RP-2001 Series Manual —
P/N 52985:D5 1/26/2017
109
Template 7: Single Hazard - Dual Zone
FACP Configuration Templates
B.7 Template 7: Single Hazard - Dual Zone
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit).
Input Zone Types:
•
Zone 1 = 2-wire smoke
•
Zone 2 = Fire
•
Zone 3 = Low Pressure
•
Zone 4 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
•
Zone 5 = Pull Station
•
Zone 6 = Manual Release
Output Circuit Types:
•
Output 1 = Alarm NAC, silenceable, coded for steady on
•
Output 2 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10
secs.), silenceable, coded for steady on
•
Output 3 = Release Solenoid 1 (unsupervised for shorts)
•
Output 4 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10
secs.), silenceable, coded for steady on
Timers
•
Soak Timer 1 - set for 10 minutes
•
Soak Timer 2 - set for 10 minutes
•
Waterflow Delay Timer - set for 10 seconds
•
AC Loss Delay Timer - set for 2 hours
Operation
•
Activation of Input Zone 1 (2-Wire Smoke)
or
Zone 2 (Fire)
or
Zone 5 (Pull Station)
or
Zone
6 (Manual Release) will operate the Alarm NAC Output #1 and Release Solenoid 1 Output #3.
Release Solenoid will turn off water release following time-out of the 10 minute Soak Timer 1
•
Activation of Input Zone 4 (Waterflow) will operate the Alarm NAC Output #1, Waterflow
NAC Output #2 and Waterflow NAC Output #4. There is a 10 second FACP initiated delay in
activation of these outputs since the Waterflow Delay Timer is set to 10 seconds
•
Activation of Input Zone 3 (Low Pressure) will not operate any Output Circuits (see Relays)
Template 7: SINGLE HAZARD - DUAL ZONE
INPUT ZONES
1
2
3
4
5
6
OUTPUT CIRCUITS
2-WIRE SMOKE
FIRE
LOW
PRESS.
WATERFLOW
PULL
STATION
MANUAL
RELEASE
#1 ALARM NAC
X
X
X
X
X
#2 WATERFLOW NAC
X
#3 RELEASE SOLENOID 1
X
X
X
X
#4 WATERFLOW NAC
X