72
NFS2-3030 Programming Manual —
P/N 52545:K1 03/20/2012
Alter Status
Disable/Enable
4.2 Disable/Enable
A point can be disabled or enabled using this screen. Press the
DISABLE/ENABLE
soft key at the
Alter Status screen to display the following.
Figure 4.3 Disable/Enable Screen
Soft Keys
DISABLE/ENABLE
Only the applicable command will display. Press to disable an installed,
programmed point, or to enable a disabled one.
Group Zone Disable - This term refers to the disabling (or enabling) of a general zone. If the
first position in a device’s zone map matches the general zone number entered at this screen,
that device will be disabled (or enabled).
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A T U E J A N 2 5 , 2 0 1 1
D I S A B L E / E N A B L E : N 1 1 4 L 0 3 D 0 5 2
A U T O M A T I C I N A C T I V E
E L E V A T O R L O B B Y E A S T W I N G
F I F T H F L O O R Z 0 0 5 S M O K E ( P H O T O )
V A L U E S : 0 1 1 % O F A L A R M , 0 4 5 % O F P R E A L A R M
D I S A B L E B A C K
!
CAUTION:
WHEN A DISABLED OUTPUT IS ENABLED, IT WILL BE AFFECTED BY CONDITIONS EXISTING
IN THE SYSTEM THAT WOULD NORMALLY AFFECT IT. THAT IS, IF A CONDITION EXISTS
THAT WOULD HAVE TURNED THE OUTPUT ON WERE IT ENABLED, IT
WILL
TURN ON WHEN
IT IS ENABLED.
NOTE:
When an input or output point associated with releasing functions is disabled, a single
supervisory trouble will be generated.
!
WARNING:
DO NOT RELY ON DISABLE TO DISABLE RELEASING POINTS DURING TESTING. RELEASING
POINTS MUST BE PHYSICALLY DISCONNECTED.