RP-2002 Series Manual —
P/N 53039:E6 1/26/2017
147
Appendix D: FACP with Keltron
The following figure illustrates the connections between the FACP and Keltron
Receiver/Transmitter.
IMPORTANT!
All connections between the FACP and Keltron modules must be made within 20
feet and enclosed within conduit or equivalently protected against mechanical injury.
!
CAUTION:
OBSERVE CORRECT TERMINAL LOCATIONS
FOR REASONS OF WIRING DIAGRAM CLARITY, TERMINAL DESIGNATIONS OF KELTRON
MODULES ARE NOT SHOWN IN ACTUAL ORDER. FOLLOW KELTRON MANUAL AND MODULE
MARKINGS FOR EXACT TERMINAL LOCATIONS TO PREVENT SEVERE MODULE DAMAGE.
Fire Alarm Control Panel
(terminal blocks are not shown in their actual
positions in order to clarify wiring connections)
Keltron 95M3158 TTM-RPS
1.
Terminals 7 and 8: Remote station alarm/trouble inputs
2.
Terminals 9 and 10: Sprinkler supervisory input
Note:
Cut TBL jumper on 4XTM module to send
alarm/trouble signal from the same pair or terminals.
Alarm/Trouble
Signal
Sprinkler Supervisory
Signal
*Note:
For more
information, refer to the
Keltron manual.
4XTM Module
UL-Listed
UL-Listed