Honeywell SiX Series Скачать руководство пользователя страница 1

 

SiXCO 

Wireless Carbon Monoxide (CO) Detector/ Wireless Carbon Monoxide (CO) Detector 

Installation Instructions 

Instructions d’installation 

This device is intended for use with Honeywell control 
panels that support SiX series devices. Before installing 
detectors, please thoroughly read these installation 
instructions. 

This device is intended for use with Honeywell 
control panels that support SiX series devices. 
Before installing detectors, please thoroughly read 
these installation instructions. 

Features 

Features 

  10-year life 

  CO Detector End-of-Life reporting (detector needs 

replacing) 

  Carbon Monoxide detector maintenance reporting  

  Low Battery Detection 

 

Multi-color status LED 

  10-year life 

  CO Detector End-of-Life reporting 

  Carbon Monoxide detector maintenance reporting  

  Low Battery Detection 

 

Multi-color status LED 

POWER UP 

 

  Remove battery pull tab. Be sure 

batteries are seated properly to 

avoid a low battery condition 

after 15 seconds. 

 

  Upon power up, Green LED 

Blinks every 2 secs / Sounder is 

Silent.  

 

POWER UP 

 

  Remove battery pull tab. Be 

sure batteries are seated 

properly to avoid a low 

battery condition after 15 

seconds. 

 

  Upon power up, Green LED 

Blinks every 2 secs / 

Sounder is Silent.

 

ENROLLMENT  

ENRÔLEMENT 

This device can be enrolled and programmed either 

before or after installation. 

1.

 

Set the Lyric Controller in Programming Mode and go to 

Zone Programming.  Select Add New and then Serial 

Number.  

2.

 

Remove the battery tabs to activate the device and begin 

the enrollment process. 

3.

 

The Green LED flashes rapidly during enrollment (up to 

about 20 seconds

). 

*NOTE: Enrollment time varies depending on the signal 

strength between the device and the controller. 

 

  The detector sends its unique MAC ID (Serial Number) 

and Services information to the controller.   

 

  The controller registers the device and displays the 

transmitter data on screen. 

4.

 

Enrollment is confirmed when the Green LED is ON for 3 

seconds and the detector chirps. 

5.

 

Press SAVE. 

 
 
 

Le dispositif peut être enrôlé et programmé avant 

ou après l'installation.

 

1.

 

Réglez le 

contrôleur Lyric

 en mode de 

programmation et accédez à la programmation 

des zones. Sélectionnez Add New (ajouter 

nouveau) et ensuite Serial Number (numéro de 

série).  

2.

 

Retirez la languette qui recouvre la pile pour 

activer le dispositif et commencer la procédure 

d'enrôlement. 

3.

 

La DEL verte clignote durant l'enrôlement 

(pendant jusqu'à environ 20 secondes*). 

NOTE

:   La durée de l'enrôlement varie selon la 

 

puissance du signal entre le dispositif et 

 

le contrôleur. 

 

Le dispositif transmet au contrôleur son ID 

MAC (numéro de série) et l'information pour les 

services.   

 

Le contrôleur enregistre le dispositif et affiche 

les données du transmetteur sur l'écran. 

 
 

Содержание SiX Series

Страница 1: ...led and programmed either before or after installation 1 Set the Lyric Controller in Programming Mode and go to Zone Programming Select Add New and then Serial Number 2 Remove the battery tabs to activate the device and begin the enrollment process 3 The Green LED flashes rapidly during enrollment up to about 20 seconds NOTE Enrollment time varies depending on the signal strength between the devic...

Страница 2: ...fault If the device is enrolled in a panel different than the intended panel and you are unable to delete it from the unintended panel reset default the device to factory default setting If the device is enrolled in a panel different than the intended panel and you are unable to delete it from the unintended panel reset default the device to factory default setting This procedure is available for ...

Страница 3: ... of detectors only after completing construction or any other dust producing activity After enrolling and before mounting permanently conduct Go No Go test see controller s instructions to verify adequate signal strength Adjust the device location as necessary 1 Remove the CO with a counter clockwise motion 2 Using two supplied screws and anchors mount the base 3 Attach the CO detector to the moun...

Страница 4: ...y rotating counter clockwise 2 Press and hold the CO test button for 3 to 5 seconds The green LED will start blinking once per second indicating the detector is in RealTest mode If the detector will not go into RealTest mode the CO sensor may be in fault or at end of life 3 While the green LED is blinking once per second spray a small amount of canned CO directly into the CO gas entry port 4 Upon ...

Страница 5: ...Trouble End of Life CID 380 Tamper Tamper Disarmed CO Trouble Armed CO Alarm RF Sensor Tamper CID 383 RF Sensor Tamper TESTING SIGNAL STRENGTH Perform this test in accordance with NFPA 72 inspection testing and maintenance requirements to determine a strong communication path with the control panel 1 Activate the wireless system s GO NO GO TEST mode 2 Press the detector s TEST button for 1 2 secon...

Страница 6: ... or explosion Keep used batteries away from children Dispose of used batteries properly BATTERY REPLACEMENT BATTERY REPLACEMENT CLEANING NOTE Notify the proper authorities when the system will be temporarily out of service IMPORTANT This detector must be tested and maintained regularly following NFPA 72 requirements The detector should be cleaned at least once a year 1 Remove the detector from the...

Страница 7: ... be used with detector guards unless the combination is evaluated and found suitable for that purpose MAINTENANCE Do not paint and do not use cleaning agents bleach or polish the detector NOTE Before performing any maintenance on the detector notify the proper authorities and Central Station that maintenance is being performed and the system will be temporarily out of service Disable the zone or s...

Страница 8: ...fe after 30 days CO End of Life after 30 days Double Blink Amber every 3 secs Double Blink Amber every 3 secs Chirp every 45 secs Chirp every 45 secs Normal Standby Normal Standby Single Blink Green every 10 secs Single Blink Green every 10 secs Silent Silent Many cases of reported carbon monoxide poisoning indicate that while victims are aware that they do not feel well they become so disoriented...

Страница 9: ...lose sensitivity and will need to be replaced The life span of the CO sensor is approximately ten years from the date of manufacture Periodically check the detector s replacement date Remove the detector head and refer to the replace by sticker placed on the underneath side of the detector The sticker will indicate the date the detector should be replaced Reminder This detector is also equipped wi...

Страница 10: ...URACELL DL123 DL123A lithium Battery Manufacturer Pile Manufacturer Panasonic DURACELL Number of Batteries Number of Batteries 2 Sensitivity Sensitivity Meets UL2034 UL2075 CO sensitivity requirements Audible Signal Audible Signal 85dBA Physical Specifications Diameter Diameter 5 3 inches 13 46cm Diameter 1 65 inches 4 19cm Thick Weight Weight 7 7oz 21g Operating Temperature Température de Fonctio...

Страница 11: ...nges or modifications to the equipment unless authorized by the Installation Instructions or User s Manual Unauthorized changes or modifications could void the user s authority to operate the equipment FCC IC STATEMENT This device complies with Part 15 of the FCC Rules and Industry Canada s license exempt RSSs Operation is subject to the following two conditions 1 This device may not cause harmful...

Страница 12: ...hsc resources wa For patent information see www honeywell com patents Pour des informations sur les brevets voir www honeywell com patents MyWebTech Warranty Patents Ê800 23974lŠ 800 23974 1 18 Rev A 2017 Honeywell International Inc Honeywell and is a registered trademark of Honeywell International Inc All other trademarks are the properties of their respective owners All rights reserved Honeywell...

Отзывы: