SPECIFICATION DATA

68-3084-02

PC3F2699IUF00 Hydronic 

Circulating 3 Speed Pump

APPLICATION

The PC3F in-line, wet rotor circulator with universal flange is 

designed for applications in closed-loop hydronic heating and 

cooling systems, as well as in solar-powered systems. The 

pump is non-submersible and for use in dry, frost-free, well-

ventilated installations.

SPECIFICATIONS

Rate of flow: 

up to 34 gpm (128.7 lpm)

Pressure head: 

up to 31 ft (9 m)

Voltage: 

/-10% 60hz

Amperage: 

See “Speed switching” on page 2.

Max. Pressure:

145 psi (at room temperature);

50 psi (at 200°F [93°C])

Temperature Range:

Ambient temperature: 32°F to 104°F (0°C to 40°C)

Media temperature: 14°F to 230°F (-10°F to 110°C) [to 200°F 

(93°C) with optional check valve installed]

Storage Temperature: 

-40°F to 100°F (-40° to 66°C)

Standards:

Insulation Class F

Temperature Class FT 95

  

Fig. 1. Pump dimensions in in. (mm).

Shipping weight: 

9.5 lbs (4.32 Kg)

L1

L2

L3

L4

L5

6.5 (165.5) 6.1 (155) 6.5 (165.5) 7.75 (197) 3.2 (80.2)