ID3000/ID2000 Fire Panel Configuration Tool Manual
Loop Devices
3 - 17
997-291, Version 3.05
November 2010
8
9
8 O/C
. Set the module’s open-circuit (O/C)
supervision option ON or OFF. For CMX
modules used as outputs and with disabled
supervision (see data sheet) and for
CMX-10R modules, O/C supervision must
be set to off, otherwise these modules will
remain in an O/C fault condition.
9 Fire/Fault Delay
. Enter the required delays
(the defaults are given opposite). If a
module is walk-tested, the delay is ignored.
Note:
You are advised to retain a delay on the S/C
and O/C fault events (the same parameter
is common to both) to allow for module
‘settling’ time, especially after power-up. If
S/C monitoring is off, do not set a fire delay
unless the equipment function makes this
necessary, and
never
for an MCP. If it is on,
a fire delay of 1 second is recommended to
stop the transition of an S/C through fire
being reported as a fire alarm.
10
Other Functions (press F2 to display the
Other Functions window, which contains
parameters applicable to the module).
i
LED Blink
(ID3000 only) - edit as for sensors.
ii
Silenceable/Non-Silenceable
. For CMX
modules of types BELL and CTRL. If Non-
silenceable is selected, the output is not
switched off when the panel’s SILENCE/
RESOUND pushbutton is operated to
silence the sounders (default is Silenceable).
iii
Slow Pulse
(CLIP loops only). For CMX
modules of types BELL and CTRL.
Determines the pulse rate if the module is
set to pulse by the Control Matrix
(
the output will pulse at the user-defined
10
VERIFICATION DELAYS - MODULES
Device Type
Default
Maximum
Fire Alarm
MCP, CDI,
ZMX, CTRL
0
2
Monitor
1
100
Sprinkler monitor 40
100
Fault (S/C, O/C)
All modules
20
100
10i
10ii
10iii