Honeywell NOTIFIER FW-MM Скачать руководство пользователя страница 1

FIGURE 2. FACEPLATE INTERIOR

MAGNET LOCATION
(DO NOT REMOVE)

 

 

 C1098-00

BATTERY REPLACEMENT

Low battery levels on the wireless devices are displayed as a trouble in the 
FACP. Therefore when the message “TROUBLE BATTERY LOW” is displayed, 
replace the battery in the device. This message is an indication that approxi-
mately one week of battery life remains.

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a compatible 
Notifier system control panel (list available from Notifier).

To replace the batteries in a wireless device use the following steps:

1. Have 4 CR123A (or DL123A) batteries available
2. Remove the faceplate from the module.
3. Open the battery compartment. (See Figure 3.)
4.  Remove the used batteries and replace with new batteries. The battery com-

partment is designed such that the batteries can only align in the appropri-
ate direction. Do not force the batteries into the openings.

5. Replace the battery compartment cover.
6. Replace the faceplace.

SPECIFICATIONS

Maximum Operating Voltage: 

3.3 VDC

Maximum Current Draw: 

5.0 mA (LED on)

Average Operating Current: 

210 µA, 3.9k EOL

EOL Resistance: 

3.9K Ohms

Maximum IDC Wiring Resistance: 

10 Ohms

Maximum IDC Voltage: 

3.2 Volts

Maximum Average IDC Current: 

5.5 µA

Maximum Transmit RF Power: 

17 dBm

Radio Frequency Range: 

902-928 MHz

Temperature Range: 

32°F to 120°F (0°C to 49°C)

Humidity: 

10% to 93% Non-condensing

Battery Type:  

4 Panasonic CR123A or 4 Duracell DL123A

Battery Life:  

2 year minimum

Battery Replacement: 

Upon TROUBLE BATTERY LOW display and/or during annual maintenance

Dimensions: 

4¼ in. H x 4¼ in. W x 1½ in. D

Accessories: 

SMB500(-WH) electrical box (preferred mounting option)

BEFORE INSTALLING

This information is included as a quick reference installation guide. Refer to 
the control panel installation manual and the 

SWIFT® Wireless Manual

 for 

detailed system information. If the modules will be installed in an existing op-
erational system, inform the operator and local authority that the system will 
be temporarily out of service. Disconnect power to the control panel before 
installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION

The FW-MM(A) Monitor Module is intended for use with a wireless gateway 
or wireless fire alarm control panel (FACP) to interface with a device having 
contacts used to signal status conditions. The input to the monitor module is 
non-latching and does not require a reset. The device communicates through 
a robust, bi-directional mesh network to the gateway and/or FACP. Rotary 
dial switches are provided for setting the module’s address. The module has a 
panel controlled LED indicator. (See Figure 1.) 

FIGURE 1. CONTROLS AND INDICATORS

 

 C1095C-00

FACEPLATE

The faceplate includes a magnet for activation and tamper resistance. (See 
Figure 2.) The faceplate magnet activates communication to the panel, there-
fore, the faceplate must be installed for the module to work properly. The 
magnet also activates a supervisory tamper fault at the panel if the nameplate 
is removed. Do NOT remove this magnet. The faceplate for a wireless module 
CANNOT be replaced with the faceplate of a standard wired module.

  

I56-4067-005 

 

 7/27/2021

FW-MM(A) Wireless Monitor Module 

I56-4067-00

5

INSTALLATION AND MAINTENANCE INSTRUCTIONS

12 Clintonville Road

Northford, CT 06472-1653

Phone: 203.484.7161

Отзывы: