ID3000/ID2000 Fire Panel Configuration Tool Manual
Panel Settings
2 - 6
997-291, Version 3.05
November 2010
2.3
Port/Printer Options Tab
Edit as follows:
1
If a P40 printer is installed, select which port
it is connected to, otherwise select None.
2
If a third party link is used to interface the
panel with customised automatic
equipment, e.g. a computer, select which
port it is connected to (None = no link).
Details of the protocol used are available
from NOTIFIER.
3
If a third party link is used, check the Enable
CONTROLS box if the panel will accept
Mute Buzzer, Evacuate, Silence Sounders,
Reset, Test and Disablement signals from
the external equipment, or leave unchecked
if it will not.
EN54 - Do not check this box.
4
If a third party link is used, check the Monitor
FAULTS box if the data link is continuously
monitored (a fault is reported by the panel if
the link fails), or leave unchecked if not.
5
Select the version of Protocol to be used
(fixed at version 11 if ID
2
net network is used).
6
Select whether a request to the external
equipment to suspend communications is
subject to a time limit (0=no limit). If
communications are not restored within the
entered time, the panel reports a fault.
7
Select Full or Half Duplex (applies to Isolated
Port only).
1
2
3
4
6
7
If P40 is set to Diagnostic,
this port must be reconfigured
at the panel before it can be
used again with the Tool.
Enable CONTROLS -Do not
check this box. Some 3rd party
signals may contravene EN54
5