76
RP-2002 Series Manual —
P/N 53039:E6 1/26/2017
Programming
Master Programming Level
After completion of the Walktest, press the
Esc
(Escape) key to exit Walktest Mode and return to
the Walktest Screen. The results of the Walktest can now be viewed by pressing
3
while viewing
the Walktest Screen. The following screen will be displayed:
Use the up and down arrow keys to view all of the walktest results which will be displayed as
illustrated in the preceding screen. Note that the Walktest log is stored in RAM. If all power (AC
and DC) is removed from the FACP, the Walktest log information will be lost. This information is
also overwritten when subsequent walktests are performed.
3.5.10 Clear Program
Pressing
1
while viewing Programming Screen #4, will select the Clear Program option. The
control panel will provide a warning to the user by prompting with the following display:
Pressing
1
for
Yes
will cause the control panel to carry out the selected clear option. Pressing
2
for
No
will prevent programming from being cleared.
3.5.11 Password Change
The factory set passwords, which have been programmed into the control panel, can be changed by
selecting the Password Change option. Pressing
2
while viewing Programming Screen #4 will
cause the following screen to be displayed:
Press
1
to change the Master Programming Level password or
2
to change the Maintenance Level
password.
Note that the passwords will not be displayed on annunciators.
The following screen will appear when either change option is selected:
A flashing cursor will appear in the center of the display. Enter a new five digit password (such as
10101 for the Master Level). After the fifth digit is entered, the following screen will be displayed:
The new five digit password must be re-entered to accept the change. The display will then return
to the initial Password Change Screen.
WALKTEST EVENTS
PROGRAMMING
1=CLEAR PROGRAM
2=PASSWORD CHANGE
Programming Screen #4
WARNING!
SYSTEM CHANGE
PROCEED?
1=YES 2=NO
PASSWORD CHANGE
1=MASTER
2=MAINTENANCE
Password Change Screen
ENTER NEW FIVE DIGIT
PASSWORD
Enter Password Screen
VERIFY NEW
PASSWORD
Password Change Screen
Содержание NOTIFIER RP-2002C
Страница 22: ...22 RP 2002 Series Manual P N 53039 E6 1 26 2017 Installation Backbox Mounting Figure 2 3 Backbox nfw 50cab cdr ...
Страница 158: ...Cut along dotted line ...
Страница 160: ...World Headquarters 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www notifier com ...