Installing the PRO3200 Two-Reader Module

Power

The assignment for each relay status LED is shown in the following table.

  Power

The Two-Reader Module accepts 12VDC with an operating range of 10 to 14VDC and consumes a 
maximum of 650mA of current. Locate power source as close to this board as possible. Connect power 
with minimum of 18AWG wire.The input voltage is regulated to 5VDC.The regulated voltage or the 
12VDC (pass through) is available for powering the readers. The selection is made via jumpers and is 
available at both reader connectors. 

Table 4:  

Additional PW6000 Two-Reader Module LEDs

LED number

Description

D3

Reader 0 activity

D4

Reader 1 activity

D5

Input 0

D6

Input 1

D7

Input 2

D8

Input 3

D9

Input 4

D10

Input 5

D11

Input 6

D12

Input 7

D13

Tamper

D14

Power

D15

Relay 0 status

D16

Relay 3 status

D17

Relay 2 status

D18

Relay 4 status

D19

Relay 1 status

D20

Relay 5 status

Содержание PRO3200

Страница 1: ...PRO3200 Two Reader Module PRO32R2 Installation Guide September 2013 Honeywell Inc All Rights reserved Document 800 15493 ...

Страница 2: ...ell reserves the right to change any information in this document at any time without prior notice WIN PAK is a trademark of Honeywell Inc Ordering Information Please contact your local Honeywell representative or visit us on the web at www honeywellaccess com for information about ordering Feedback Honeywell appreciates your comments about this manual Please visit us on the web at www honeywellac...

Страница 3: ...ii Unpacking Procedure vii Shipping Instructions viii Installing the PRO3200 Two Reader Module Description 1 Specifications 2 Setup 3 Setting Jumpers 3 Setting DIP Switches 4 LED Operation 5 Power 6 Communications 7 Wiring 7 Reader Wiring 10 Input Wiring 11 Control Output Wiring 11 Mounting Options 12 Installing the Module 12 PRO3200 2 Reader Input Module Programming Sheet ...

Страница 4: ... of egress buttons for example may be illegal in some cities In most applications single action exit without prior knowledge of what to do is a life safety requirement Always make certain that any required approvals are obtained in writing DO NOT ACCEPT VERBAL APPROVALS BECAUSE THEY ARE NOT VALID Honeywell never recommends using the PRO3200 or related products for use as a primary warning or monit...

Страница 5: ...imits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to c...

Страница 6: ...ate of shipment Satisfaction of this warranty shall be limited to repair or replacement of Products which are defective or defective under normal use Honeywell s warranty shall not extend to any Product which upon examination is determined to be defective as a result of misuse improper storage incorrect installation operation or maintenance alteration modification accident or unusual deterioration...

Страница 7: ...o Reader Module Installation Guide Document 800 15493 vii other party The covenants contained in this section shall remain effective throughout the term of this Agreement and thereafter unless specifically waived by Honeywell in writing ...

Страница 8: ...re Caution If any damage to the shipment is noticed before unpacking a claim must be filed with the commercial carrier All containers should be opened and unpacked carefully in order to prevent damage to the contents The following steps are used to unpack equipment in preparation for installation 1 Open the container and remove the unit s and all packing material Retain the container and all packi...

Страница 9: ...son you are returning the equipment Your original purchase order number invoice number and if the unit is still under warranty A new purchase order number if the unit is not under warranty 2 From the customer service department obtain the Return Authorization Number RMA 3 Show the RMA number on all packages shipped Packages which are not marked with an RMA number will be refused at the factory and...

Страница 10: ...o connectors provide the reader and associated I O terminals for reader 0 The last connector on the rack mount edge provides terminals for two additional general purpose inputs When the board is mounted flat two additional relay outputs and two additional general purpose inputs are available along with two dedicated inputs for cabinet tamper and power fault detection on the opposite edge of the bo...

Страница 11: ...cal Environment Reader power 5VDC 5 6 2 150mA max each or 12VDC pass through 175mA max each Reader LED output TTL compatible high 3V low 0 5V 5mA source sink max Reader buzzer output Open collector 5VDC open circuit max 10mA sink max Reader data inputs TTL compatible inputs RS 485 9 600 to 38 400 bps Power 1 twisted pair 18AWG RS 485 24AWG 4 000 feet 1 200 m max 2 twisted pair with shield 120 23pf...

Страница 12: ...mpers Table 1 Jumper Settings Jumper Setting Default Selected J1 OFF Port 1 RS 485 EOL terminator is not active ON Port 1 RS 485 EOL terminator is active J2 OFF Reader 0 Power Terminal provides 5 VDC ON Reader 0 Power Terminal provides 12 VDC J3 OFF Reader 1 Power Terminal provides 5 VDC ON Reader 1 Power Terminal provides 12 VDC ...

Страница 13: ...OFF OFF OFF ON ON ADDRESS 3 OFF OFF ON OFF OFF ADDRESS 4 OFF OFF ON OFF ON ADDRESS 5 OFF OFF ON ON OFF ADDRESS 6 OFF OFF ON ON ON ADDRESS 7 OFF ON OFF OFF OFF ADDRESS 8 OFF ON OFF OFF ON ADDRESS 9 OFF ON OFF ON OFF ADDRESS 10 OFF ON OFF ON ON ADDRESS 11 OFF ON ON OFF OFF ADDRESS 12 OFF ON ON OFF ON ADDRESS 13 OFF ON ON ON OFF ADDRESS 14 OFF ON ON ON ON ADDRESS 15 OFF OFF Reserved OFF ON 9 600 BPS ...

Страница 14: ...ut When any relay or input is energized or ON its corresponding status LED becomes ON also The LED remains ON for as long as the relay is energized Table 3 Onboard LEDs Mode LED D1 LED D2 Description Power up sequence ON OFF Start power up hardware setup OFF ON Testing RAM ON ON Testing ROM and completing initialization FLASH ON LED D1 flashes four times after power up is completed Normal Operatio...

Страница 15: ...8AWG wire The input voltage is regulated to 5VDC The regulated voltage or the 12VDC pass through is available for powering the readers The selection is made via jumpers and is available at both reader connectors Table 4 Additional PW6000 Two Reader Module LEDs LED number Description D3 Reader 0 activity D4 Reader 1 activity D5 Input 0 D6 Input 1 D7 Input 2 D8 Input 3 D9 Input 4 D10 Input 5 D11 Inp...

Страница 16: ...negative side of the transmit and receive differential signal 3 GND is the signal ground The wiring for this signal is required and NOT optional This signal must NOT be connected to chassis GND 4 Use 24 AWG low capacitance two twisted pair shielded cable Belden 9842 or equivalent Note For RS 485 Communication Connections twist the blue pair together and use as the common use the orange pair as you...

Страница 17: ...ge is selected by Jumper J2 On Board RED BROWN YELLOW WHITE GREEN BLACK DRAIN RED BROWN YELLOW WHITE GREEN BLACK DRAIN BLACK RED D1 D2 D3 D4 D15 D16 D17 D20 D18 D19 D5 D6 D7 D8 D9 D10 D11 D12 D13 D14 RS 485 TR RS 4845 TR RS 485 GND 12V GND READER1 V READER1 LED READER1 BZR READER1 D1 READER1 D0 READER1 GND IN2 IN2 COMMON IN3 IN3 COMMON RELAY2 NO RELAY2 C RELAY2 NC RELAY3 NO RELAY3 C RELAY3 NC READ...

Страница 18: ...t to chassis GND at one side ONLY NC N C Low Battery C Low Battery 12VDC Power Supply DC Output _ Relay 4 NC Relay 4 C Relay 4 NO Relay 5 NC Relay 5 C Relay 5 NO IN6 IN6 Common IN7 IN7 Common Self Powered Audio Visual Alarm Indicator NO C PWR PWR PWR PWR The connectors on this side of the board are not accessible when it is rack mounted Tamper Switch In CLOSE position when Cabinet Door is Closed T...

Страница 19: ...red via host software to support one wire single or bi colored reader LED An example of the most common configuration is shown below If Beeper Control is not used its terminal can be programmed to be the second wire for the two wire bi colored reader LED To fully utilize each reader port a 6 conductor cable 18AWG is required Reader port configuration is set via host software Table 5 Settings for W...

Страница 20: ...condition Input configuration including debounce and hold time is set via host software Control Output Wiring Six form C relay contacts are provided for controlling door strike or other devices Each may be assigned to door related functions or general purpose output They are configurable as standard energize to activate or fail safe de energize to activate via host software The energized or ON tim...

Страница 21: ... flat is that it is being installed remotely to be located near the door s being monitored In this case it will be mounted in its own enclosure creating the need to monitor cabinet tamper and power fault detection inputs The two additional general purpose inputs and outputs provided allow for the monitoring of extra sensors and control of local horns or other equipment Installing the Module 1 Set ...

Страница 22: ...0 Two Reader Module Installation Guide Document 800 15493 13 8 Recheck wiring for correct connections and continuity 9 When all boards have been installed connect the power supply cord for proper connections and power 10 Set up the panel controls using the host software ...

Страница 23: ...493 14 PRO3200 2 Reader Input Module Programming Sheet Project Name Location Country Host IC Board 0 Board Description PW Panel RS485 Port 3 Board Address 0 Location Floor Cabinet Location Tamper Input Connected Powerfail Shunted Termination Jumper J1 Not Active ...

Страница 24: ...e Cable Destination Conductor Color Power Pin 1 Power Pin 2 Inputs 4 and 5 Connected Cable Cable Destination Conductor Color Input 4 Pin 1 Input 4 Com Pin 2 Input 5 Pin 3 Input 5 Com Pin 4 Door 1 Input Output Connected Cable Cable Destination Conductor Color Input 0 Pin 1 Input 0 Com Pin 2 Input 0 Pin 3 Input 1 Com Pin 4 Relay 0 No Pin 5 Relay 0 Com Pin 6 Relay 0 NC Pin 7 Relay 1 No Pin 8 Relay 1 ...

Страница 25: ...ct J2 5 Volt Connected Cable Cable Destination Conductor Color DC Out Pin 1 Red LED Pin 2 Beeper Ctrl Pin 3 Data 1 Pin 4 Data 0 Pin 5 Common Pin 6 Door 2 Input Output Connected Cable Cable Destination Conductor Color Input 2 Pin 1 Input 2 Com Pin 2 Input 3 Com Pin 3 Input 3Com Pin 4 Relay 2 No Pin 5 Relay 2 Com Pin 6 Relay 2 NC Pin 7 Relay 3 No Pin 8 Relay 3 Com Pin 9 Relay 3 NC Pin 10 ...

Страница 26: ...tion Conductor Color DC Out Pin 1 Red LED Pin 2 Beeper Ctrl Pin 3 Data 1 Pin 4 Data 0 Pin 5 Common Pin 6 Inputs 6 and 7 Connected Cable Cable Destination Conductor Color Input 6 Pin 1 Input 6 Com Pin 2 Input 7 Pin 3 Input 7 Com Pin 4 Outputs 4 and 5 Connected Cable Cable Destination Conductor Color Relay 4 NC Pin 1 Relay 4 Com Pin 2 Relay 4 NO Pin 3 Relay 5 NC Pin 4 Relay 5 Com Pin 5 Relay 5 NO Pi...

Страница 27: ...ed Security 135 W Forest Hill Avenue Oak Creek WI 53154 United States 800 323 4576 414 766 1798 Fax www honeywellaccess com Specifications subject to change without notice Honeywell All rights reserved Document 800 15493 ...

Отзывы: