SPACING & MOUNTING

Notifier recommends spacing sensors in compliance with NFPA 72. In low air 
flow applications with smooth ceilings, space sensors 30 feet apart (9.1 m). When 
using the photoelectric and temperature sensors as a heat detector in FM3210 
compliant applications, space sensors 20 feet apart (6 m). For specific informa-
tion regarding sensor spacing, placement, and special applications, refer to NFPA 
72 or the System Smoke Detector Application Guide, available from Notifier.  
Duct Applications: FSP-951T-SELFT is not listed for use in ducts. 

Mounting Note: Units installed on ceilings must remain in ceiling-oriented 
position; those mounted on walls must remain in the wall orientation.

WIRING GUIDE

All wiring must be installed in compliance with the National Electrical Code, 
applicable local codes, and any special requirements of the Authority Having 
Jurisdiction. Proper wire gauges should be used. The installation wires should 
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the 
event of a fire. Please note that installation distances, wiring styles and wire 
gauge requirements may vary for Self-Test sensors in comparison to standard 
sensors, please refer to the panel's SLC Wiring documentation for further in-
formation.

Remove power from the communication line before installing sensors.

1.   Wire the sensor base (supplied separately) per the wiring diagram, Figure 2.

2.   Set the desired address on the sensor address switches, see Figure 1.

3.   Install the sensor into the sensor base. Push the sensor into the base while 

turning it clockwise to secure it in place.

4.   After all sensors have been installed, apply power to the control panel and 

activate the communication line.

5.   Test the sensor(s) as described in the TESTING section of this manual.

CAUTION

Dust covers provide limited protection against airborne dust particles during 
shipping. Dust covers must be removed before the sensors can sense smoke. 
Remove sensors prior to heavy remodeling or construction. The Self-Test func-
tion of your Notifier system can determine that all dust covers on the SLC 
have been removed when you run the Self-Test process in order to prove that 
there isn’t anything causing a potential obstruction for smoke entry.

SPECIFICATIONS

Operating Voltage Range: 

15 to 32 VDC

Operating Current @ 24 VDC:  

200 uA (one communication every 5 seconds with green LED blink on communication)

Maximum Alarm Current:  

2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)

Maximum Self-Test Alarm Current:  300 mA (Not be used for battery standby calculation as Self-Test will not work in auxiliary power mode) 
Maximum Current:  

4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)

Operating Humidity Range: 

10% to 93% Relative Humidity, Non-condensing

Operating Temperature Range: 

32°F to 115°F (0°C to 47°C)

Storage Temperature Range: 

-4°F to 140°F (-20°C to 60°C)

Air Velocity: 

0 to 4000 ft./min. (0 to 1219.2 m/min.) 

Air Velocity using Self-Test:  

0 to 300 ft./min. (0 to 304.8 m/min.) 

Height: 

2.0˝ (51 mm) installed in B300-6 Base

Diameter: 

6.2˝ (156 mm) installed in B300-6 Base; 4.1˝ (104 mm) installed in B501 Series Base

Weight: 

3.5 oz. (100 g) 

Isolator Load Rating:  

0.0063*

*Please refer to your isolator base/module manual for isolator calculation instructions.

UL 268 listed for Open Air Protection 
UL 521 listed for Heat Detectors 

This sensor must be installed in compliance with the control panel system 
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when 
installed in compliance with the National Fire Protection Association (NFPA); 
see NFPA 72. 

GENERAL DESCRIPTION

Model FSP-951T-SELFT is a plug-in type multi-sensor smoke sensor that com-
bines  a photoelectronic sensing chamber and 135°F (57.2°C) fixed temper-
ature heat detector across addressable-analog communications. The sensor 
transmits an analog representation of smoke density over a communication 
line to a control panel. Its internal Self-Test unit and beaconing capability can 
test the detector to relevant requirements of NFPA 72.

Rotary dial switches are provided for setting the sensor’s address. (See Fig-
ure 1.) The intelligent photoelectric and temperature sensors also transmit an 
alarm signal due to heat at 135°F (57.2°C) per UL 521.

FIGURE 1. ROTARY ADDRESS SWITCHES

 

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

 C0162-00

Two LEDs on the sensor are controlled by the panel to indicate sensor status. 
An output is provided for connection to an optional remote LED annunciator  
(P/N RA100Z). 

Notifier panels offer different features sets across different models. As a result, 
certain features of the photoelectric and temperature sensors may be available 
on some control panels, but not on others. FSP-951T-SELFT will support only 
FlashScan® protocol mode. The possible features available if supported by the 
control panel are:

1.   The sensor’s LEDs can operate in three ways—on, off, and blinking–and 

they can be set to red, green, or amber. This is controlled by the panel. 

2.   The remote output may be synchronized to the LED operation or con-

trolled independent of the LEDs.

3.   Devices are point addressable up to 159 addresses.

5.   Yearly maintenance, in accordance to NFPA 72, can use the built in Self-

Test functionality.

Please refer to the operation manual for the UL listed control panel for spe-
cific operation. The photoelectric and temperature sensors require compatible 
addressable communications to function properly. Connect these sensors to 
listed-compatible control panels only. 

I56-6783-000

INSTALLATION AND MAINTENANCE INSTRUCTIONS

12 Clintonville Road

Northford, CT 06472-1653

Phone: 203.484.7161

FSP-951T-SELFT  
Intelligent Photoelectric and Temperature 
Self-Test Smoke Sensor 

  

I56-6783-000 

 

 1/6/2021

Содержание NOTIFIER FSP-951T-SELFT

Страница 1: ... condensing Operating Temperature Range 32 F to 115 F 0 C to 47 C Storage Temperature Range 4 F to 140 F 20 C to 60 C Air Velocity 0 to 4000 ft min 0 to 1219 2 m min Air Velocity using Self Test 0 to 300 ft min 0 to 304 8 m min Height 2 0 51 mm installed in B300 6 Base Diameter 6 2 156 mm installed in B300 6 Base 4 1 104 mm installed in B501 Series Base Weight 3 5 oz 100 g Isolator Load Rating 0 0...

Страница 2: ...ne you must verify the completion of the visual inspection of the sensor via the App recording any remedial action required if necessary Criteria for success fully passing the visual inspections is available to review in the relevant section of NFPA 72 guidance 4 If the label of the self test sensor is incorrect you can update this on the App subject to holding the relevant user licence which will...

Страница 3: ...CATION When configured at the fire alarm control panel this detector is capable of op erating in a special application mode such that it has a higher sensitivity than is normally allowed by UL 268 for areas where early warning is important In this mode the detector does not comply with the Cooking Nuisance Smoke Test Detectors Sampling ports set to the special application mode are not suitable for...

Страница 4: ...g etc are adequately protected to avoid tampering of the system that could result in information disclosure spoofing and integrity violation FCC STATEMENT This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may caus...

Отзывы: