6. Series 8 I/O
Configuration
6.6. Defining Channel blocks
174
Series 8 I/O User's Guide
R500
Honeywell
April 2017
Table 43 Digital Output fault handling
Source
Destination
Mode
MODEATTR
FAULTSTATE
transitions
PID.OP
DO.OP
Cas
N/A
1, 2, 3, 5, 7
1
PIDER.OP
DO.OP
Cas
N/A
1, 2, 3, 5, 7
1
PID-PL.OP
DO.OP
Cas
N/A
1, 2, 3, 5, 7
1
PIDFF.OP
DO.OP
Cas
N/A
1, 2, 3, 5, 7
1
PosProp.
RAISETIME
DO.OFFPULSE
Cas
N/A
1, 2, 3, 5, 7
2
PosProp.
LOWERTIME
DO.OFFPULSE
Cas
N/A
1, 2, 3, 5, 7
2
PosProp.
RAISETIME
DO.ONPULSE
Cas
N/A
1, 2, 3, 5, 7
2
Posprop.
LOWERTIME
DO.ONPULSE
Cas
N/A
1, 2, 3, 5, 7
2
DevCtl.PO
DO.OFFPULSE
Cas
N/A
1, 2, 3, 5, 7
DevCtl.PO
DO.ONPULSE
Cas
N/A
1, 2, 3, 5, 7
DevCtl.DO
DO.SO
Cas
N/A
1, 2, 3, 5, 7
Logic
DO.SO
Cas
N/A
1, 2, 3, 5, 7
SCM
DO.OP
Man
Program
1, 2, 3, 5, 7
SCM
DO.SO
Man
Program
1, 2, 3, 5, 7
User
DO.OP
Man
Operator
1, 4, 6
User
DO.SO
Man
Operator
1, 4, 6
The FAULTOPT parameter determines the behavior of an individual output value when
a fault condition exists. The following modes apply to the FAULTOPT parameter: