40
NFS2-3030 Programming Manual —
P/N 52545:K1 03/20/2012
Program
Panel Program Menu (2)
Soft Keys
LOOP
SELECTION:
Pressing this soft key will invoke the cursor at the underlined field. Enter the
loop number desired (
01
through
10
) in the yy of the Lyy format.
NEXT/PREVIOUS
SELECTION:
Press either key to go forward or back through the loop
selections.
ACCEPT:
Press to proceed to the Loop Point Programming screen.
Loop Programming
Figure 3.27 Loop Programming Screen
Soft Keys
INSTALLED:
Press this soft key to choose YES or NO, depending on whether an SLC is installed
at this address.
DETECTOR
POLL:
Press to select loop-polling mode. (See note below.)
MODULE
POLL:
Press to select loop-polling mode. (See note below.)
RAPID
POLL:
For CLIP mode only - enable or disable Rapid Poll for CLIP. This feature will poll
the first 20 modules more often to speed response on manual pull stations.
WIRING
STYLE:
Press to select the NFPA wiring style (4 or 6) of the loop. If Style 6 is entered
when the wiring is Style 4, a trouble message will be generated at the panel.
BLINK
MODE:
Press to enable (
ON
) or disable (
OFF
) detector LED blinking for this loop. If the
Loop is configured in FlashScan mode with Blink Mode enabled, all detector and module LEDs
will remain OFF. If the loop is configured in CLIP mode with Blink Mode enabled, the LEDs for
detectors and monitor modules will remain OFF while the control modules operate normally.
L O O P C O N F I G U R A T I O N
I N S T A L L E D : Y E S B L I N K M O D E : _ O N
D E T E C T O R P O L L : C L I P
M O D U L E P O L L : C L I P
R A P I D P O L L : E N A B L E D A C C E P T
W I R I N G S T Y L E : 6 B A C K
NOTE:
FlashScan and CLIP Mode
Most FlashScan devices can be programmed to run in either CLIP or FlashScan mode. The types
cannot be mixed on a loop: for example, if Loop 1 is programmed with a FlashScan module poll,
CLIP modules may not be used on that loop.
A detector’s LEDs will light a steady green for several seconds while it is subjected to a detector test
during FlashScan polling. Each detector is tested this way on a regular basis. During the short time
the LEDs are on steady, the detector is not providing fire protection.