SCS Series Manual —
P/N 15712:L 7/18/16
The SCS⁄SCE
Programming
Example:
Switch group 1 for an SCS at address 1 would have protocol points 1-4 asso-
ciated with it. If the switch group was defined as switch group type 5, a con-
trol module would be mapped to point 1 and a monitor module would be
mapped to point 3 with points 2 and 4 unneeded.
Optional Feature Programming for Control and
Monitor Modules
In order for control and monitor modules to function properly in smoke con-
trol applications, certain optional features must be set. When programming Control Modules for smoke control applications, the Walk Test
option must be disabled and the Signal Silence option must be enabled. This is accomplished by answering "NO" to the question "IS THE
WALK TEST OPTION TO BE ENABLED FOR THIS DEVICE?" and answering "YES" to the question "IS THE SIGNAL SILENCE
OPTION TO BE ENABLED FOR THIS DEVICE?" within partial point programming, as shown below, or full point programming, as
shown in Section 2.4.4. When programming Monitor Modules for smoke control applications, the Tracking option must be enabled. This is
accomplished by answering "YES" to the question "DO YOU WANT TO CHANGE THE TRACKING OPTION FOR THIS DEVICE?"
within partial point programming, as shown below, or full point programming, as shown in Section 2.4.4.
Programming of the optional features for all modules can be accomplished through Partial Point Programming. After entering the program-
ming mode, select option 3, partial point programming, of the Main Programming Menu by pressing the following keys at the prompt:
3 [
3=PPRG
Option 3 from the Programming Menu allows the programmer to change the operational parameters of SLC Loop devices, software-defined
zones, and EIA-485 protocol points.
After entering Partial System Programming, select option 4, Optional Features, by pressing the following keys at the prompt:
4 [
4=OPTNS
Option 4 of the Partial Point Programming Menu allows the programmer to individually enable or disable, per device, the functions of Signal
Silence and Walk Test (for control modules), Alarm Verification and Sensitivity (for addressable detectors), and Tracking (addressable detec-
tors and monitor modules). These functions must still be enabled or disabled, as appropriate, for the entire system (see Partial System Pro-
gramming). For an explanation of the functions of Signal Silence, Alarm Verification, Sensitivity, and Tracking, see the Glossary of Terms
and Abbreviations at the end of this manual.
A control module example:
PRESS@1=TYPID,2=CBE,3=LBL,4=OPTNS,5=AMAP,6=CCBE@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:@4
ENTER@LXX(D/M)YY,@ZXXX@OR@AXXPYY@FOR@PT.@CHANGE@(BCKSPC@TO@ABORT)@@@@@@@:@L3M21
DO@YOU@WANT@TO@CHANGE@THE@SIGNAL@SILENCE@OPTION@FOR@THIS@DEVICE?@(Y=YES,N=NO):@Y
IS@THE@SIGNAL@SILENCE@OPTION@TO@BE@ENABLED@FOR@THIS@DEVICE?@(Y=YES,N=NO)@@@@@:@Y
DO@YOU@WANT@TO@CHANGE@THE@WALK@TEST@OPTN@FOR@THIS@DEVICE?@(Y=YES,N=NO)@@@@@@@:@Y
IS@THE@WALK@TEST@OPTION@TO@BE@ENABLED@FOR@THIS@DEVICE?@(Y=YES,N=NO)@@@@@@@@@@:@N
A monitor module example:
PRESS@1=TYPID,2=CBE,3=LBL,4=OPTNS,5=AMAP,6=CCBE@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:@4
ENTER@LXX(D/M)YY,@ZXXX@OR@AXXPYY@FOR@PT.@CHANGE@(BCKSPC@TO@ABORT)@@@@@@@:@L5M13
DO@YOU@WANT@TO@CHANGE@THE@TRACKING@OPTN@FOR@THIS@DEVICE?@(Y=YES,N=NO)@@@@@@@@:@Y
IS@THE@TRACKING@OPTION@TO@BE@ENABLED@FOR@THIS@DEVICE?@(Y=YES,N=NO)@@@@@@@@@@@:@Y
Full Point Programming
After entering the programming mode, select option 4, full point programming, of the Main Programming Menu by pressing the following
keys at the prompt:
4 [
L3M64
A1P1
A1P4
L3M65
A1P2
A1P3
unneeded
unneeded