Application

The Q3400A Igniter-Flame Rod Assembly replaces the

original igniter-flame rod assembly in the Q3450 and Q3480
Pilot Hardware used with the SV9500 and SV9600
SmartValve

 System. The Q3400A has a unique keyed

plug connector that will only fit the SV9500/SV9600 Sys-
tems.

This assembly can be replaced without removing the pilot

burner, see Fig. 1.
TEMPERATURE RATING:

Flame Rod Tip: 1800

°

 F [982

°

 C].

Igniter Insulator: 905

°

 F [485

°

 C].

Flame Rod Insulator: 1250

°

 F [677

°

 C].

Flame Rod Lead: 500

°

 F [260

°

 C].

Installation

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to follow

them could damage the product or cause a hazardous condi-
tion.

2. Check the ratings and description given in the instruc-

tions to make sure the product is suitable for your application.

3. Installer must be a trained, experienced service techni-

cian.

4. After installation is complete, check out product op-

eration as provided in these instructions.

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH.
Follow these warnings exactly:
1. Disconnect power supply before removing any

connectors to prevent electrical shock or equip-
ment damage.

2. To avoid dangerous accumulation of fuel gas,

turn off gas supply at appliance service valve
before starting igniter-flame rod assembly re-
moval.

REMOVE OLD ASSEMBLY

1. Turn off power at circuit breaker or fuse box.
2. Hold the bottom of the assembly with one hand. With

the other hand, remove spring clip by pulling it away from the
pilot burner. See Fig. 1.

3. Remove the assembly from the pilot burner.
4. Disconnect the leadwires from the ignition system

control module.

5. Discard the old assembly and spring clip.

G. S.  •  Rev. 7-94  •  

 Honeywell Inc. 1994  •  Form Number 69-0751—2

Q3400A

Igniter-Flame Rod Assembly

IMPORTANT: Make sure the assembly is oriented in the

proper direction for installation into the pilot burner.

MOUNT REPLACEMENT ASSEMBLY

1. Insert assembly in the pilot burner until assembly is

flush with pilot burner bracket. Secure with new spring clip
provided. See Fig. 1.

2. Connect the  igniter-flame rod assembly keyed plug to

Igniter connector on the ignition system control.

Startup and Checkout

1. Set thermostat to call for heat.
2. Watch the pilot burner during the ignition sequence.

See if:

a. Igniter glows red and pilot lights.
b. Igniter ceases to glow red after the pilot is lit.
c. Main burner lights.

3. If the ignition sequence is not as described, trouble-

shoot the system by following the procedures in the Service
section of the SV9500 SmartValve

 System Control In-

structions, form 69-0709.

!

Fig. 1—Replace Q3400A Igniter-Flame Rod
Assembly in keyed slot of pilot burner bracket.

IGNITER-
FLAME 
ROD 
ASSEMBLY

PILOT
BURNER

M9042

SPRING 
CLIP

IGNITER

FLAME 
ROD

KEYED 
SLOT

TARGET

MAKE SURE SPRING CLIP
IS FULLY OVER BOTH PILOT
BURNER AND IGNITER-
FLAME ROD BRACKETS.

Q3400A