INSTALLATION INSTRUCTIONS

69-1459—4

R7184A,B,P,U Series 5

Interrupted Electronic Oil Primary,

EnviraCOM™ Enabled

APPLICATION

The R7184A,B,P,U Interrupted Electronic Oil Primary is a 
line voltage, safety rated, interrupted ignition oil primary 
control for residential oil fired burners used in boilers, 
forced air furnaces and water heaters. The 
R7184A,B,P,U used with a cad cell flame sensor, 
operates an oil burner and optional oil valve. The primary 
controls fuel oil, senses flame, controls ignition spark and 
notifies a remote alarm circuit when in lockout.

The R7184 can be used with both hydronic and forced air 
systems. When used with hydronic systems, line voltage 
switching Aquastat® Controllers normally provide for the 
starting and stopping of the combustion sequences. With 
forced air systems, both mechanical and electronic low 
voltage thermostats control the starting and stopping of 
the combustion process.

Some hydronic and forced air systems now require a 
delayed valve-on and burner motor-off delay. The R7184 
operates an oil valve that prevents the flow of oil when 
the burner motor is running prior to combustion (delayed 
valve-on) and when the burner motor is running after 
combustion (burner motor-off delay).

The R7184 models are intended for use only on oil 
burning appliances which do not require prepurge and 
post-purge as a safety related function as defined in 
UL296. The valve-on delay and burner motor-off delay in 
this control are intended only to help establish draft and 
reduce oil after-drip related problems.

The R7184 is EnviraCOM™ enabled, making it 
compatible with EnviraCOM™ home networks.

FEATURES

Thermostat(s)

The oil primaries are compatible with both standard 
thermostats and EnviraCOM™ communicating 
thermostats.

Limited Recycle

This feature limits the number of recycle trials (for each 
call for heat) to a maximum of three trials. If the flame is 
lost three times and does not successfully satisfy a call 
for heat, the R7184 locks out.

Pump Priming Cycle

To facilitate purging air from the oil lines and filters, the 
R7184 can be placed in a purge routine by pressing and 
releasing the reset button during the safety check, 
delayed valve-on, ignition or carry-over periods. The 
lockout timing will be extended to four minutes and the 
ignition set in the intermittent mode for this cycle only. 
The R7184 automatically reverts to its labeled interrupted 
and safety switch timing states. The pump priming cycle 
can only be entered if there have been no lockout 
occurrences since the last successful heat call. To reset 
the device so that the pump priming cycle can be 
entered, press and hold the reset button until the light 
emitting diode (LED) flashes (approximately 30 
seconds).

Data Port

Controls are designed to allow networking and upgrade 
modules to be added in the field by simply plugging them 
into the data port/network. (See Fig. 2.)

Disable Function

Pressing and holding the reset button will disable all 
functions until the button is released. The R7184 will 
restart at the beginning of the normal heat cycle on safety 
check.

Limited Reset (Restricted Mode)

In order to limit the accumulation of unburned oil in the 
combustion area, the control can only be reset three 
times. The reset count returns to zero each time a call for 
heat is successfully completed. 

To reset from restricted mode: Press and hold the reset 
button for 30 seconds. When the LED flashes twice, the 
device has reset.

69-1459-4.fm  Page 1  Wednesday, August 10, 2005  1:07 PM

Содержание R7184A

Страница 1: ...with EnviraCOM home networks FEATURES Thermostat s The oil primaries are compatible with both standard thermostats and EnviraCOM communicating thermostats Limited Recycle This feature limits the number of recycle trials for each call for heat to a maximum of three trials If the flame is lost three times and does not successfully satisfy a call for heat the R7184 locks out Pump Priming Cycle To fac...

Страница 2: ...r off Delay 0 2 4 or 6 minutes Field selectable using dual inline programmable DIP switch positions 1 and 2 Select models have 0 5 2 4 or eight minute delays See Fig 2 NOTE For universal R7184U model valve on delay and burner motor off delay timings can be enabled values as listed or disabled values are zero in the field using DIP switch position 3 Lockout 15 30 or 45 seconds factory programmed Re...

Страница 3: ...ounting the control make line voltage connections as shown in Fig 2 through 8 Splice lines with solderless connectors Do not exceed load ratings shown on the device label 3 If necessary use the control as a template to mark and drill new mounting holes 4 Mount the device using No 6 screws obtained locally WIRING WARNING Electrical Shock Hazard Can cause severe injury death or property damage Disco...

Страница 4: ...oil supply line 3 Device enters recycle mode 4 Device tries to restart system after approximately 60 seconds 5 Safety switch locks out approximately in safety switch timing indicated on label Indicator light flashes 1 2 second on 1 2 second off Ignition and motor stop and oil valve closes Simulate Ignition Failure 1 Follow starting procedure to turn on burner but do not open oil supply hand valve ...

Страница 5: ...LIMIT JUNCTION BOX ALARM T T 3 2 1 T T LEGEND TO REMOTE ALARM CIRCUIT SCREW TERMINAL 1 4 IN QUICK CONNECT TERMINAL SOLDERLESSWIRE CONNECTOR THERMOSTAT L8148A C JUMPER AQUASTAT CONTROLLER R W ENVIRACOM TERMINAL L2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED OPTIONAL FEATURE ON SELECT MODELS REFER TO DEVICE LABEL FOR WIRE COLOR CODE VALVE IS OPTIONAL ON SPECIFIC MODELS ...

Страница 6: ...ontrol provides lockout recycle and cad cell indications as follows POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED OPTIONAL FEATURE ON SELECT MODELS REFER TO DEVICE LABEL FOR WIRE COLOR CODE VALVE IS OPTIONAL ON SPECIFIC MODELS FACTORY INSTALLER JUMPERS ENVIRACOM TERMINAL 3 IS ALSO THE FIRST THERMOSTAT TERMINAL 1 M19978A 2 3 4 5 6 LEGEND SCREW TERMINAL 1 4 IN QUICK CONNE...

Страница 7: ... stripped WARNING Electrical Shock Hazard Can cause severe injury death or property damage Troubleshoot with the system powered Be careful to observe all precautions to prevent electrical shock or equipment damage Refer to Table 4 for further troubleshooting information Fig 9 Typical wiring diagram for24 Vac thermostat and R7184 for valve on delay burner motor off oil burner system Table 2 Switch ...

Страница 8: ...ALVE CAD CELL LIMIT L1 JUNCTION BOX ALARM T T TO REMOTE ALARM CIRCUIT L1 HOT 1 JUMPER LINE VOLTAGE THERMOSTAT OR AQUASTAT CONTROL LIMIT POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED OPTIONAL FEATURE ON SELECT MODELS REFER TO DEVICE LABEL FOR WIRE COLOR CODE ENVIRACOM TERMINAL 3 IS ALSO THE FIRST THERMOSTAT TERMINAL 1 2 3 4 3 3 3 3 LEGEND SCREW TERMINAL 1 4 IN QUICK CONN...

Страница 9: ... seconds a Turns on indicator light b If flame is lost and lockout time has not expired R7184 returns to Trial for Ignition period c If flame is lost and lockout time has expired R7184 enters Recycle Mode 6 Carry Over time expires ignitor turns off 7 Enters Run Mode a Flame is monitored until call for heat ends or flame is lost If flame is lost 1 Control enters Recycle Mode 2 Recycle time starts 6...

Страница 10: ...ld cad cell from external light Indicator light turns off Eliminate external light source or permanently shield cad cell Indicator light stays on Replace cad cell with new cad cell and recheck If indicator light does not turn off remove cad cell leadwires from R7184 and recheck If indicator light turns off replace cad cell bracket assembly Refer to TRADELINE Catalog for bracket part numbers If ind...

Страница 11: ...ll face with soft cloth Check sighting for clear view of flame Place cad cell back in socket c Reconnect line voltage power and close line switch d Start burner Burner locks out Go to step 11 Burner keeps running System is okay 11 Check cad cell a Disconnect line voltage power and open line switch b Remove existing cad cell and replace with new cad cell c Disconnect all wires from ther mostat term...

Страница 12: ...TRONIC OIL PRIMARY ENVIRACOM ENABLED Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 69 1459 4 fm Page 12 Wednesday August 10 2005 1 07 PM ...

Отзывы: