SPECIFICATION DATA
68-3083-02
PC3F1558IUF00 Hydronic
Circulating 3 Speed Pump
APPLICATION
The PC3F in-line, wet rotor circulator with universal flange is
designed for applications in closed-loop hydronic heating and
cooling systems, as well as in solar-powered systems. The
pump is non-submersible and for use in dry, frost-free, well-
ventilated installations.
SPECIFICATIONS
Rate of flow:
Up to 15 gpm (56.8 lpm)
Pressure head:
Up to 19.4 ft (6 m)
Voltage:
115 VAC +/- 10% 60Hz
Amperage:
See “Speed switching” on page 2.
Max. Pressure:
145 psi (at room temperature);
50 psi (at 200°F [93°C])
Temperature Range:
Ambient temperature: 32°F to 104°F (0°C to 40°C)
Media temperature: 14°F to 230°F (-10°C to 110°C) [to 200°F
(93°C) with optional check valve installed]
Storage Temperature:
-40°F to 100°F (-40° to 66°C)
Standards:
Insulation Class F
Temperature class: TF 95
Fig. 1. Pump dimensions in in. (mm).
Shipping Weight:
7.8 lbs (3.54 Kg)
L1
L2
L3
L4
L5
6.5 (165.5) 5.5 (140)
4.7 (118)
6.6 (167)
3.2 (80.2)
M32832A
L2
L4
L3
L1
L5