PW7K1R1E Wiring and Setup
DIP Switch Configuration
PW7K1R1E Configuration and Installation Guide,
Document 800-26498
13
2.4 DIP Switch Configuration
The four switches on S1 DIP switch are used to configure the operating mode of the
MR62e. DIP switches are read on power-up except where noted.
All other switch settings are unassigned and reserved for future use. X = don’t care
Table 2: Jumper Settings
Jumper
Set at
Description
J1
N/A
Ethernet Connection with PoE/POE+ support
J2
N/A
Factory Use Only
J3
N/A
Tamper Switch (normally open contact) See section
14
J4
N/A
RS-485 Termination, install only if the MR62e is at the end of
the communication bus
J5
PoE
MR62e powered from the Ethernet connection
VIN
MR62e powered from an external 12 Vdc power source
connected to TB4-3 (VIN), TB4-4 (GND)
J6-J13
N/A
Factory Use Only
1
2
3
4
Definitions
OFF
OFF
OFF
OFF
Normal operating mode.
ON
X
OFF
OFF
After initialization, enable default User Name (admin) and
Password (password). The switch is read on the fly, no need
to reboot. See IT Security section for additional information
OFF
ON
OFF
OFF
Use factory default communication parameters.
ON
ON
OFF
OFF
Use OEM default communication parameters. Contact
system manufacture for details. See Bulk Erase below.
ON
ON
OFF
OFF
Bulk Erase prompt mode at power up. See Bulk Erase
section.