NFW-50X Manual —
P/N LS10129-001NF-E:C 7/25/2018
43
Optional Module Installation
Installation
N-
ANN-RLY Annunciator Module
Specifications
•
Operating Voltage: 24 VDC
•
Max. Current:
Alarm: 75 mA
Standby: 15 mA
•
Operating Temperature: 32°F to 120°F (0°C to 49°C)
•
For indoor use in a dry location only
Mounting/Installation
The N-ANN-RLY relay module can be mounted inside the FACP main circuit board chassis or inside the ROME Series enclosure. Refer
to the
N-ANN-RLY Installation Document #53318
for instructions on chassis mounting or to the
ROME Series Installation Document
#53530
for mounting in the separate backbox.
mounting holes
mounting hooks through
mounting slots
grounding wire
N-ANN-RLY
ANN-MBRLY
mounting bracket
mounting holes
mounting holes
FACP Backbox Installation
using ANN-MBRLY mounting bracket
FACP Chassis Installation
mounting holes
mounting holes
N-ANN-RLY on
ANN-MBRLY
mounting bracket
ROME Series Installation
using ANN-MBRLY mounting bracket
Figure 2.28 N-ANN-RLY Mounting Options