background image

B

P/N 53232:B

ECN 14-0161

Document 53232
2/26/2014                    Rev:

Auxiliary Power Supply

APS2-6R/E

Instruction Manual

  

Содержание NOTIFIER APS2-6R/E

Страница 1: ...B P N 53232 B ECN 14 0161 Document 53232 2 26 2014 Rev Auxiliary Power Supply APS2 6R E Instruction Manual ...

Страница 2: ... adequate warning of a fire Smoke detectors cannot be expected to provide adequate warn ing of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materi als etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined r...

Страница 3: ...ds Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will not interfere with battery trans former or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage...

Страница 4: ...priate version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for printe...

Страница 5: ...s 13 3 3 4 Connecting Multiple APS2 6R Power Supplies 14 3 4 Configuring the APS2 6R 14 3 5 Servicing the APS2 6R 15 Appendix A UL 864 9th Edition Configurations 17 A 1 NFS2 3030 17 A 1 1 Connecting to the AMPS 24 and NFS2 3030 17 A 2 NFS2 640 and NFS 320 19 A 2 1 Connecting to the CPS 24 and CPU2 640 NFS 320 19 Appendix B UL 864 8th Edition Configurations 20 B 1 AFP 200 20 B 1 1 Connecting the AP...

Страница 6: ... has not been evaluated and may not comply with NFPA 72 and or the latest edition of UL 864 These applications will require the approval of the local Authority Having Jurisdiction AHJ 1 3 Compatible Equipment For a complete list of compatible devices refer to the Device Compatibility Document 1 4 Related Documentation The table below contains a list of document sources for supplemental information...

Страница 7: ...xWorks NFN Gateway Embedded Platform 52306 BACNet Gateway 51659 HS NCM Series Installation Document 54014 Notifier Device Compatibility Document 15378 Document Name Part Number CAUTION Information about procedures that could cause programming errors runtime errors equipment damage WARNING Indicates information about procedures that could cause irreversible equipment damage irreversible loss of pro...

Страница 8: ...us power Two 2 special application filtered power limited 24 VDC outputs each rated at 3A One 1 special application filtered non power limited 24 VDC output rated at 6A Immediate brownout detection default and reporting via trouble bus or relay contacts Delayed one to two 1 2 hour s or two to three 2 3 hours brownout reporting via trouble bus Battery voltage supervision Disconnect of deeply discha...

Страница 9: ... by the XPIQ transponder Cable P N 75121 only Special applications refer to Section 3 3 1 Trouble Supervision Bus J3 J4 J3 output J4 input Form A contact open collector Cable P N 71033 For trouble supervision connect cable p n 71033 from J3 to a trouble bus connection of a fire panel main power supply or J4 of another APS2 6R Sections 3 3 3 3 3 4 and A 1 1 Fuse F2 F2 Battery Supervision 32 VAC 10A...

Страница 10: ...off 42026 2 6 32 self tapping screw 38164 1 Trouble supervision cable 71033 Table 2 1 Hardware Kit Components TB3 J9 TB4 JP4 J4 J3 JP2 JP3 LED1 LED2 F2 F1 NOTE The cover has been removed for illustration purposes only Three 24 VDC output circuits One 1 non power limited Two 2 power limited Refer to the appropriate appendix for more specific information on output circuits Fuse F2 for battery protec...

Страница 11: ...in the corners of the board Set the CPU board aside in a safe clean place Avoid static discharge which may damage the board 3 Align the APS2 6R over the mounting holes of the cabinet Observe orientation of the power supply when installing it into the cabinet See Figure 3 2 below 4 Insert a self tapping screw from the hardware kit through each of the printed circuit board mounting holes threading e...

Страница 12: ... adhesive squares to secure the wiring 3 3 Wiring an APS2 6R 3 3 1 Field Wiring Output Circuit 3 J9 can be used as a source of power for the XPIQ Audio Transponder only See Section B 6 for wiring connections For primary and secondary power connections see the appropriate appendix for specific system information mounting holes AFP 200 Cabinet battery connection Screws 2 places Figure 3 2 Mounting a...

Страница 13: ...ing not exceeding 20 feet 6 1 m in length 3 3 3 Trouble Supervision Bus The APS2 6R supervises battery power If the battery voltage should drop the APS2 6R will generate and transmit a trouble to the control panel via trouble supervision cable 71033 NOTE TB4 is for UL 864 9th Edition applications only See Appendix B for UL 864 8th Edition applications and wiring TB4 JP4 J4 J3 JP2 JP3 LED2 aps26rtb...

Страница 14: ...nfiguring the APS2 6R The APS2 6R may be configured for the following No delay for reporting loss of AC power default 1 2 hour delay for reporting loss of AC power cut jumper JP2 2 3 hour delay for reporting loss of AC power cut jumpers JP2 and JP3 Figure 3 5 Wiring Multiple APS2 6R Power Supplies To trouble input on main power supply or control panel First APS2 6R Second APS2 6R Connect power as ...

Страница 15: ...erviceable part on the APS2 6R is a reverse battery protection fuse F2 If this fuse fails replace it with a fuse of the same type and rating See Section 2 3 for more information on F2 1 Turn off and remove all power sources 2 Replace fuse as required 3 Reconnect power TB3 J9 F2 F2 aps26rjf2wmf Figure 3 7 Servicing the APS2 6R ...

Страница 16: ...16 APS2 6R E Instruction Manual P N 53232 B 2 26 2014 Notes ...

Страница 17: ...S 24 6 Connect secondary power from TB3 on the APS2 6R to TB3 on the AMPS 24 7 Attach battery interconnect cable WARNING Risk of electrical shock Remove all power sources to equipment while connecting electrical components Leave the external main power breaker OFF until installation of the entire system is complete To reduce the risk of electric shock make sure to properly ground the unit Apply an...

Страница 18: ...0 Figure A 1 Wiring to AMPS 24 and NFS2 3030 FMM 1 If the SLC device does not match the one in this figure refer to the SLC manual appendix which contains wiring conversion charts for type V and type H modules LCM or LEM Non Power Limited Circuits Power Limited Circuits Non Power Limited Circuits Power Limited Circuits AMPS 24 side view AC Note Maintain 0 25 spacing between Power limited and Non p...

Страница 19: ... 320 4 Connect AC power to TB1 on the CPS 24 Make sure to properly ground the unit to the backbox 5 Connect batteries to TB3 on the CPS 24 6 Connect secondary power from TB3 on the APS2 6R to TB3 on the CPS 24 7 Attach battery interconnect cable WARNING Be sure to finish installation before applying power Test AC power before continuing 47K ELR P N R 47K SLC CPS 24 and CPU2 640 CPU 320 APS2 6R to ...

Страница 20: ... cable supplied with the AFP 200 into two pieces 5 Connect the batteries to TB3 on the APS2 6R Use wire nuts to attach one half of the battery cable to 18 AWG wire 6 Connect secondary power from TB3 on the APS2 6R to terminal block J3 and on the AFP 200 using the second piece of battery cable WARNING Risk of electrical shock Remove all power sources to equipment while connecting electrical compone...

Страница 21: ... on the MPS 400 4 Connect AC power to TB1 on the MPS 400 Make sure to properly ground the unit to the backbox 5 Connect batteries to TB1 on the MPS 400 6 Connect secondary power from TB3 on the APS2 6R to terminal block TB1 and on the MPS 400 JP2 JP7 JP5 SW3 SW2 JP3 JP9 JP1 JP6 Figure B 1 Wiring to AFP 200 aps26rafp200 wmf Power limited circuit Non power limited circuits grounding stud BB 17 Backb...

Страница 22: ... primary power from TB1 on the APS2 6R to MPS 24A terminal block TB1 Pin 5 NEUT and Pin 7 HOT 4 Connect AC power to TB1 on the MPS 24A Make sure to properly ground the unit to the backbox 5 Connect batteries to TB2 on the MPS 24A 6 Connect secondary power from TB3 on the APS2 6R to MPS 24A terminal block TB2 Pin 1 and Pin 2 J4 Note Maintain 0 25 spacing between Power limited and Non power limited ...

Страница 23: ...Make sure to properly ground the unit to the backbox 5 Connect batteries to TB3 on the MPS 24B RB 6 Connect secondary power from TB3 on the APS2 6R to MPS 24B RB terminal block TB3 Pin 1 and Pin 2 P4 P3 JP5 TB1 TB2 F1 CB1 P5 R27 P2 EARTH GND AC NEUTRAL AC HOT 24R COMMON 24 COMMON POWER LIMITED BAT BAT Note Maintain 0 25 spacing between Power limited and Non power limited wiring Install tie wraps a...

Страница 24: ... primary power from TB1 on the APS2 6R to TB2 on the CPU 640 4 Connect AC Power to TB2 on the CPU 640 Make sure to properly ground the unit to the backbox 5 Connect batteries to TB1 on the CPU 640 6 Connect secondary power from TB3 on the APS2 6R to TB1 on the CPU 640 Note Maintain 0 25 spacing between Power limited and Non power limited wiring Install tie wraps and adhesive squares to secure the ...

Страница 25: ... 6R to TB3 on the AMPS 24 4 Connect AC power to TB3 on the AMPS 24 Make sure to properly ground the unit to the backbox 5 Connect batteries to TB4 BAT IN and TB5 BAT IN respectively on the AMPS 24 6 Connect secondary power from TB3 on the APS2 6R to TB4 BAT OUT and TB5 BAT OUT respectively on the AMPS 24 Note Maintain 0 25 spacing between Power limited and Non power limited wiring Install tie wrap...

Страница 26: ...n power limited power See the XPIQ Instruction Manual for information 4 Connect primary power from TB1 on the APS2 6R to TB1 on the XPIQ PS 5 Connect AC power to TB1 on the XPIQ PS Make sure to properly ground the unit to the backbox 6 Connect batteries to TB2 on the XPIQ PS 7 Connect secondary power from TB3 on the APS2 6R to TB2 on the XPIQ PS Note Maintain 0 25 spacing between Power limited and...

Страница 27: ...Phone 1 Phone 2 Phone 3 Phone 4 Spkr4 TB9 2 X 2W 2 X 2W 1 X 4W 1 X 4W OUT SHLD 1 2 3 4 5 6 S S S S 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 TB3 J9 TB4 JP4 J4 J3 JP2 JP3 LED1 LED2 F2 F1 15 BATTERY AC GND NEUT HOT CONTROL INTERFACE POWER FOR XPIQ MB F2 J2 J1 Note Maintain 0 25 spacing between Power limited and Non power limited wiring Install tie wraps and adhesive squares to secure the wiring APS2 6R to batte...

Страница 28: ...28 APS2 6R E Instruction Manual P N 53232 B 2 26 2014 Notes ...

Страница 29: ...to MPS 24A 22 to MPS 24B RB 23 to MPS 400 21 to NFS 320 19 to XPIQ 26 CPS 24 19 CPU2 3030 17 CPU2 640 19 CPU 3030 25 CPU 320 19 CPU 640 24 E earth ground 9 F features of the APS2 6R 8 field wiring 12 FMM 1 13 17 19 fuse 9 10 15 H hardware kit 10 HS NCM Series 7 I ICE 4 27 ICM 4 27 IPDACT Internet Protocol DACT 6 J JP2 jumper 10 JP3 jumper 10 jumper 14 L LCD 160 6 LCD 80 6 LED status indicators 10 ...

Страница 30: ... 1 Remote Microphone 7 S secondary power 17 19 20 21 22 23 24 25 26 shunt 20 21 22 23 24 25 26 SLC 13 17 19 specifications 9 output circuits 9 primary power 9 secondary power circuit 9 status indicators 10 System 5000 6 22 T trouble bus 8 9 10 13 17 19 20 21 22 23 24 25 26 W wiring 12 wiring multiple 14 X XP Series Transponder 6 XP5 Series Transponder 6 XP6 Transponder 6 XPIQ Transponder 6 12 26 ...

Страница 31: ...MPLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS This document constitutes the on...

Страница 32: ...World Headquarters 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www notifier com ...