Honeywell
Parameters 35
8
8.1 QUICK SETUP PARAMETERS (VIRTUAL MENU, SHOWS WHEN PAR.
3.1 = 1)
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.1
Motor nominal
voltage
180
690
V
230
400
575
110
Check rating plate on the
motor
P1.2
Motor nom. fre-
quency
30
320
Hz
50,00
111
Check rating plate on the
motor
P1.3
Motor nominal
speed
300
20000
rpm
1440
112
Default applies for a 4-pole
motor.
P1.4
Motor nominal
current
0,2 x
I
Nunit
2,0 x
I
Nunit
A
I
Nunit
113
Check rating plate on the
motor
P1.5
Motor cos
0,30
1,00
0,85
120
Check rating plate on the
motor
P1.7
Current limit
0,2 x
I
Nunit
2 x
I
Nunit
A
1,5 x
I
Nunit
107
P1.15 Torque boost
0
1
0
109
0
= Not used
1
= Used
P2.1
1
3
1
125
1
= I/O terminal
2
= Keypad
3
= Fieldbus
P2.2
0
1
0
505
0
=
Ramp
1
=
Flying start
P2.3
0
1
0
506
0
=
Coasting
1
=
Ramp
P3.1
Min frequency
0,00
P3.2
Hz
0,00
101
P3.2
Max frequency
P3.1
320
Hz
50,00
102
P3.3
I/O reference
0
4
3
117
0
= Preset Speeds (0-7)
1
= Keypad Reference
2
= Fieldbus Reference
3
= AI1
4
= AI2
P3.4
0,00
P3.2
Hz
5,00
124 Activated by digital inputs
P3.5
0,00
P3.2
Hz
10,00
105 Activated by digital inputs
P3.6
0,00
P3.2
Hz
15,00
106 Activated by digital inputs
P3.7
0,00
P3.2
Hz
20,00
126 Activated by digital inputs
P4.2
Acceleration time
0,1
3000
s
1,0
103
Acceleration time from 0 Hz
to maximum frequency
P4.3
Deceleration time
0,1
3000
s
1,0
104
Deceleration time from
maximum frequency to 0
Hz
P6.1
AI1 Signal range
0
3
0
379
0
= Voltage 0…10 V
1
= Voltage 2…10 V
Table 8.1: Quick setup parameters