stripped from Device Family Domain Name Software Name and Software Revision If Software Name or Software Revision is composed of all blanks then the underscore that would have proceeded is o...

Страница 136: ...er application Microsoft NET Framework Latest FF Communication DTM Free version of FF Communication DTM available for download from CodeWrights website The SLG700 FF DTM can be downloaded from Honeywell website www honeywellprocess com NI FBUS communication modem NI FBUS communication modem driver Available at www ni com 6 3 Downloads Download 1 PACTware 4 x and NET 2 0 Download from http pactware...

Страница 137: ...f NI modem USB connector to the PC COM port 5 Run PACTware and select the Device Catalog option under the View menu The Device Catalog window should open to the right hand side of the display 6 Click on the Update Device Catalog button at the bottom of the Device Catalog window and click on Yes in the confirmation pop up window 7 Select the Project option on the Window menu to close the Device Cat...

Страница 138: ...ion User s Guide Rev 3 0 8 Right click on the selected project and select Add Device from the context menu 9 In the device pop up window select the FF H1 Communication DTM device and click on the OK button at the bottom of the window ...

Страница 139: ...ION Fieldbus Option User s Manual Page 123 10 The popup will be appear as below then click on Yes 11 Right click on the FF H1 Communication DTM device in the project view and select Add Device from the context menu ...

Страница 140: ...LG700 device that matches the transmitter model SLG 700 Rev 1 R100 Rev 2 R101 and Rev 3 R102 13 Click on the OK button at the bottom of the window 14 Right click on the SLG700 FF device in the project menu 15 Select Connect from the context menu After a few seconds the device label should turn to bold ...

Страница 141: ...tional functions 17 Then select Set DTM Address from the context menu The new window will open then provide device address device to be commissioned before this with experion or NI host Double click on the SLG700 Rev 1 R100 or Rev 2 R101 or Rev 3 R102 in the project window depending on which firmware version is running on the SLG700 transmitter ...

Страница 142: ...ial reading of data is completed then the user can observe each transducer block menu to advance to the main menu items 1 Go through the respective block and perform action for example double click on LEVELTB block and click on menu DEVICE and then tick the block mode target as OOS to configure the parameters 2 The above statement can be applicable for all the blocks to configure the parameters ...

Страница 143: ...Rev 5 FOUNDATION Fieldbus Option User s Manual Page 127 6 5 DTM Help Take the mouse over the symbol next to a parameter to read its description ...

Страница 144: ...the SLG 700 transmitter in most applications This configuration consists of few parameters Level TB contains three main menus Device Process Diagnostics 6 6 1 Device menu This menu contains three tabs namely Block modes Ranges Sensor Block Mode This menu provides facility to the user to select the mode of the target device to configure any parameter user has to keep the target mode as OOS if it is...

Страница 145: ... Manual Page 129 Ranges Using this tab Level range Product volume range Level rate range and its units can be configured Level mm cm m in ft Level Rate m s m h in s in min ft s ft min Volume l m in ft yd US gal US bbl liq US bbl oil imp gal ...

Страница 146: ... Guide Rev 3 0 Sensor This menu contains parameters which are related to sensor such as sensor serial Number Hardware revision firmware version of sensor etc Device Reset will be part of Field Diagnostics which is available under Resource block ...

Страница 147: ...on Process variables and Trends as shown below The Process configuration menu groups the most commonly modified parameters into five categories Process Measurement Probe Mounting Attenuation The parameters in these groups address the major site specific configuration that might be needed during the commissioning of a transmitter ...

Страница 148: ...dium are slowed by an amount related to the dielectric constant 2 The relative amount of the original pulse that is reflected from the boundary between two mediums is related to the dielectric constants of the media on each side of the interface For the reflected pulse the reduction in the amplitude with respect to the original pulse amplitude can be calculated from the dielectric constants of the...

Страница 149: ... above the product This application is shown in Figure 30 Figure 30 Single Liquid Two Liquids Flooded In this application there are two liquid products in the tank one supported on top of the other as shown below in Figure 31 As the name indicates the tank is always full with the Upper Product occupying the entire upper portion of the tank so that there is no vapor above the Upper Product The SLG ...

Страница 150: ...Required by Application Single Liquid Two Liquid Non Flooded Two Liquid Flooded Vapor DC Vapor DC Product DC Upper Product DC Upper Product DC Lower Product DC Lower Product DC The dielectric constant of most gasses is very close to 1 0 and the Vapor Dielectric Constant parameter will most often not need to be edited Enter the correct value if it is significantly different than 1 0 Upper Product L...

Страница 151: ...ottom reference plane This fixed bottom reference plane should be a location from which accurate measurements to the reference Plane can be obtained It may be the bottom of the vessel but it may also be the ground or other convenient location and does not necessarily have to be the plane that represents a level of 0 0 Level Offset C The distance between the fixed bottom reference plane and the pla...

Страница 152: ... it should be the distance to the top of the end weight Reference plane R The GWR transmitter inherently measures the time of flight of radar pulses that reflect off the boundary between two different mediums This time is first transformed into a measure of the distance between a fixed point on the transmitter body referred to as the Reference Plane and the boundary between the two medium The Refe...

Страница 153: ...via drop down Probe End Type This parameter specifies how the probe is terminated For Rod and Coaxial probes the only available option is None For Wire probes the available options are Clamp Weight and Loop Probe Length This is a factory setting based on the purchase order Adjustments to this parameter is only required if the probe has been replaced or cut shorter This parameter should always be m...

Страница 154: ... the Low Transition Distance The minimum value for Blocking Distance Low as well as transition distances is shown in Table 23 Blocking Distance High Blocking distances are areas of the sensor reading range where it is not desirable to search for reflections possibly due to poor signal to noise ratios The Blocking Distance High is the distance value measured starting from the Sensor Reference Plane...

Страница 155: ...es It is recommended that a value somewhat larger than that 6 6 2 7 Mounting The main configuration parameters in this group deal with describing how the transmitter is physically mounted to the tank The lower portion of the display provides access to a number of advanced options and actions that may be necessary to fine tune the transmitter performance in cases where the characteristics of the mo...

Страница 156: ... how the GWR transmitter is located on the tank The available selections are Tank Mounted to a flat surface in the tank ceiling or wall Bracket Mounted to a bracket over an open roof tank Nozzle See transmitter specifications for limits on nozzle dimensions Bypass See transmitter specifications for limits on bypass dimensions Stillwell Stillwell must extend beyond the length of the probe Unknown T...

Страница 157: ...ell as any false echoes generated by obstacles in the tank ladders pipes valves in the vicinity of the probe There is no limit on the length that can be specified by the user As with the field background the level in the tank needs to be about 30cm below the end of the requested echo One difference between the obstacle suppression echo and the field background echo is that the sensor algorithms an...

Страница 158: ...ound is also stored in permanent memory and is applied after a sensor reset if dynamic background is enabled At all times the sensor maintains a copy of the original user acquired static background echo and will revert to this if the dynamic background feature is once again disabled Re enabling dynamic background at that point starts the process anew It is recommended that this feature is turned o...

Страница 159: ...length of this region varies with the transmitter model mounting location and probe type A pop up message similar to the one shown below will be displayed indicating the required length If the OK option is selected another message will pop up asking for user input whether can be moved to OSS since Field background capture can be performed only in OOS mode as shown below once block is moved to OOS ...

Страница 160: ...completion of the process a pop up message such as the one shown below will be displayed indicating whether the capture was successful or not In the case of a successful capture there may also be some additional information or warnings provided The new background is immediately applied by the transmitter but sees the comments above for the active Background Type parameter Method will ask whether t...

Страница 161: ...ation Vapor Attenuation This sets the linear attenuation coefficient Radar Pulse energy dissipation of Vapor Linear Attenuation Model The gain amplitude of the radar reflection is exponentially decayed based on the linear attenuation coefficient This accounts for radar pulse energy dissipation to the vapor and media surrounding the probe and is a function of the distance travelled This is modeled ...

Страница 162: ... reflections this reference point is the transmitter s Reference Plane For the Interface reflection this reference point is the location of the Surface reflection in non flooded applications and the location of the transmitter s Reference Plane for flooded applications The Reflection Model panel has entry fields where the locations of these reference points can be entered In many cases these locat...

Страница 163: ...6 2 Process variable Button is shown clicking that button we get to this Menu This page will show values of different process parameters in dial form Trends menu Trends menu contains the Trends of all Device variables of transmitters In Section 6 6 2 Trends Button is shown clicking that button we get to this Menu This page will show values of different process parameters in Trend form ...

Страница 164: ... FOUNDATION Fieldbus Option User s Guide Rev 3 0 6 6 4 Diagnostics Diagnostics menu consists of block errors alarms and Static Revision the detail description of block error information is available in Table 3 ...

Страница 165: ...enu provides the facility to select the mode of the target device to configure any parameter keep the target mode as OOS if it is in AUTO mode then the parameters can t be configured Block Modes General This menu consists of block errors the detail description of diagnostics information is available in Table 3 ...

Страница 166: ...description of diagnostics information is available in Table 36 Diagnostics Electronic Temperature Diagnostics This menu consists of Max Electronic Temperature Min Electronic Temperature Electronics Temperature Unit ET Over Range CTR ET Over Range Date ET Under Range CTR and ET Under Range Date parameters the description of diagnostics information is available in Table 36 Diagnostics ...

Страница 167: ...n critical status 1 non critical status the description of diagnostics information is available in Table 36 Diagnostics Device Model Details This menu consists of comm model details such as model key model part 1 model part 2 and model number reconcile selection the description of the device model detailed information is available in Table 36 Diagnostics ...

Страница 168: ... Time in service Service life Stress monitor parameters the description of diagnostics information is available in Table 36 Diagnostics Power Track This menu consists of Power cycle last pawer up cycle time parameters the description of diagnostics information is available in section Table 36 Diagnostics ...

Страница 169: ...Page 153 Operating Voltage Track This menu consists of supply voltage minimum voltage reset minimum voltage status of current voltage last minimum volage time parameters the description of diagnostics information is available in Table 36 Diagnostics ...

Страница 170: ...vice to configure any parameter keep the target mode as OOS if it is in AUTO mode then the parameters can t be configured 6 8 2 Display Settings This menu consists Rotation time Language Language pack Display connected Contast level Display software version Message Rotate enable parameters the description of parameters under display settings menu is available in section 3 8 3 ...

Страница 171: ...e 1 Custom unit 1 Custom tag 1 Screen format 1 Decimals 1 Low limit 1 High limit 1 Trend duration 1 parameters the description of parameters is available in section 3 8 3 Similarly screen 2 to 8 has the same parameters as like screen 1 General This menu consists of block errors the detail description of diagnostics information is available in Table 3 ...

Страница 172: ...e process or mounting configuration changed from what was ordered some of the default options may need to be adjusted Aux TB contains three main menus Device Configuration diagnostics 6 8 4 Device menu This menu contains three tabs namely Block modes parameters it provides the facility to select the mode of the target device to configure any parameter keep the target mode as OOS if it is in AUTO m...

Страница 173: ...ry and it is possible that the Product Level will not be equal to Sensor Height Level Offset Distance to Product Likewise for the Interface if is being calculated Table should be entered either in ascending or descending order only Enable Linearization If enabled linearization will convert the level as measured by the sensor to a corrected level value as defined by the user in the linearization ta...

Страница 174: ...curve and at each step calculate the difference between the model and the echo curve referred to as the Objective Function Typically the smallest value of the Objective Function corresponds to the level selected by the sensor algorithms but the values must be below a user defined threshold In case of multiple local minima there is additional logic to select the best candidate The final best candid...

Страница 175: ... side lobes to either side of the central lobe Increased attenuation results in smaller side lobes Note that the asymmetric property means that the side lobes will each have a slightly different shape This attenuation parameter should not be confused with the medium attenuation that determines how the RADAR amplitude diminishes as it propagates down the probe There are a total of 5 reflection mode...

Страница 176: ...re the optional Remote Mount Cable is installed as it indicates the observed distance between the Reference and Process Connector reflections It is a calculated offset and is therefore a read only parameter If the Remote Mount cable is not installed this offset will default to zero The Reference Plane Offset m is a read only parameter that is determined in the factory for each transmitter It corre...

Страница 177: ...ge etc The calculation of volume by the transmitter is based on measured level and additional tank geometry measurements Wet Volume Calibration When the measured level for the tank reaches a level where the corresponding volume is known select a row in the method enter the corresponding volume in the textbox below and proceed further This will immediately set the values into the selected row in th...

Страница 178: ...e Units Resolution to select the resolution to select the resolution of the data collected Impacts upload time Clear Echo curve Save To File Allows users to save to disk and later perform analyses on the data or send for offline analysis by experts For detail information on how to take Echo curve using different types refer section 3 6 3 and for trouble shooting the echo curve please refer section...

Страница 179: ...OUNDATION Fieldbus Option User s Manual Page 163 6 10 Diagnostics Diagnostics menu consists of block errors alarms and Static Revision the detail description of block error information is available in Table 3 ...

Страница 180: ...ity to select the mode of the target device to configure any parameter keep the target mode as OOS if it is in AUTO mode then the parameters can t be configured 6 11 2 Field Diagnostics This menu consists of field diagnostics parameters the description of parameters under display settings menu is available in section 3 4 3 Alarms tab ...

Страница 181: ...Rev 5 FOUNDATION Fieldbus Option User s Manual Page 165 Mapped tab Mask tab ...

Страница 182: ...Page 166 FOUNDATION Fieldbus Option User s Guide Rev 3 0 Priority tab Simulate tab ...

Страница 183: ...Rev 5 FOUNDATION Fieldbus Option User s Manual Page 167 Active tab General tab ...

Страница 184: ...age 168 FOUNDATION Fieldbus Option User s Guide Rev 3 0 6 11 3 Common Diagnostics General tab This menu consists of block errors the detail description of diagnostics information is available in Table 3 ...

Страница 185: ...es the transducer s input data selected by channel number and makes it available to other function blocks at its output For details information of calculation equation of Output from Level Transducer block refer section 3 5 Figure 36 Analog Input Block Level TB contains three main menus Device Process Variables Diagnostics ...

Страница 186: ...ck Mode This menu provides the facility to select the mode of the target device to configure any parameter to keep the target mode as OOS if it is in AUTO mode then the parameters can t be configured Configuration is also available in Permitted mode normal mode Configuration This menu contains required parameters for configuration of AI block to function ...

Страница 187: ...te Interface Level Distance To Interface Interface Level Rate Vapor Thickness Product Volume Electronic Temperature Vapor Volume Upper Product Volume Lower Product Volume Upper Product Thickness For details information of using configuration tab refer Section 3 9 1 Scaling Scaling menu contain three sub menu namely Channel refer section 7 11 1 2 Transducer scaling and Output scale units ...

Страница 188: ...mic Variable which display the Output value with units and status of AI block for details refer section 3 9 Diagnostics This menu contains two sub menus namely General and Alarms General General menu consists of block errors alarms and Static Revision the detail description of block error information is available in Table 3 ...

Страница 189: ...n User s Manual Page 173 Alarms The block supports standard block alarms see section 3 3 Additionally it supports standard HI_HI HI LO and LO_LO alarms applied to OUT For details on configuration of Process alarms refer section 3 3 1 ...

Страница 190: ...stics to monitor the functions and status of the device operations When errors and or faults are detected they are reported in the status bits of certain block parameters for example BLOCK_ERR The other parameters can be seen by viewing the status descriptions and or a value which may help to identify a fault Device status and operational faults are identified by viewing key parameter values or st...

Страница 191: ...its determine the cause and correct it Insufficient current to the device Measure the DC current voltage ranges to the device The DC current voltage ranges must be within the limits If the current voltage is insufficient determine the cause and correct it More than two or less than two terminators are wired to fieldbus link Check to see that only two terminators are present on a link Correct if ne...

Страница 192: ...nded action Incorrect Standard Dictionary Device Description DD or Symbols on host computer Verify that the Standard Dictionary the DD or symbols files are correct for the device Install the compatible version of Standard Dictionary and DD for the device on the host computer Incorrect pathnames to descriptions on host computer Check that the pathnames to locations of the Standard Dictionary and DD...

Страница 193: ...k Problem cause Things to check Recommended action Resource block mode is OOS mode and is not going to AUTO mode Read MODE_BLOCK PERMITTED Add AUTO mode to MODE_BLOCK PERMITTED Read MODE_BLOCK ACTUAL of Resource block If necessary Set MODE_BLOCK TARGET to AUTO NOTE If the mode is set to OOS for maintenance then do not change the mode to AUTO Resource block is not running Check BLOCK_ERR for errors...

Страница 194: ...parameters used by sensor and stored in the communication board EEPROM differs Restart of Device required If error persists try replacing the Electronics module If this does not fix the problem replace the sensor module Sensor and Communication Board Database version Mismatch This fault is set if configuration parameters database version used by sensor differs from communication board EEPROM datab...

Страница 195: ...e then status associated with device variables derived from distance to product will be shown as uncertain in local display and on host the status would be poor accuracy Interface in BDH This indicates that interface reflection has been tracked into the upper zone near the Reference Plane where measurements are not accurate This is a condition that can occur during normal operation and does not ge...

Страница 196: ...e has valid ranges and units assigned Check Field Diagnostics Status bit of Characterization data and Calibration data Corrupt and Sensor Characterization Status and Sensor Calibration Status bits of Sensor Details Status parameter of Diagnostic Block Change the Sensor housing Verify parameter Distance To Level and Product Level Value status are not GOOD Verify the Surface configuration of the Cor...

Страница 197: ... Diagnostic Block Change the sensor housing Verify parameter Distance To Interface and Interface Level Value Status are not GOOD Verify that correct Measured Product Two Liquid Flooded or Two Liquid Non Flooded and the Surface and Interface configuration of Correlation Algorithm parameters and Sensor parameters configuration Ensure that Auxiliary Transducer block is in AUTO mode Check Sensor Confi...

Страница 198: ...igned Verify that correct Correlation Algorithm Surface and Interface values are assigned by reading Echo curve again Transducer Block does not produce valid Vapor Thickness and Vapor volume Check Distance to Product Product Level value Verify sensor configuration and correlation algorithm configuration Transducer block does not produce valid Upper Product Thickness Upper Product Volume and Lower ...

Страница 199: ...ock mode is in OOS and does not change to AUTO mode Read MODE_BLOCK PERMITTED Add AUTO mode to MODE_BLOCK PERMITTED Read MODE_BLOCK ACTUAL of Resource block If necessary Set MODE_BLOCK TARGET to AUTO NOTE If the mode is set to OOS for maintenance then do not change the mode to AUTO Sensor Diagnostics Sensor voltage diagnostics Electronic temperature diagnostics values are not updating Read UPLOAD_...

Страница 200: ... is available remove and reconnect the local display and check if display powers up If display is not powering up contact Honeywell TAC Writing to some of display parameter in SCREEN_1 SCREEN_2 SCREEN_3 SCREEN_4 SCREEN_5 SCREEN_6 SCREEN_7 or SCREEN_8 fails Check DISPLAY_TYPE These parameters are supported only by the Advanced Display Local display shows Attention as title with some text Check the ...

Страница 201: ...OOS mode with Block Configuration Error Read CHANNEL parameter and range CHANNEL must be set to a valid value and cannot be left at the initial value of zero XD_SCALE UNITS_INDX must be compatible with the units in the transducer block for the channel Read L_TYPE parameter L_TYPE must be set to Direct Indirect or Indirect Square Root and cannot be left at the initial value of zero Check if L_TYPE ...

Страница 202: ... Table 35 Read SP_HI_LIM SP_LO_LIM OUT_HI_LIM OUT_LO_LIM Check that SP_HI_LIM SP_LO_LIM OUT_HI_LIM OUT_LO_LIM Mode does not change from IM target mode is MAN AUTO or Cas No path to process Assure that the downstream blocks to at least one AO are all in Cas mode and that the path ends in an AO block All BKCAL connections must be linked Mode does not change from MAN target mode is MAN AUTO or Cas Ch...

Страница 203: ...Mode Schedule the block to execute Input Selector block mode is in OOS mode with Block configuration Error Check SELECT_TYPE SELECT_TYPE must be set to a valid value and cannot be left at 0 Status of output is Bad Check Inputs Make sure at least one input has status as good Check OP_SELECT OP_SELECT is not set to 0 or it is linked to an input that is not used and it points to an input that is Bad ...

Страница 204: ... mode is set to OOS for maintenance then do not change the mode to AUTO Mode does not change from OOS Configuration error BLOCK_ERR shows the Block Configuration Error condition since ARITH_TYPE is not set Value of output is incorrect Error in configuration Ensure that engineering units are correct for the computation If that fails see section 3 Block alarms are not reported Read FEATURE_SEL Repor...

Страница 205: ...ge the mode to AUTO Mode does not change from OOS Configuration error BLOCK_ERR shows the Block Configuration Error condition This could be because The block IN_ARRAY is not configured correctly or LOCKVAL is not set to a valid value Value of output is incorrect Error in configuration Ensure that engineering units are correct for the computation Also check if IN_ARRAY and OUT_ARRAY are configured ...

Страница 206: ...necessary Set MODE_BLOCK TARGET to AUTO NOTE If the mode is set to OOS for maintenance then do not change the mode to AUTO Mode does not change from OOS Configuration error BLOCK_ERR shows the Block Configuration Error condition due to array configuration errors Value of output is incorrect Error in X or Y array See section 3 Block alarms are not reported Read FEATURE_SEL Reports are not selected ...

Страница 207: ...ge CHANNEL 0 1 13 Initial Value is a configuration error Set value to valid range L_TYPE 0 Uninitialize 1 2 3 direct indirect sq root Initial Value is a configuration error Set value to valid range PV_FTIME 0 0 200 Set value to valid range ALARM_HYS 0 5 0 50 Set value to valid range HI_HI_PRI HI_PRI LO_LO_PRI LO_PRI 0 0 15 Set value to valid range HI_HI_LIM HI_LIM INF INF or within OUT_SCALE range...

Страница 208: ...Page 192 FOUNDATION Fieldbus Option User s Guide Rev 3 0 Parameter Initial Value Valid Range Corrective Action SP_HI_LIM SP_LO_LIM 100 0 PV_SCALE 10 Verify that SP_HI_LIM SP_LO_LIM ...

Страница 209: ...ailure is detected a status bit is set in the BLOCK_ERR parameter in the appropriate block object Diagnostic checks are performed continuously on the device functional databases of the transmitter application shown in Table 36 Table 36 Diagnostics Device Functional Area Location Block object database DB RAM and EEPROM Communication stack database DB EEPROM Boot ROM ROM Program ROM ROM Trend and li...

Страница 210: ...ues to calculate PV output 2 Critical Fault Transmitter drives PV output to failsafe state 3 Block Configuration Errors Incorrect parameter values causes the transmitter to generate a fault for example BLOCK_ERR or MODE_BLK OOS A description of each condition in each category is provided in Table 37 Table 38 and Table 39 The condition is described a probable cause is stated and a recommended corre...

Страница 211: ...ge See Table 39 Good constant Uncertain Non critical See Table 38 AI ALARM_SUM CURRENT Block alarm Critical Non critical See BLOCK_ERR of all blocks in the device in Table 3 Process alarm Non critical See Table 38 All Blocks BLOCK_ERR Block Configuration Error 1 Non critical Check the value of all configurable parameters in the block and correct if necessary See Resolving the block configuration e...

Страница 212: ...e table is typical of values or messages seen when using the NI FBUS configurator Critical Fault In the case of a critical fault due to Memory Failure NV Static data loss or the readback check failure writes to the RESTART parameter twice for the transmitter to fully recover from the fault condition Therefore 1 Write 4 or restart processor to RESTART parameter of resource block 2 Wait until commun...

Страница 213: ...tatus inaccurate PV value of transducer block is outside range of XD_SCALE When AI block CHANNEL 1 OR OUT value of AI block is outside of OUT_SCALE range Sensor board may have been damaged Check the transmitter for accuracy and linearity Replace the sensor board and recalibrate if needed AI block is executing but status of OUT parameter is One of the following AI alarms is active in ALARM_SUM CUR ...

Страница 214: ...et If the diagnostics is related to input being open check the connections as per the connections diagram If the failure still exists write 4 or restart processor to RESTART parameter of resource block If the failure persists and sensor related replace the sensor board if the If the failure persists and communication board related replace the communication board AI block is executing but status of...

Страница 215: ...n simulation mode is enabled the SIMULATE parameter in the AI and DI blocks provide a user selected value as the input to the AI or DI block Setting the simulation jumper A hardware jumper on the Communication board is set to enable or disable the SIMULATE parameter See Figure 37 for jumper location Table 40 shows how to set the simulation jumper on the Communication board Figure 37 Simulation Jum...

Страница 216: ...ust be set to the following values SIMULATE STATUS Good alarm status constant suggested setting SIMULATE SIMULATE_VALUE supplied by user Used as the input to the AI block SIMULATE ENABLE_DISABLE Active Enabled Simulation mode truth table Table 41 shows the states of the simulation jumper and SIMULATE parameter shows how to activate the simulation mode Table 41 Simulation Mode Truth Table When the ...

Страница 217: ...ets disabled automatically The hardware write lock feature must be enabled before placing the hardware write lock jumper in the On position If the hardware write lock feature is selected with the hardware jumper being enabled the selection is rejected See Figure 37 for jumper location For more information on write protection see Table 42 Table 42 Write Lock To Set the Jumper to Disable the Read an...

Страница 218: ...of security vulnerabilities affecting Honeywell products and services To report potential security vulnerability against any Honeywell product please follow the instructions at https honeywell com pages vulnerabilityreporting aspx Submit the requested information to Honeywell using one of the following methods Send an email to security honeywell com or Contact your local Honeywell Process Solution...

Страница 219: ......

Страница 220: ...ACIFIC Honeywell Process Solutions Phone 800 12026455 or 44 0 1202645583 TAC hfs tac support honeywell com Australia Honeywell Limited Phone 61 7 3846 1255 FAX 61 7 3840 6481 Toll Free 1300 36 39 36 Toll Free Fax 1300 36 04 70 China PRC Shanghai Honeywell China Inc Phone 86 21 5257 4568 Fax 86 21 6237 2826 Singapore Honeywell Pte Ltd Phone 65 6580 3278 Fax 65 6445 3033 South Korea Honeywell Korea ...

Отзывы: