ID3000/ID2000 Fire Panel Configuration Tool Manual
Loop Devices
3 - 14
997-291, Version 3.05
November 2010
None: No effect
default).
0-7: Select the
a p p r o p r i a t e
application number in
order to reduce false
alarms from the
typical nuisance
environments listed.
Application Numbers for SMART Sensors
To further minimise false alarms SMT4 devices
with OPAL Protocol may be configured to work
more effectively in different types of ‘nuisance’
environment. This is achieved using sensitivity
presets called ‘application numbers’. Each
application number corresponds to a different
combination of sensitivity level settings of the
various detection elements of the sensor,
expressed using the range of values ‘0 - 7’ for
active profiles and ‘None’ for the ‘no effect’
setting (default).
By default, when selecting a SMART 4 device
type this function is inactive and a setting of
‘None’ is indicated.