should be placed more than 3ft (914mm) away from any strong air source 
which is greater than 300 ft./min. (e.g. an air conditioning outlet).
Duct Applications: FSP-951-SELFT is not listed for use in ducts. 
Mounting Note: Units installed on ceilings must remain in ceiling-oriented 
position; those mounted on walls must remain in the wall orientation.

WIRING GUIDE

All wiring must be installed in compliance with the National Electrical Code, 
applicable local codes, and any special requirements of the Authority Having 
Jurisdiction. Proper wire gauges should be used. The installation wires should 
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the 
event of a fire. Please note that installation distances, wiring styles and wire 
gauge requirements may vary for Self-Test sensors in comparison to standard 
sensors, please refer to the panel's SLC Wiring documentation for further in-
formation.

Remove power from the communication line before installing sensors.

1.   Wire the sensor base (supplied separately) as shown in the wiring 

diagram. (See Figure 2.)

2.   Set the desired address on the sensor address switches. (See Figure 1.) 
3.   Install the sensor into the sensor base. Push the sensor into the base while 

turning it clockwise to secure it in place.

4.   After all sensors have been installed, apply power to the control panel and 

activate the communication line.

5.   Test the sensor(s) as described in the TESTING section of this manual.

CAUTION

Dust covers provide limited protection against airborne dust particles during 
shipping. Dust covers must be removed before the sensors can sense smoke. 
Remove sensors prior to heavy remodeling or construction. The Self-Test func-
tion of your Notifier system can determine that all dust covers on the SLC 
have been removed when you run the Self-Test process in order to prove that 
there isn’t anything causing a potential obstruction for smoke entry.

SPECIFICATIONS

Operating Voltage Range: 

15 to 32 VDC

Operating Current @ 24 VDC:  

200 uA (one communication every 5 seconds with green LED blink on communication)

Maximum Alarm Current:  

2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)

Maximum Self-Test Alarm Current:  300 mA (Not be used for battery standby calculation as Self-Test will not work in auxiliary power mode) 

Maximum Current:  

4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)

Operating Humidity Range: 

10% to 93% Relative Humidity, Non-condensing

Operating Temperature Range: 

32°F to 122°F (0°C to 50°C)

Storage Temperature Range: 

-4°F to 140°F (-20°C to 60°C)

Air Velocity: 

0 to 4000 ft./min. (0 to 1219.2 m/min.) 

Air Velocity using Self-Test:  

0 to 300 ft./min. (0 to 304.8 m/min.) 

Height: 

2.0˝ (51 mm) installed in B300-6 Base

Diameter: 

6.2˝ (156 mm) installed in B300-6 Base; 4.1˝ (104 mm) installed in B501 Base

Weight: 

3.5 oz. (100 g)  

Isolator Load Rating:  

0.0063*

*Please refer to your isolator base/module manual for isolator calculation instructions.

UL 268 listed for Open Air Protection. 
This sensor must be installed in compliance with the control panel system 
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when 
installed in compliance with the National Fire Protection Association (NFPA); 
see NFPA 72. 

GENERAL DESCRIPTION

Model FSP-951-SELFT is a plug-in type smoke sensor that combines a photo-
electronic sensing chamber with addressable-analog communications.
The sensor transmits an analog representation of smoke density over a com-
munication line to a control panel. Rotary dial switches are provided for set-
ting the sensor’s address. (See Figure 1.) 

FIGURE 1. ROTARY ADDRESS SWITCHES

 

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

 C0162-00

Two LEDs on the sensor are controlled by the panel to indicate sensor status. 
An output is provided for connection to an optional remote LED annunciator  
(P/N RA100Z). 
Notifier panels offer different features sets across different models. As a result, 
certain features of the photoelectric sensors may be available on some con-
trol panels, but not on others. FSP-951-SELFT will support only FlashScan® 
protocol mode. The possible features available in the photoelectric sensors, if 
supported by the control panel are: 
1.   The sensor’s LEDs can operate in three ways—on, off, and blinking–and 

they can be set to red, green, or amber. This is controlled by the panel. 

2.   The remote output may be synchronized to the LED operation or con-

trolled independent of the LEDs.

3.   Devices are point addressable up to 159 addresses.
5.   Yearly maintenance, in accordance to NFPA 72, can use the built in Self-

Test functionality.

Please refer to the operation manual for the UL listed control panel for specific 
operation. The photoelectric sensors require compatible addressable com-
munications to function properly. Connect these sensors to listed-compatible 
control panels only. 

SPACING AND MOUNTING 

Notifier recommends spacing sensors in compliance with NFPA 72. In low air 
flow applications with smooth ceilings, space sensors 30 feet apart (9.1 m). 
For specific information regarding sensor spacing, placement, and special ap-
plications, refer to NFPA 72 or the System Smoke Detector Application Guide, 
available from Notifier. If using the self-test application, the FSP-951-SELFT 

I56-6782-000

INSTALLATION AND MAINTENANCE INSTRUCTIONS

12 Clintonville Road

Northford, CT 06472-1653

Phone: 203.484.7161

FSP-951-SELFT  

Intelligent Photoelectric  

Self-Test Smoke Sensor

  

I56-6782-000 

 

 1/6/2021

Содержание NOTIFIER FSP-951-SELFT

Страница 1: ...ity using Self Test 0 to 300 ft min 0 to 304 8 m min Height 2 0 51 mm installed in B300 6 Base Diameter 6 2 156 mm installed in B300 6 Base 4 1 104 mm installed in B501 Base Weight 3 5 oz 100 g Isolator Load Rating 0 0063 Please refer to your isolator base module manual for isolator calculation instructions UL 268 listed for Open Air Protection This sensor must be installed in compliance with the ...

Страница 2: ...it to the system when you pair the device with the Connected Life Safety Ser vices gateway on completion of the visual inspection SELF TEST TOKENS If your license requires Self Test tokens in order to activate the Self Test pro cess please refer to your Connected Life Safety Services guides in order to purchase the required volume of tokens to complete testing on your project MANUAL TESTING A Func...

Страница 3: ...ithin the protected space a normal application detector or normal application mode must be used for that area Special application mode is not for general use and the detector may be more prone to false alarms if used in unsuitable environments While no list is all inclusive some examples of unsuitable environments for special applica tion mode are areas with airborne particulate or aerosols includ...

Страница 4: ...tected to avoid tampering of the system that could result in information disclosure spoofing and integrity violation FCC STATEMENT This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operation WA...

Отзывы: