SEC-H-600 SECURITY CONTROLLER
29
95-7759—07
4.
Digital input DI1 of the SEC-H-600 must be wired to the door tamper switch of its enclosure. See Fig. 12 on page 22. If
additional WEBs-AX Security Enclosures are used in the system, each door tamper switch must also be wired to DI1 of
one
of the contained expansion modules.
5.
Only UL listed, 12V Wiegand-type readers can be used with the system.
6.
Exit request input circuits and initiating devices must be contained within the secured area. Exit device circuits must be con-
nected to UL listed switches or exit devices.
7.
Door strike power must be provided from a UL listed burglar alarm system power supply. When required in accordance with
NFPA 101, if the door strike circuit is arranged as fail secure (door remains locked upon loss of power), UL listed emer-
gency panic hardware must be provided to allow exit from the secured area. A fail-safe configuration results in the door
strike circuit unlocking in case of a power loss.
8.
Audible signal appliance circuits, such as shown in Fig. 11 on page 21, are for supplementary use only.
Compatible Readers
Compatible Readers when used with the NPB-PWR-UN-H power supply are
• HID — Models 5355,
5365
, 5375,
5395
,
5455
,
6005
,
6100
,
6120
, 6125, 6130
• GE Security — Model
T-200
Only readers shown
bolded
above are also approved for use with the UL listed Battery-backed Power Supplies listed in the next
section.
This includes HID models 5365, 5395, 5455, 6005, 6100, 6120, and GE Security model T-200 (Reader Input rated 8.1–14 Vdc).
Battery-backed Power Supplies
The following third-party, battery-backed power supplies are UL approved for powering remote SEC-H-R2R and SEC-H-RIO
expansion modules:
NOTE: Configure power supply for 12Vdc output operation.
Also see previous “Compatible Readers” section.
The Security Controller must be powered by the integral 15Vdc power supply (NPB-PWR-UN-H) in a WEBs-AX Security
Enclosure, model SEC-ENC-H-1 or SEC-ENC-H-2.
For wiring details related to using third-party, battery-backed power supplies, refer to the installation document for either of the
expansion modules. See “Related Documentation,” page 5.
Honeywell
http://www.honeywellpower.com/access.html
AlarmSaf
http://alarmsaf.com/
Model
Output
Model
Output
HP300ULX
12/24Vdc 2.5A
CPS-200C-7-UL/CSA
12/24Vdc 2.5A
HP400ULX
12/24Vdc 4.0A
CPS-400C-UL/CSA
12/24Vdc 4.0A
HP600ULX
12/24Vdc 6.0A
CPS-600C-UL/CSA
12/24Vdc 6.0A
HP300ULPD4CB
12/24Vdc 2.5A with Distribution PCB
CPS-800C-UL/CSA
12/24Vdc 8.0A
HP400ULPD4CB
12/24Vdc 4.0A with Distribution PCB
HP600ULPD16CB 12/24Vdc 6.0A with Distribution PCB