3.2.3 Define Sounder Tone Slots
This configuration option applies to OPAL
protocol loop sounder/strobe devices only.
The device sounder tone and volume setting
is normally configured using the device’s DIP
switches located on the base of the device.
However, the panel can override the DIP switch
settings by setting up a maximum of 8 sounder
tone slots from the 32 available with these
advanced electronic-type sounders. Once
configured, these tone slots can be selected
as part of a Control Matrix output rule.
From the ‘System Parameters’ menu select
the ‘Select Custom Tone’ option. Next, a
screen listing eight available tone slots is
displayed with the first slot highlighted.
Tone slots can be configured individually,
leaving gaps if so desired, or as an entire
group of 8. If individual tone slots are to be
configured these must first be selected in the
list. If configuring all eight tone slots it is not
important which tone number is highlighted
(tone slot 1 is highlighted by default); however,
if less than 8 custom tones are selected the
first and subsequent slots numbers are ‘taken’.
Note:
See overleaf for details about
precedence rules.
To configure the tone slots select ‘Get Pre-
Define Tones’ in the top-left hand corner of
the Define Custom Tones screen.