NFW-50X Manual —
P/N LS10129-001NF-E:C 7/25/2018
75
Master Programming Level
Programming
Pressing
1
while viewing this screen will select System Sensor synchronization,
2
will select Wheelock, and
3
will select Gentex.
Maximum Number of Strobes for Synchronization
The total current draw for each Notification Appliance Circuit cannot exceed 2.5 amps. Refer to the manufacturer’s documentation sup-
plied with the Strobes to determine the maximum current draw for each strobe and ensure that the circuit maximum is not exceeded. To
ensure proper strobe and circuit operation, there is also a limit to the number of strobes that can be attached to each circuit.
Relays
Pressing
3
while viewing System Setup Screen #2 will allow the programmer to configure two main circuit
board Form-C relays from the following screen:
To program Relay 1 or Relay 3, press the number corresponding to the selected relay. Note that Relay 2 is fixed as a Trouble relay.
Selecting Relay 2 will have no effect on its programming. The following screen will appear for each relay to be programmed:
Pressing
1
for Type while viewing the Relay Screen will cause the following screens to be displayed:
While viewing the selected screen, press the number corresponding to the desired relay type to program the main circuit board relay. The
choice will be stored in memory and the display will return to the Relay Type Screen which will show the programmed type choice.
Press the Escape key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.
Canadian Option
Pressing
1
while viewing System Setup Screen #3 will configure the FACP to comply with Canadian
requirements. The display will change to
Canadian Opt. On
. Each press of the
1
key will cause the display
to toggle between
Canadian Opt. On
and
Canadian Opt. Off
. Refer to the table on page 46 for permissible
settings.
Important!
For Canadian Applications, this option must be set to ON prior to any other panel programming.
The Canadian Options configures the FACP with the following as required by Canada:
•
The following monitor module type codes are
not
available:
monitor
non-latching supervisory
non-latching drill
non-latching process monitor
process monitor
hazard
tornado
medical alert
•
The auto-silence timer is fixed at 20 minutes and cannot be changed.
•
Addressable ionization smoke detector sensitivity is automatically monitored using Canadian specifications.
•
The Positive Alarm Sequence and Pre-Signal option are not available for Canadian applications.
SYSTEM SETUP
1=TIMERS
2=NACS
System Setup Screen #2
RELAYS
1=RELAY 1
2=RELAY 2
3=RELAY 3
Relays Selection Screen
RELAY #
1=TYPE
ALARM
Relay Type Screen
RELAY
1=ALARM
2=SUPERVISORY
3=SUPERVISORY AR
Relay Screen #1
RELAY
1=TROUBLE
2=COMM FAIL
3=PROCESS_MON
Relay Screen #2
RELAY
1=PROCESS MON AR
2=AC LOSS
3=HAZARD
Relay Screen #3
RELAY
1=MEDICAL
2=SILENCEABLE ALARM
3=CARBON MONOXIDE
Relay Screen #4
NOTE:
1.
AR (AutoResettable)
in
SUPERVISORY AR
and
PROCMON AR
means that a relay with the Supervisory and/or Process Monitor type
code, when activated, will automatically reset when the corresponding condition is cleared.
2. A relay programmed with the Silenceable Alarm type will activate upon any alarm and deactivate when the FACP Alarm Silenced LED is
illuminated.
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3
SYSTEM SETUP
1=CANADIAN OPT OFF
2=WATERFLOW SIL. NO
Содержание NOTIFIER NFW-50X