background image

D2

P/N 51850:D2

ECN 16-0219

Document 51850
10/07/2016                    Rev:

Liquid Crystal Display

LCD-160

Manual

Содержание NOTIFIER LCD-160

Страница 1: ...D2 P N 51850 D2 ECN 16 0219 Document 51850 10 07 2016 Rev Liquid Crystal Display LCD 160 Manual ...

Страница 2: ...uate warning of a fire Smoke detectors cannot be expected to provide adequate warn ing of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materi als etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate o...

Страница 3: ...cuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will not interfere with battery trans former or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening m...

Страница 4: ... version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for printed manu...

Страница 5: ...g 16 6 1 Overview 16 6 2 The RDP Bus 17 6 2 1 Wire Runs 17 6 2 2 RDP Bus Wiring Specifications 17 6 2 3 Shielding the RDP Bus 18 6 2 4 Connecting the RDP Bus 18 6 3 Earth Ground 19 6 4 Power Supply Connections 20 6 5 Connecting the Annunciator Key Switch 21 Section 7 The LCD 160 Interface 22 7 1 The Liquid Crystal Display 22 7 2 The Keypad 22 7 2 1 Soft Keys 22 7 2 2 Fixed Function Keys 23 7 2 3 S...

Страница 6: ... 9 2 1 Event Counts Display 34 9 2 2 More Information 36 9 2 3 Multiple Event List Display 37 9 3 Service Screens 39 9 3 1 Version Information 39 9 3 2 Power up Screen 40 9 3 3 Download Screen 40 9 3 4 Download Application Screen 41 9 3 5 Download Bootloader Screen 41 9 3 6 Download Strings Screen 41 9 3 7 Application Corrupt Screen 42 Index 44 ...

Страница 7: ...DAMAGE IRREVERSIBLE LOSS OF PROGRAMMING DATA OR PERSONAL INJURY When you see Specifies Example text in all caps and bold text In body text text as it appears in the LCD display or on the panel MARCH TIME is a selection that appears in the LCD display or Press the ENTER key text in quotes a reference to a section or a LCD menu screen Status Change specifies the Status Change section or menu screen ...

Страница 8: ...o become familiar with functions in general make use of the documentation listed in Table 2 1 2 2 UL 9th Edition Compliance This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL 864 9th Edition The following products have not received UL 864 9th Edition certification and may only be used in retrofit applications ...

Страница 9: ...cement of any programmable devices Custom graphics Rubberized keypad Input for AKS 1 key switch Non volatile storage of local parameters text and a single character set Fits in two ACS Annunciator module locations Display and Control Center DCC participation indication 3 2 2 Specifications 24 VDC input supply voltage via non resettable power supply interface TB2 Data Communications Port RDP interf...

Страница 10: ...out is illustrated in Figure 3 1 J1 Key Switch LED 13 Transmit LED 12 Receive SW17 LED14 MicroFail LED11 Status TB2 Power TB1 RDP Port See Figure 6 6 See Figure 6 3 See Figure 6 8 See Figures 6 4 and 9 3 J4 NUP Future Figure 3 1 LCD 160 Board Layout 24 VDC 24 VDC COMMON COMMON RDP RDP RDP RDP REF EARTH ELR Programming Switch REF ...

Страница 11: ...panel Figure 5 2 2 Mount the dress panel to the backbox 3 Make all electrical connections RDP bus shielding if necessary Figures 6 2 6 3 Power circuit Figure 6 6 4 Attach doors to backboxes Section 5 2 5 Power up system according to instructions in the control panel manual 6 Configure the LCD 160 Section 9 1 If mounting into an ABS 2D 4D or ABF 2B 4B backbox Section 4 1 Make all electrical connect...

Страница 12: ...abinet A surface or semi flush enclosure for mounting one to four rows of equipment plus batteries up to two 25AH batteries There are four different sizes available The separately ordered doors can be mounted on the left or the right side of the cabinet reversible hinges are provided so that this choice can be made in the field Doors open a full 180 degrees and have locks A trim ring option is ava...

Страница 13: ...ounts on a CAB 4 series backbox and the LCD 160 mounts directly to threaded studs on the dress panel An LCD 160 mounted on an ADP 4B fits in front of most CAB 4 series chassis as long as the top layer of the chassis is displayless or unoccupied Figure 4 2 ADP 4B shown with LCD 160 VP 2B VP 2 Use the VP 2B Vented Dress Panel when annunciators are to be installed in the top row of a Notifier cabinet...

Страница 14: ... security for the control switches on the LCD 160 The key switch kit includes a key and hardware for mounting to the trim plate of a flush mount type annunciator enclosure An adhesive backed Annunciator Label for use with the key switch dress plate assembly is also included The B version is black and displays the Notifier logo ...

Страница 15: ...Bus on page 18 and Power Supply Connections on page 20 3 If using a semi flush mount backbox attach the door Align the door with the dress plate and slide the door down onto the pins on the dress plate When positioned correctly the door will open and close freely In an ABS 2D 4D or ABF 2B 4B backbox 1 Plug the two annunciator terminal blocks into the annunciator to complete communication and power...

Страница 16: ...different knockouts Install tie wraps and adhesive squares to secure the wiring WARNING REMOVE ALL POWER SOURCES TO EQUIPMENT WHILE CONNECTING ELECTRICAL COMPONENTS LEAVE THE EXTERNAL MAIN POWER BREAKER OFF UNTIL INSTALLATION OF THE ENTIRE SYSTEM IS COMPLETE WARNING SEVERAL SOURCES OF POWER CAN BE CONNECTED TO THE CONTROL PANEL BEFORE SERVICING THE CONTROL PANEL DISCONNECT ALL SOURCES OF INPUT POW...

Страница 17: ...RDP bus 6 2 2 RDP Bus Wiring Specifications Wire the RDP bus as shown in Connecting the RDP Bus on page 18 These requirements must be followed There is a maximum of 4000 feet at 12 AWG to 18 AWG between the panel and the last device on the RDP bus subject to your system s power restrictions The wiring size must be a 12 AWG to 18 AWG twisted pair cable having a characteristic impedance of 120 ohms ...

Страница 18: ...ting the RDP Bus Figure 6 3 provides RDP circuit diagrams for the LCD 160 See RDP Bus Wiring Specifications on page 17 for circuit requirements End of Line Resistor for RDP Devices If the LCD 160 is the last device on the RDP bus the end of line resistor on SW17 must be enabled SW17 is located on the bottom edge of the LCD 160 board Switch 2 on the dip switch SW17 sets the end of line resistor for...

Страница 19: ...s a cold water pipe Connect the LCD 160 s Earth Ground located on the RDP interface to a mounting screw on the backbox or cabinet See Figures 6 3 and 6 5 NOTE Switches 3 and 4 MUST remain disabled Figure 6 4 SW17 ELR Disabled LCD160SW17 wmf LDC160SW17location wmf The End of Line Resistor is disabled Switch 2 is OFF The slider is away from the display screen Figure 6 5 Grounding the LCD 160 ...

Страница 20: ... run to the LCD 160 need not contain a Power Supervision Relay because loss of power is inherently supervised through communication loss loss of RDP communication is registered at the control panel during loss of power to the LCD 160 For details about connections to particular control panels see the appropriate control panel manual Note On the LCD 160 earth ground is located on TB1 with the RDP in...

Страница 21: ...nabled Common Reference LCD 160 Remote Power Supply A caba3 wmf Fire Alarm Control Panel or Network Control Annunciator Two wire RDP bus Power Loop When more than one power supply is used on an RDP bus a common reference connection must be established and only one supply can have ground fault detection enabled lcd160 keypad cdr Power Loop Common Reference Remote Power Supply B Ground fault detecti...

Страница 22: ...es of keys soft keys and fixed function keys With the exception of the lamp test key all keys are disabled when the Annunciator Key Switch is locked 7 2 1 Soft Keys The six keys to the right and left of the display function to select commands that appear on the display Each screen has different information and each key changes function to suit the screen Beneath each screen in this manual is a des...

Страница 23: ...rifies the command on all networked displays This key will not function if the key switch is locked or Local Control is disabled If the associated fire panel has both MNS and Fire alarm conditions present at the same a second system reset is needed to fully reset the panel once the conditions have been cleared Refer to the appropriate panel manual for further information about this function DRILL ...

Страница 24: ...s are unacknowledged Supervisory Yellow Illuminates when at least one supervisory event exists It will flash if any of these events are unacknowledged System Trouble Yellow Illuminates when at least one trouble event exists It will flash if any of these events are unacknowledged Other Event Yellow Illuminates for any category of event not listed above including MNS alarms Process Monitor CO Alarm ...

Страница 25: ... each 40 characters long Line one is a custom message Line two is a standard message showing the System Normal status Line five indicates the current time and date 8 1 2 Event Reporting Format When there is an off normal event the System Normal message will be replaced by a message in the Event Reporting format There are two basic types of message formats point event formats which are generated fr...

Страница 26: ...L03D002 Line 1 DisplaysTROUBLE the type of trouble and whether it has been acknowledged or cleared Event Format nottrouble or pre alarm Event Format trouble Line 1 Displays PREALARM the sensitivity reading and whether it has been acknowledged or cleared PREALARM 120 OF FIRE SENSITIVITY LEVEL5 ELEVATOR LOBBY EAST WING FIFTH FLOOR Z239 SMOKE PHOTO 11 58 45A TUE JAN 12 2016 N112L03D002 Event Format p...

Страница 27: ...me The user s actions at any participating station panel or remote display determine which location will be the DCC An LCD 160 s DCC participation is set at the fire panel If the panel associated with an LCD 160 has been programmed to participate in the DCC all remote displays with Local Control ON will automatically participate Refer to the panel programming manual for more information When an LC...

Страница 28: ... DCC Request Screen Figure 8 4 DCC Release Screen YES Press this key to release control to the requesting device NO Press this key to deny control to the requesting device FIRE ALARM ELEVATOR LOBBY EAST WING FIFTH FLOOR Z005 SMOKE PHOTO 11 57 45A TUE JAN 12 2016 N112L03D052 REQUESTING AUTHORIZATION FROM N054 FIRE ALARM ELEVATOR LOBBY EAST WING FIFTH FLOOR Z005 SMOKE PHOTO 11 57 45A TUE JAN 12 2016...

Страница 29: ... acknowledge or as a group block acknowledge Event Acknowledge Event acknowledge acknowledges off normal events one at a time you must press the acknowledge key once for each event to be recognized Fire and MNS alarms must always be individually acknowledged Block Acknowledge Block Acknowledge acknowledges multiple events other than fire alarms with the press of a single button Fire and MNS Alarms...

Страница 30: ... screen This option will not be visible if any unacknowledged fire alarms exist or if the programming switch is disabled See pages 31 32 GRAPHIC SCREEN Press this key to display the Graphic Screen This key will not be available while there are any off normal events See page 30 9 0 2 The Graphic Screen The LCD 160 allows for custom graphics Pressing the soft key to the right of GRAPHIC SCREEN on th...

Страница 31: ...alarm present 9 1 1 Setting the Programming Switch The LCD 160 s programming switch must be enabled to program the LCD 160 Set dip switch 1 on SW17 to permit programming on the LCD 160 SW17 is located on the bottom edge of the LCD 160 board To enable use a small screwdriver to slide the switch up towards the display To disable slide the switch down away from the display LAKESIDE GENERAL HOSPITAL S...

Страница 32: ...ase the LCD 160 s address on the RDP bus The address will cycle from 1 to 32 PIEZO Press this key to toggle the status of the piezo between OFF and ON LCD DISPLAY Press this key to go to the LCD Display menu ACCEPT Press this key to accept changes programmed in Panel Program Menu and LCD Display A confirmation screen will display before your new settings are saved BACK Press this key to return to ...

Страница 33: ...IL DEFAULT Press this key to revert all screen preferences to their factory settings ACCEPT Press this key to accept your changes A confirmation screen will display before your new settings are saved BACK Press this key to return to the previous screen without accepting information entered LCD DISPLAY LCD INTENSITY 40 BRIGHTER DEFAULT DARKER ACCEPT BACKLIGHT ON EXCEPT AC FAIL BACK NOTE ON EXCEPT A...

Страница 34: ... soft key to the left of EVENT COUNTS DISPLAY on the Main Menu brings up the Event Counts screen This screen can be displayed anytime including when no off normal events exist It will automatically display if an off normal event requiring acknowledgement occurs Fire alarm events however will display even in programming mode Lines one through five display the system normal message when no off norma...

Страница 35: ... key to silence all panel outputs programmed as silenceable SYSTEM RESET Press this key to send a reset command to the panel and to clear the LCD 160 database of all off normal events If both Fire and MNS conditions are present on the panel a second System Reset is needed to clear the alarms from the panel MENU Press this key to return to the Main Menu This option will not be visible if an unackno...

Страница 36: ...tor exceeding the prealarm level by 45 Line 12 ALARM 6 1 66 Six is the preprogrammed alarm level value for this detector its value is 1 66 indicating the percent per foot obscuration value assigned to level 6 PREALARM 3 0 47 Three is the preprogrammed pre alarm level value for this detector its value is 0 47 indicating the percent per foot obscuration value assigned to level 3 Line 13 ACTION STATU...

Страница 37: ...e are displayed in this line Line 16 BACK Press to return to the previous screen 9 2 3 Multiple Event List Display Pressing the soft key to the left of the MULTIPLE EVENTS LIST message on the Main Menu brings up the Multiple Events List screen The Multiple Event List shows off normal events simultaneously in groups of eight An event is shown at the top and seven are shown in the list below it When...

Страница 38: ...vent in the event reporting format See Event Reporting Format on page 25 Line five will read PRESS ANY KEY Pressing any key will return the display to the Event Counts screen With Fire as the highest priority With MNS as the highest priority USA Event Order Canada Event Order USA Event Order Canada Event Order Fire Fire MN Alarm CO Alarm CO Alarm Fire Fire MN Alarm CO Alarm CO Alarm CO Pre alarm C...

Страница 39: ...n three seconds The following screen will appear while the LAMP TEST key is pressed Figure 9 11 Version Screen ACKNOWLEDGED FIRE ALARM ELEVATOR LOBBY EAST WING FIFTH FLOOR Z005 SMOKE PHOTO 11 57 45A TUE JAN 12 2016 N112L03D052 FIRE ALARM 0001 OF 0003 2 ALM 6FLR ELEVATOR LOBBY EAST WING 3 ALM 5FLR ELEVATOR LOBBY EAST WING 1 SUP MAIN ELEVATOR LOBBY EAST WING 2 SUP 6FLR ELEVATOR LOBBY EAST WING 1 TBL...

Страница 40: ...the factory defaults Figure 9 12 Self Test Screen 9 3 3 Download Screen The Download screen appears immediately before a download Downloading is initiated at the panel Figure 9 13 Download Menu Screen ACKNOWLEDGE Press this soft key to acknowledge troubles and silence the piezo You may use the TROUBLE scroll display key to list individual troubles BOOT 001 000 048 APP 001 000 149 SELF TEST RAM TES...

Страница 41: ...tloader downloads Downloading is initiated at the panel The progress meter shows the progress of the current download Figure 9 15 Download Bootloader Screen 9 3 6 Download Strings Screen This screen is displayed during strings downloads Downloading strings is initiated at the panel The progress meter shows the progress of the current download TROUBLE LOADING NO SERVICE A01 LCD 160 BOOTLOADER UPDAT...

Страница 42: ...results from a power interrupt during a critical period of application download The Trouble LED will flash and the piezo if enabled will sound while this screen is in effect All corrupt images will activate the corresponding system trouble Pressing the Trouble Scroll button will scroll through all system troubles Figure 9 17 Application Corrupt Screen TROUBLE LOADING NO SERVICE A01 LCD 160 BOOTLOA...

Страница 43: ...al Ratings Input Voltage 24 VDC must be non resettable Data Communications Port RDP interface power limited Class 2 Non Fire Alarm Status A Power LED is on backlight is off Number of LCD 160 modules _____ X 0 075 A _________ amps Non Fire Alarm Status B Power LED is on backlight is also on Number of LCD 160 modules assumed to have points active simultaneously _____ X 0 300 A __________ amps Total ...

Страница 44: ...display 37 Verify Count display 37 Detector information 36 37 DIP Switch see SW17 Disabled Point events and Other Event Scroll Display key 23 Display and Control Center 23 27 28 Display intensity 33 Download screens 40 41 DP DISP 13 Dress Panels 13 15 Drill and Power up screen 40 fixed function key 23 E Earth Ground 19 Electrical connections 16 18 20 Electrical ratings 43 ELR see End of Line Resis...

Страница 45: ...amming Screens 31 34 Programming Switch see also SW17 R RDP 17 18 terminal location 10 Receive Mode 29 Receive LED indicator 11 Remote Data Port see RDP S Scroll Back 39 SCROLL DISPLAY keys 23 Security events 29 event format 26 LED indicator 24 SCROLL DISPLAY key 23 Self Test Screen see Power Up Screen Service Screens 39 42 Shielding 18 Signal Silence fixed function key 23 Signals Silenced LED ind...

Страница 46: ...46 LCD 160 Manual P N 51850 D2 10 07 2016 W W Index Power limited Class 2 16 RDP 17 ...

Страница 47: ...D OR IMPLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS This document constitutes ...

Страница 48: ...World Headquarters 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www notifier com ...