ID3000/ID2000 Fire Panel Configuration Tool Manual
Loop Devices
3 - 18
997-291, Version 3.05
November 2010
10v
function is not selected, the default rate is
used (1 second on, 1 second off).
Note:
If the loop is heavily loaded with devices
(especially sounders), select one of the
Slow Pulse options to ensure adequate
synchronisation of the sounders.
iv
Priority Scan
- edit as for sensors.
If CDI or
ZMX modules are used to connect
conventional MCPs
: to meet the response
time specified in BS5839 Part 1 para. 20.2(b),
set these modules to priority and do not
exceed 21 priority devices per loop.
v
Not Synchronised
(CLIP loops only). Option
for modules of type BELL only. Allows the
selection of individual sounders to be
excluded from the panel global setting of
PULSING (refer to
Tab). This is a useful way to exclude any
sounders that are not enhanced protocol-
compatible so that they can be configured as
not
synchronized. This action must be taken
even if these sounders are never to be
included in a Control Matrix PULSING rule.
Upon selection of the ‘Synchronize
Sounder(s)’ or ‘Unsynchronize Sounder(s)’
option while editing devices of type BELL, the
tool automatically displays the ‘Other
Functions’ column to confirm the change of
device status. A
synchronized
status is the
default once the global option is set and,
consequently, selecting ‘Synchronize’ will clear
the
unsynchronized
status of any selected
device(s), if changed to
unsynchronized
at an
earlier time.
10iv
10iv