200
SCS Series Manual —
P/N 15712:L 7/18/16
AM2020/AFP1010 Control-By-Event
Programming Examples
Example # 3
L1D1 activates Z1. L1M1 turns on when Z1 is active. L1D2 is a
null equation. L1M2 activates with L1D2 after a ten minute
delay. Z238 is active July 4th of every year. L1M3 will activate
when Z1 and Z238 are active. Z239 is active when Z1 is on after
a one minute delay and will stay on for 5 minutes. L1M4 turns
on when Z239 is active.
Example # 4: Fire Floor, Floor Above, Floor
Below
L1D1 activates Z1 and Z2. L1D2 activates Z1, Z2 and Z3. L1D3
activates Z2, Z3 and Z4. L1M1 will activate when Z1 is active.
L1M2 will activate when Z2 is active. L1M3 will activate when
Z3 is active. L1M4 will activate when Z4 is active.
L1M3
L1D1
RZON
Z239
RZON
Z240
L1D2
L1M2
L1M1
Z1
L1M4
RZON
Z239
RZON
Z238
(Z1)
( )
DEL(00.01.00 00.05.00 (Z1))
TIM( 7 - 4 - )
AND(Z1 Z238)
OR(Z239)
DEL(00.10.00 (L1D2))
OR(Z1)
Z4
L1D1
Z2
L3D1
Z3
L2D1
L1M2
L1M1
Z1
L1M4
L1M3
(Z1 Z2)
(Z1 Z2 Z3)
(Z2 Z3 Z4)
OR(Z1)
OR(Z2)
OR(Z3)
OR(Z4)