IRD 1020

Flame detection device for
oil and gas flames

INTRODUCTION

The IRD 1020 detector is used to supervise gas or oil flames.
This flame monitoring device should be connected to a
Satronic oil burner control box. Monitoring is based on the
infra-red flicker principle, in other words, the flickering infra-
red light of the flame is detected. The steady radiation from,
for example, the glowing refractory layer on the inside of the
boiler, has no effect on the detector. The IRD 1020 replaces
the IRD 920. When exchanging the units, care must be taken
to wire them correctly.

TYPES AVAILABLE (also see page 4)

Item no.

Designation

16521

Flicker detector IRD 1020 side-on-right

16522

Flicker detector IRD 1020 end-on viewing

16523

Flicker detector IRD 1020 side-on left

The infra-red flicker detector can be used with any one of the
following control boxes:

IRD 1020

DKG 972
DLG 974, 976
DMG 970, 971, 972, 973
TFI 812.2
MMI 810, 811, 812, 815, 816, 962
MMG 810, 811, 816,
TMG 740-2, 740-3
SGU 930, 930i

CONSTRUCTIONAL FEATURES

The infra-red sensor and the pre-amplifier are hermetically
sealed in glass and along with the electronics form an
integrated unit in the flame detector. Wiring is by way of a
plug connection. The sensitivity control and two LED’s for
indication of the flame signal are situated on the rear of the
flicker detector.

Infra-red flicker detector

TECHNICAL DATA

Supply voltage

220 / 240 V (-15... +10%)
50 Hz (50 - 60 Hz)

Nominal current input

approx. 4 mA

Power consumption

1 VA

Ambient temperature

-20

°

 C to +60

°

 C

Insulation standard

IP 41

Mounting attitude

any

Weight

40 g

Flame viewing attitude

side-on or end-on according
to type

Spectral response

800 - 1100 nm

(with daylight filter)

maximum 950 nm

Frequency range

15 Hz.... 250 Hz (-12 dB)

Sensitivity adjustment
range

approx. 1 : 20 (26 dB)

Switch-on delay
(after connecting
operating voltage)

< 3.5 sec.

Response time

< 0.1 sec.

Cut-out time

< 1 sec.

Содержание Satronic IRD 1020

Страница 1: ...orcanbeusedwithanyoneofthe following control boxes IRD 1020 DKG 972 DLG 974 976 DMG 970 971 972 973 TFI 812 2 MMI 810 811 812 815 816 962 MMG 810 811 816 TMG 740 2 740 3 SGU 930 930i CONSTRUCTIONAL FEATURES The infra red sensor and the pre amplifier are hermetically sealed in glass and along with the electronics form an integrated unit in the flame detector Wiring is by way of a plug connection Th...

Страница 2: ...peration as follows Check that the detector is connected properly Wrong connectionsarearisktosafety andcouldcausedamage to the detector unit or burner system Adjust to maximum sensitivity and start the burner If the LED indicator is lit after the start impulse carefully adjust the sensitivity control until LED 1 extinguishes No LED should light up during the pre purge phase With the system set for...

Страница 3: ...2 NoindicationfromLED safterestablishmentofflame a Incorrect or faulty wiring b Sensitivity set too low c Detector positioned wrongly receives no light d Detector or viewing window dirty e Defective detector f IRDflangeM93defective cracksorothermechanical defects The standard sensitive version of the IRD 1020 has a blueinprint Whiteorredinprintsaremarkingdetectors with special attributes They may ...

Страница 4: ...e Flange M93 59093 Sensor cable Plug type 3 wire 0 6 m with tag wire ends 7236001 The above ordering information refers to the standard version Special versions are also included in our product range Specifications subject to change without notice FLICKER DETECTOR IRD 1020 VARIANTS Satronic IRD 1020 Satronic IRD 1020 Satronic IRD 1020 Light entrance from right Item no 16521 35 3 26 4 5 15 1 48 ø20...