Programming
Basic Program
Change Autoprogram Default Values
To assign system default values from the basic program screen, Press
0
(clear), then press
1
(autoprogram). Refer to the chart below for default values and how to modify them.
Table 2.1 Autoprogram Defaults (1 of 2)
Function
Default Values
To Alter, refer to
Software
Zones
01-99
Default custom label “Zone xx” where xx is the
number of the zone
Note
: Zone 00 is reserved for a general alarm.
“How to Create a Custom Zone Label (5=
ZONE
)” on page 27
F0
PRG PRESIGNAL FUNCT PRESIGNAL DELAY
DELAY=180
PAS=NO
F00
Releasing
Zones
R0-R9
PRG RELEASE FUNCT RELEASE CONTROL
DELAY=00 ABORT=ULI CROSS=N SOK=0000
“R0-R9 (Releasing Functions) The Releasing Function screen
provides fields for changing releasing functions: Delay Timer,
Abort Switch, Cross Zone, and Soak Timer. For details on
releasing applications, refer to “NFPA Releasing Applications”
on page 61.” on page 29 and “How to Program a Releasing
Zone” on page 61.
F5 and F6
PRG TIME FUNCTION
TIME CONTROL
ON=**:** OFF=**:** DAYS=********
F7
PRG HOLIDAY FUNCTION **/** **/** **/**
**/** **/** **/**
**/** **/** **/**
F8
PRG CODING FUNCTION CODE TYPE
MARCH TIME
F08
F9
PRE-ALARM FUNCT
ALERT
F09
System
Parameters
SIL INH=0000 AUTO=0077
0 VERIFY=30 USA TIME
TERM=N AC_DLY=Y LocT BLINK=01 ST=4 ACS=N
“How to Change Global System Functions (7=
SYSTEM
)” on
Passwords Default programming passwords are:
Program Change=00000
Status Change=11111
“How to Change a Password (3=
PASSWD
)” on page page 25
SYSTEM
NORMAL
message
(YOUR CUSTOM SYSTEM MESSAGE HERE)
SYSTEM NORMAL 10:23A 041508 Tue
A message, along with the current day, time, and
date, that displays on the second line of the LCD
display during normal operation.
Note
: The second line, “SYSTEM NORMAL”, is a standard
system message that you cannot change
NOTE: The FCM-1-REL has an inherent two second
delay, which must be factored into the DELAY TIME
and SOK (soak time) entries.