R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 AMPLIFIERS FOR 7800 SERIES AND R7140 RELAY MODULES

65-0109—14

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 

TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or 

phone:

1.

Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).

2.

Honeywell Customer Care

1985 Douglas Drive North

Minneapolis, Minnesota 55422-4386

3.

http://customer.honeywell.com or http://customer.honeywell.ca

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

The R7886A Dynamic Self-Check Ultraviolet Amplifier is a 

solid state plug-in amplifier that responds to a pulsed direct 

current signal from a C7076A,C Ultraviolet Flame Detector 

with adjustable sensitivity to indicate the presence of flame 

when used with 7800 SERIES and R7140 Relay Modules.

FEATURES

• Flame failure response time of 0.8 or 1 second; or 2.0 

or 3.0 seconds, depending on the amplifier and relay 

module selected. See Table 1.

• Plug-in to 7800 SERIES and R7140 Relay Module 

through printed circuit board edge connector keyed 

for proper orientation.

• Flame signal test jacks measure amplifier flame signal 

voltage.

• 0.0 to 5.0 Vdc Flame signal strength reading range.
• Color coded label identifies flame detection type:

— Green—rectification.

Red—infrared.

— Purple—ultraviolet.

Blue—pulsed rectification.

— White—optical.

• R7847B, R7848B, R7849B Dynamic Ampli-Check® 

circuitry tests all flame amplifier components 12 times 

per minute. The 7800 SERIES and R7140 Relay Module 

locks out on safety shutdown with amplifier failure.

• R7824C, R7847C Dynamic Self-Check Rectification 

Amplifier, R7851C Dynamic Self-Check Optical Flame 

Amplifier, R7861 Self-Check Ultraviolet Flame 

Amplifier and R7886A Dynamic Self-Check Ultraviolet 

Amplifier test the detectors and all electronic 

components in the flame detection system 12 times 

per minute. The 7800 SERIES and R7140 Relay Module 

locks out on safety shutdown with flame detection 

system failure. 

NOTE: R7824C, Series 2 or greater and R7847C Series 4 

or greater, pulse the shutter when signal of 1.5 Vac 

is sensed. Display readings of 0.7 to 2.4 Vdc are 

common.

SPECIFICATIONS

Models:

Flame Detection Systems (see Table 2):

Rectification:

R7824C for use with C7024E,F Solid State Ultraviolet 

Detectors.

R7847A,B for use with flame rods or C7012A,C Solid State 

Ultraviolet Detectors.

R7847C for use with C7012E, F Solid State Ultraviolet 

Detectors.

Содержание R7824

Страница 1: ...40 Relay Modules The R7849A B Ultraviolet Flame Amplifiers are solid state plug in amplifiers that respond to an ultraviolet signal from a C7027 C7035 or C7044 Ultraviolet Flame Detector to indicate the presence of flame when used with 7800 SERIES and R7140 Relay Modules The R7851B Optical Flame Amplifiers are solid state plug in amplifiers that respond to optical signals from C7927 and C7962 Flam...

Страница 2: ...n the amplifier and relay module selected See Table 1 Plug in to 7800 SERIES and R7140 Relay Module through printed circuit board edge connector keyed for proper orientation Flame signal test jacks measure amplifier flame signal voltage 0 0 to 5 0 Vdc Flame signal strength reading range Color coded label identifies flame detection type Green rectification Red infrared Purple ultraviolet Blue pulse...

Страница 3: ...able The Amplifiers R7847B C R7861A R7886 R7851C or R7852B used with the appropriate flame detector and used in Relay Module EC7810A 20A 30A 40L 50A RM7800 E G L M 30A 38 A B C 40 E G L M 50A 90 A B C D 97 A C 98A is SIL 3 Capable in a properly designed Safety Instrumented System See form number 65 0312 for Certificate Agreement Approvals Underwriters Laboratories Inc Listed File no MP268 Guide no...

Страница 4: ... and R7847C Series 4 or greater pulse the shutter when signal of 1 5 Vdc is sensed Display readings of 0 7 to 2 4 Vdc are common i Order flame rod separately see flame detector Instructions for holder Plug in Flame Signal Amplifiers Applicable Flame Detectors Type Color Self Checking Model Flame Failure Response Time sec a Fuel Type Models Rectification Green Dymanic Self Check R7824Cb c h 3 Gas o...

Страница 5: ...Shock Hazard Can cause severe injury death or property damage Disconnect the power supply before beginning installation More than one power supply disconnection can be involved 1 Align the amplifier circuit board edge connector with the keyed receptacle on the 7800 SERIES and R7140 Relay Module Be sure the amplifier nameplate faces away from the Relay Module 2 Push in the amplifier until the circu...

Страница 6: ...AGE FLAME DETECTOR LEADS ARE COLOR CODED THE BLUE LEAD MUST BE CONNECTED TO THE F TERMINAL AND THE WHITE MUST BE CONNECTED TO THE G TERMINAL THE UV SENSING TUBE IS POLARITY SENSITIVE FLAME DETECTOR LEADS ARE COLOR CODED THE BLUE LEAD MUST BE CONNECTED TO THE F TERMINAL AND THE YELLOW MUST BE CONNECTED TO THE G TERMINAL THE UV SENSING TUBE IS POLARITY SENSITIVE CAUTION EQUIPMENT DAMAGE HAZARD INCOR...

Страница 7: ... amplifier and flame detector is used Flame Signal Measurement Fig 4 Flame signal can be measured at the Flame Signal Test Jacks see Fig 4 and at the Keyboard Display Module Measure the flame signal at the appropriate times defined in the Checkout section see applicable 7800 SERIES and R7140 Relay Module Instructions See Table 3 for acceptable and maximum flame signal voltage strengths CAUTION Equ...

Страница 8: ...t and the power supply is of the correct voltage and frequency and is sinusoidal 2 Check the detector wiring for defects including a Incorrect connections b Wrong type of wire c Deteriorated wire d Open circuits e Short circuits f Leakage paths caused by moisture soot or accu mulated dirt 3 For a flame rod make sure a There is enough ground area b The flame rod is properly located in the flame c T...