Installation
Output Circuits
The NAC Follower input is power-limited (Class 2) (refer to Section 2.12, “UL Power-limited Wiring Requirements”, on page 42) and
supervised by the host FACP. Supervision requires that a 4.7 K
Ω
EOL resistor be connected to the last device in the NAC Follower
chain.
2.5.4 Night Ring
The external audio input allows a building’s Private Branch Exchange (PBX) to activate the NFC-50/100. Connections need to be made
to TB16 on the main control board and to TB5.1 and TB5.2 on the display board. Refer to Section 1.2.2 for electrical specifications to
the external audio input.
2.6 Output Circuits
2.6.1 Relays
MNS Active Relay - TB1
The main control board provides a Form-C MNS Active relay. The MNS Active Relay will transfer state when any Mass Notification
(MNS) event occurs. The system must be enabled for Mass Notification in programming for use of this relay.
from FACP NAC (or NAC Follower
output) or previous device
to next device
4.7K ELR needed for
last device in chain.
alarm polarity shown
TB18
1 2 3 4
Figure 2.10 NAC Follower Wiring
NFC-50/100 Main Control Board
e
c
c
tb
1
8
.w
m
f
+ -
PBX
audio out
external audio input
GND
In
contact
closure output
TB5 on display
board
TB16 on main
control board
e
c
c
tb
1
6
.w
m
f
Figure 2.11 Night Ring Wiring
Figure 2.12 MNS Active Relay
TB1
e
c
c
a
c
rl
.w
m
f
Shown in normal,
Inactive condition
Содержание Notifier FirstCommand Series
Страница 84: ...84 Notifier FirstCommand Series Manual P N LS10001 001NF E H 1 8 2018 Notes ...
Страница 86: ...Cut along dotted line ...
Страница 88: ...Cut along dotted line ...
Страница 92: ...92 Notes ...
Страница 94: ...Cut along dotted line ...
Страница 96: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...