SEC-H-600 SECURITY CONTROLLER
95-7759—07
18
Supervised Input
The SEC-H-600 controller has six (6) supervised inputs, located on three 3-position connectors next to the DB-9 connector (see
Figure 9 below). Under each connector, terminals are labeled SI
n
, GND, SI
n
, for example: SI3, GND, SI4. This means when
wiring,
two
conductors are typically landed to each GND terminal.
NOTE: Supervised inputs SI1 through SI4 are reserved for Door 1 and 2 usage. Supervised inputs SI5 and SI6 are available for
general usage. For more details, see “Door Terminal Associations,” page 15.
Each supervised input can monitor dry contacts, either normally-open (N.O.) or normally-closed (N.C.). One End-of-Line Resistor
Pack is required at the monitored contacts for each input, for proper operation. Figure 9 shows wiring of supervised inputs S1 and
SI2, which are reserved for Door 1 usage.
Fig. 9. Supervised input wiring to Security Controller.
End-of-Line Resistor Pack
You must install an end-of-line (EOL) resistor pack at the monitored device for proper operation of each input. Six (6) EOL resistor
packs are shipped with each SEC-H-600 controller. Each resistor pack has four leads:
• New style (shipping soon): One red, one white, two black leads. Wire as shown in Figure 9 above.
• Old style: Two white, two black leads. Wire black leads across contacts, and wire the white lead shown internally connected to
the black lead (common) to the “GND” input, and the other white lead to the “SIn” input. See the detail in lower right of
Figure 9.
Install each EOL resistor pack as close as possible to the actual monitored switch/contacts.
GN
D
SI
6
SI
1
SI
2
SI
3
SI
5
SI
4
GN
D
GN
D
1K
1K
Black
Black
(Old white)
White
Shield
Shield
Request
to Exit
Resistor Pack
(New Style)
Door
Monitor
Switch
Normally
Open
or
Normally
Closed
Normally
Open
or
Normally
Closed
Three 3-position
connectors for Supervised
Inputs
Tape back
shield at
device
Tape back
shield at
device
NOTE:
Supplied EOL resistor packs use
two internal 1K ohm resistors. Wire
new
style
EOL packs (leads red, white, 2 black)
as shown above.
Black
Black
White
to “GND”
1K
1K
Black
Red
White
Black
Black
Red
White
Black
Resistor Pack
(New Style)
White
New Style
EOL Pack
(Internal)
shipping
soon
Old Style
EOL Pack
(Internal)
White
to
“SI
n
”
NOTE:
If using
old style
EOL packs (2
white leads, 2 black leads), connect white
that is common with black to “GND” on
controller, and the other white to “SI
n.
”
com
mo
n
Red
(Old black)
Door 1