SCS Series Manual —
P/N 15712:L 7/18/16
85
Programming
The SCS⁄SCE
After selecting option 3 from the Main Programming menu, the display will show the Partial Point Programming submenu:
PRESS@1=TYPID,2=CBE,3=LBL,4=OPTNS,5=AMAP,6=CCBE@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:
After entering Partial System Programming, select option 2, Control-By-Event, by pressing the following keys at the prompt:
2 [
2=CBE
Option 2 of the Partial Point Programming Menu allows the programmer to change the Control-By-Event (CBE) for any detector, module or
software zone. The panel maintains a CBE for each device and zone installed in the system.
When programming a particular device, the control panel prompts the programmer with:
ENTER@CONTROL-BY-EVENT@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:
The following display illustrates CBE programming for control module number 23 on SLC Loop 2 to activate software zones 15 and 29.
PRESS@1=TYPID,2=CBE,3=LBL,4=OPTNS,5=AMAP,6=CCBE@@@@@@@@@@@@@@@@@@@@@@@@@@@@:@2
ENTER@LXX(D/M)YY,@ZXXX@OR@AXXPYY@FOR@PT.@CHANGE@(BCKSPC@TO@ABORT)@@@@@:@L2M23
ENTER@CONTROL-BY-EVENT@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:
(Z15@Z29)
For a complete description of the types, parameters, limitations, and guidelines of CBE programming, see Appendix A, Control-By-Event.
EIA-485 Protocol Point Mapping
Each control and monitor module associated with the FACP (being used for the purpose of smoke control or HVAC) must be properly and
separately mapped to the specific protocol points of each toggle switch group within the SCS⁄SCE. This information must be programmed so
that data going between the SCS⁄SCE and control/monitor modules can be properly routed through the FACP.
Programming of point mapping for all modules can be accomplished through Partial Point Programming. After entering the programming
mode, select option 3, partial point programming, of the Main Programming Menu by pressing the following keys at the prompt:
3 [
3=PPRG
Option 3 from the Programming Menu allows the programmer to change the operational parameters of SLC Loop devices, software-defined
zones, and EIA-485 protocol points.
After selecting option 3 from the Main Programming menu, the display will show the Partial Point Programming submenu:
PRESS@1=TYPID,2=CBE,3=LBL,4=OPTNS,5=AMAP,6=CCBE@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:
After entering Partial System Programming, select option 5, Annunciator Point Mapping, by pressing the following keys at the prompt:
5 [
5=AMAP
Option 5 of the Partial Point Programming Menu allows the programmer to individually map devices or zones to EIA-485 protocol points for
proper communication.
The following display illustrates mapping monitor module 11 on SLC Loop 1 to an SCS Module at address 1, Point 3.
PRESS@1=TYPID,2=CBE,3=LBL,4=OPTNS,5=AMAP,6=CCBE@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:@5
ENTER@LXX(D/M)YY,@ZXXX@OR@AXXPYY@FOR@PT.@CHANGE@(BCKSPC@TO@ABORT)@@@@@@@:@L1M11
DO@YOU@WANT@TO@CHANGE@THE@ANNUNCIATOR@MAPPING@FOR@THIS@POINT?@(Y=YES,N=NO)@@@:@Y
DO@YOU@WANT@THIS@POINT@MAPPED@TO@AN@ANNUNCIATOR?@(Y=YES,N=NO)@@@@@@@@@@@@@@@@:@Y
ENTER@AXXPYY@FOR@ANNUNCIATOR@POINT@MAPPING@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:@A1P3
Each protocol point must be installed through Full Point Programming, as shown in Section 2.4.2, before a control or monitor module may
be mapped to it. Every control and monitor module utilized for smoke control must be mapped to its associated protocol point within its
respective switch group, as shown below.
NOTE:
A software zone is not a physical zone, but rather a software grouping in control panel memory.