S9240F1004 MODULATING HOT SURFACE IGNITION INTEGRATED FURNACE CONTROL
27
69-2088—01
Compressor Heating/Cooling Display – System Status
LED Error Codes
There are four types of LED error codes:
• Warning Only: IFC continues normal operation.
• Wait for Recovery: IFC resumes normal operation after
fault recovers.
• Soft Lockout: A state caused by failure internal to the
control or by a system fault such as loss of flame or
pressure switch failure. Heating related functionality is
inhibited during Soft Lockout. Assuming the fault that sent
the IFC to Soft Lockout has cleared, Soft Lockout exits
after the Auto Restart Delay when a call for heat is active.
The operator can cycle power to remove the Soft Lockout
without waiting for the Auto restart Delay.
• Hard Lockout: A state caused by a failure internal to the
control or by a system fault such as a flame rollout. Heating
related functionality is inhibited during Hard Lockout. Hard
Lockout can be exited only by cycling power to the IFC.
Table 11. Compressor Heating/Cooling LED Display.
Description
Display Example
a
(LED display in bold)
a
The current display mode is immediately interrupted if the operating mode changes
Heating Stage:
Shows what stage of furnace heating is currently operating. Shown only while heating is
active and unit is set up to work as staged equipment (not modulating).
The display example in this table shows the LED display when the 1st stage heat is active.
H 1
Pause
Display CFM
Repeat
Dehumidification Mode:
Shows that the unit is providing dehumidification instead of straight cooling.
D
Pause
Display CFM
Repeat
Cooling Stage:
Shows what stage of cooling is currently operating.
The display example in this table shows the LED display when the 2nd stage cooling is
active.
C 2
Pause
Display CFM
Repeat
Defrost Mode:
Shown only while in an active defrost
(simultaneous Y, W, and O).
D F
Pause
Display CFM
Repeat
Table 12. LED Status Codes.
Error/Fault Condition
Code
Error Handling
(in addition to displaying error code)
Result
Outside air sensor out of range
(open or no discharge air sensor is OK)
180 None
Warning
Only
Low flame in run mode
240 None
Discharge air sensor (DAS) out of range
(open or no discharge air sensor is OK)
310 None
Firing rate reduced to match CFM
311 Reduce firing rate every 60 seconds to match available CFM.
Restricted airflow cooling or continuous fan
312 None
Line voltage low
110 Resume normal operation after fault recovers.
Wait for
Recovery
Line voltage high
113 Resume normal operation after fault recovers.
Zero crossing not detected or frequency out of
range
115 Resume normal operation after fault recovers.
Low 24 volts
115 Resume normal operation after fault recovers.
Flame circuit check error
125
a
Resume normal operation 300 seconds after fault recovers.
Hardware failure
125
a
Resume normal operation 300 seconds after fault recovers.
Micro inter-communication failure
125
a
Resume normal operation 300 seconds after fault recovers.
Circulator communication failed
201 Resume normal operation after fault recovers.
Gas valve miswire
204 Resume normal operation after fault recovers.
Low pressure switch failed (stuck) Open
223 If longer than 300 seconds, start pressure switch calibration.