TFI 812

Gas Burner Control Box

INTRODUCTION

The TFI 812.2 gas burner control boxes are capable of
controlling and monitoring atmospheric gas burners. They
have been tested and approved as per DIN 4788 part 3
edition 04.89 and with the European standard EN 298. They
are also suitable for use with stationary warm air generators
(as per DIN 4794).
The control boxes are designed for maximum safety in case
of fluctuations in the voltage supply. If the mains voltage
drops below the permitted level, operation is interrupted
and the control box automatically prevents the start sequence
from being repeated. In this way, the safety of the system is
not put at risk by a drop in the mains voltage.
The control box and the monitoring function which it performs
is not negatively affected by occasional stray ignition sparks
jumping to the ionisation electrode.
The FR 870 remote reset (item no. 70700) can be connec-
ted, and allows remote reset of the control box (see doc.
no. 750).
The TFI 812 mod.5 can be installed in place of the TFI
712 F, and the TFI 812 mod.10 can be employed to replace
the TFI 712.
It is not necessary to rewire or replace the baseplate. The
difference in the heights of the units can be compensated by
attaching the reset button extension (item no. 70601).
The difference between the TFI 812.1 and the TFI 812.2 is
that the TFI 812.2 control boxes are equipped with the
voltage drop fail-safe function. Otherwise, they are identical
in terms of operation and possible applications.

CONSTRUCTIONAL FEATURES

The control box is well protected by a flame-resistant,
transparent, plug-in type plastic housing which encloses
the thermo-mechanical temperature-compensated timing
unit, the flame monitoring unit and the reset device.
The reset button, which incorporates an indicator lamp, and
the central screw fastening, are situated on the upper part
of the control box.
The baseplate, which can be equipped with additional
terminals, together with the various optional cable entry
points, makes universal wiring possible.

For 2-stage atmospheric gas burners

Possible flame detectors:
- Ionisation probe
- Infra-red flicker detector

TYPES AVAILABLE

TFI 812.2 mod. 5

Safety interval nominal 5 sec.
Pre-ignition time approx. 15 sec.
appropriate nominal capacity
according to the appliance standort
or the gas appliance directive.

TFI 812.2 mod. 10

Safety interval nominal10 sec.
Pre-ignition time approx. 10 sec.
appropriate nominal capacity
according to the appliance standort
or the gas appliance directive.

TFI 812.2 B mod. 5

dito – without Pre-ignition time

TFI 812.2 B mod. 10 dito – without Pre-ignition time

TECHNICAL DATA

Supply voltage

220 / 240 V (-15... +10%)
50 Hz (40 - 60 Hz)

Fuse rating

10 A rapid or 6 A slow

Power consumption

5 VA

Max. current per
output terminal

4 A

Max. current total

6 A

Pre-ignition time

15 or 10 sec.

Delay, post-ignition time

none

Safety interval nominal

5 or 10 sec.

Safety interval max.

10 or 20 sec.

2nd stage delay

approx. 20 sec.

Reset delay after lockout

approx. 60 sec.

Permissible ambient temperature -20

°

 C to +60

°

 C

Sensitivity

1.5 

µ

A

Min. ionisation current required

2 - 3 

µ

A

Ionisation probe insulation

probe - earth
greater than 50 M

Stray capacitance

probe - earth
less than 1000 pF
(max. 20 m cable)

Insulation standard

IP 44

Weight incl. baseplate

250 g

Mounting attitude

any

EN1C-0143SZ20 R0305

Distribuitor: 

FLAME POWER SRL 

021-3121727 ; 0744-340566 

[email protected] ; www.arzatoare.ro

Содержание Satronic TFI 812 Series

Страница 1: ...type plastic housing which encloses the thermo mechanical temperature compensated timing unit the flame monitoring unit and the reset device The reset button which incorporates an indicator lamp and the central screw fastening are situated on the upper part of the control box The baseplate which can be equipped with additional terminals together with the various optional cable entry points makes u...

Страница 2: ...The applicable installation regulations must be observed during installation COMMISSIONING AND MAINTENANCE 1 Important notes The wiring must be checked exactly when commissioning the installation Incorrect wiring could damage the con trol box putting the safety of the burner system at risk The chosen fuse rating must not on any account be higher than the value given in the technical data Failure t...

Страница 3: ...ST Safety thermostat RT Controlling thermostat IS Ionisation probe Z Ignition V1 Solenoid valve 1st stage V2 Solenoid valve 2nd stage SA remote lockout indicator M Auxiliary blower tw Pre ignition time approx 15 sec mod 5 approx 10 sec mod 10 ts Safety time nominal 5 sec mod 5 10 sec mod 10 tv2 2nd stage delay approx 20 sec blue black brown Kl 8 Kl 1 Kl 9 IRD 1020 1 TFI 812 RF R26 1 Ion 9 RT ST HS...

Страница 4: ... no longer available Control box TFI 812 2 B mod 10 no longer available Socket Wiring base S98 9 pin 75300 Socket Wiring base S98 12 pin 75310 Insert plate PG plate 70502 optionally Cable entry plate 70503 Flame detector IRD 1020 1 end on viewing 16532 Flame detector IRD 1020 1 side on left 16533 Flame detector IRD 1020 1 side on right 16531 IRD mounting flange IRD Holder M93 59093 Flame detector ...

Отзывы: