Parameters 37
8
8.2 MOTOR SETTINGS (CONTROL PANEL: MENU PAR -> P1)
NOTE!
These parameters are shown, when
P13.1 = 0
.
Code
Parameter
Min
Max
Unit Default
ID
Note
P1.1
Motor nominal
voltage
180
500
V
230
400
110
Check rating plate on the
motor
P1.2
Motor nominal
frequency
30
320
Hz
50,00
111
Check rating plate on the
motor
P1.3
Motor nominal
speed
300
20000 rpm
1440
112
Default applies for a 4-pole
motor.
P1.4
Motor nominal
current
0,2 x
I
Nunit
2,0 x
I
Nunit
A
I
Nunit
113
Check rating plate on the
motor
P1.5
Motor cos
0,30
1,00
0,85
120
Check rating plate on the
motor
P1.7
Current limit
0,2 x
I
Nunit
2 x
I
Nunit
A
1,5 x
I
Nunit
107
P1.8
0
1
0
600
0
= Frequency control
1
= Speed control
P1.9
0
2
0
108
0
= Linear
1
= Squared
2
= Programmable
P1.10
30,00
320
Hz
50,00
602
P1.11
Voltage at field
weakening point
10,00
200
%
100,00 603
% of Nominal voltage of the
motor
P1.12
0,00
P1.10
Hz
50,00
604
P1.13
0,00
P1.11
%
100,00 605
% of Nominal voltage of the
motor
P1.14
Output voltage at
zero frequency
0,00
40,00
%
0,00
606
% of Nominal voltage of the
motor
P1.15 Torque boost
0
1
0
109
0
= Not used
1
= Used
P1.16
1,5
16,0
kHz
6,0
601
P1.17 Brake chopper
0
2
0
504
0
= Disabled
1
= Used in Run state
2
= Used in Run and
Stop state
P1.18 Motor identification
0
1
0
631
1
= Identification without
run after start command
Table 8.2: Motor settings